CompAir DELCOS XL Series Quick guide

GB ZS1091756 / 01 - October 2013
Translation of the original operating
instructions
Compressor controller
DELCOS XL / DH-Series

Contents
2 / 80 GB October 2013
CONTENTS
1 Foreword........................................................ 3
1.1 About these operating instructions............3
1.2 Intended use............................................. 3
1.3 Intentional misuse..................................... 3
1.4 Service...................................................... 3
2 Safety conditions.......................................... 4
2.1 Identification of safety instructions............ 4
2.2 Safety sign................................................ 4
3 Control panel and control............................ 8
3.1 General handling / entry of
parameters................................................ 8
4 Menus........................................................... 10
4.1 Menu Structure....................................... 10
4.2 Menu "Home"..........................................10
4.3 Pictogram................................................ 14
4.4 Menu "Trends"........................................ 14
4.5 Menu "Settings"...................................... 16
4.6 Menu "Fault History".............................. 20
4.7 Menu "Access Code"............................... 20
5 Configuration...............................................22
5.1 Choose Language...................................22
5.2 Inverting the screen output..................... 22
5.3 Setting the date and time........................22
5.4 Setting the measurement units............... 23
5.5 Advanced Settings.................................. 25
5.5.1 Setting the pressure bands.....................25
5.5.2 Programming Inputs and Outputs........... 27
5.5.3 Timer control operation...........................31
5.5.4 Programming dryer pre-run time.............35
5.5.5 Configuring RS484 communication.........36
5.5.6 Setting automatic restart after a power
failure.......................................................37
5.5.7 Setting Remote Start and Stop............... 38
5.5.8 Remote Load and Off-Load (FS)............ 39
6 Operations................................................... 40
6.1 Stopping the compressor in an
emergency...............................................40
6.2 Starting the compressor..........................40
6.3 Start Inhibits............................................ 40
6.4 Operations...............................................41
6.5 Operating Modes.................................... 41
6.6 Water circuit control................................ 41
6.7 Stopping the compressor........................ 42
6.8 Operational monitoring............................42
7 Troubleshooting.......................................... 43
7.1 Troubleshooting check list...................... 43
7.2 How the Fault and Warning Codes are
Structured................................................43
7.3 Troubleshooting.......................................44
8 Advanced operation....................................53
8.1 Maintenance Level..................................53
8.2 Additional maintenance level graph
screens....................................................53
8.3 Resetting the statistics on-load hours..... 54
8.4 Setting the service interval......................54
8.5 Data logging............................................55
9 Setting Up a Replacement Controller........57
9.1 The Setup Code and Compressor
Identification Number.............................. 57
9.2 Setting up a replacement controller........ 57
10 Base Load Sequencing (BLS)....................60
10.1 Base Load Sequencing...........................60
10.2 Supported slave controllers.................... 60
10.3 Menu "Base Load Sequencing"............... 61
10.4 Compressor Status Messages................63
10.5 Compressor settings and information..... 64
10.6 Base Load Sequencing Settings.............65
10.7 BLS function description......................... 67
10.8 Trend and statistics graphs.....................68
10.9 RS485:3 module installation................... 69
10.10 Installing the compressor module
(STD).......................................................70
11 Appendix...................................................... 75
11.1 Status messages.................................... 75
11.2 Settings................................................... 76

Foreword 1
October 2013 GB 3 /80
1 FOREWORD
1.1 About these operating
instructions
These operating instructions contain information
about controllers for fixed speed or variable speed
compressors and water- or air-cooled compres-
sors.
Special sections are labelled accordingly:
(FS) (fixed speed); for fixed speed compres-
sors
(RS) (regulated speed); for variable speed
compressors
(A) (air); for air-cooled compressors
(W) (water); for water-cooled compressors
All the inputs shown (parameters, settings and
configurations) are examples and do not apply to
a special application. They are not specific values
for your particular model of compressor.
The controller DELCOS XL is exclusively intended
for use with series DH compressors from Gardner
Denver.
These operating instructions are valid for the con-
troller DELCOS XL from software version DXL-
DH(RS)-1.0x.
Personnel Requirements
Only appointed personnel may work on the con-
troller and the compressor. The personnel have
been trained and briefed about the compressor.
The responsibilities of the personnel for operation,
maintenance and repair must be clearly defined.
The safe and hazard-aware working of the person-
nel must be checked regularly.
Personnel who are to be trained in, taught about
or instructed as part of a general training course,
must only work on the controller and compressor
under the constant supervision of an authorised
person.
If safety-relevant changes are made to compres-
sor or arise in its operating behaviour, the com-
pressor must be immediately shutdown and the
fault reported to the responsible post/person.
Faults, especially those that could impair safety,
must be immediately rectified. Otherwise the com-
pressor must not be operated.
Work on the electrical equipment may only be car-
ried out by a skilled electrician in accordance with
electrical engineering rules and regulations.
Reference documents
These operating instructions only describe the
DELCOS XL controller.
The operating instructions for the compressor
must be observed in addition to these operating in-
structions.
1.2 Intended use
The controller DELCOS XL installed is exclusively
intended for use with series DH compressors from
Gardner Denver.
1.3 Intentional misuse
Only changes authorised by Gardner Denver may
be carried out on the controller, both where soft-
ware and hardware are concerned.
1.4 Service
If you have any questions about or problems with
the compressor please contact your responsible
Gardner Denver agency.
The trained specialised personnel will ensure you
receive quick and proper assistance.
In case of queries
If you have a query or wish to make a spare parts
order, please specify the identification number and
year of manufacture on the name plate. Specifi-
cation of this data will ensure that you receive the
correct information and/or spare parts.
Your Gardner Denver Deutschland GmbH
agency
Please enter the details of your local Gardner
Denver agency in the following table.
Name:
Contact:
Address:
Phone
Fax
Email:
Chart 1-1: Local Gardner Denver agency

2 Safety conditions
4 / 80 GB October 2013
2 SAFETY CONDITIONS
Gardner Denver Deutschland GmbH accepts no
responsibility for material damage or injuries that
arise from non-observation of safety conditions or
the failure to observe normal levels of care and at-
tention, even where this is not expressly stated in
these operating instructions.
The operating instructions for the compressor
must be observed in addition to these operating in-
structions.
2.1 Identification of safety
instructions
Within the operating instructions, safety instruc-
tions are used as special warnings with the follow-
ing described names and symbols.
These special warnings are intended to prevent
danger and are located close to the possible dan-
ger both in terms of space and time:
on the system close to the danger source
in the operating instructions, before a sequence
of actions / activity is described
Structure of safety instructions
The special warnings in the operating instructions
are structured as follows:
DANGER WORD
Safety sign
Danger (danger sequence)
Description of the danger (danger
source)
Protective measure (danger pre-
vention)
Parts of safety instructions
Danger (danger sequence): The danger se-
quence names the type of hazard.
Description of the danger (danger source): The
danger source names the cause of the hazard.
Protective measure (danger prevention): Dan-
ger prevention describes the measures for com-
batting the hazard.
Danger word: The danger word subdivides the
severity of the danger into four steps, graphically
highlighted by different colours. The danger word
is used in the safety instructions as described be-
low.
DANGER indicates a directly dangerous situa-
tion which, if not protected against, could result in
death or serious (irreversible) injuries.
WARNING indicates a potentially dangerous situa-
tion which, if not protected against, could result in
death or serious (irreversible) injuries.
CAUTION indicates a potentially dangerous situa-
tion which, if not protected against, could result in
minor or less serious (reversible) injuries.
ATTENTION indicates information or recommen-
dations that directly or indirectly concern the safety
of persons or system protection.
2.2 Safety sign
The following safety signs (danger signs) may be used in the surroundings of the compressor and in the
operating instructions.
Safety sign Meaning Use / Behaviour
General danger Warning of a general danger.
Observe the warning and proceed with the necessary
caution (e.g. protective clothing) or care.
Risk of slipping Warning against the risk of slipping.
Caution during walking, running or climbing.
Chart 2-1: Safety sign

Safety conditions 2
October 2013 GB 5 /80
Safety sign Meaning Use / Behaviour
Pressurised part or sys-
tem
Identification of devices or rooms in which there is per-
manently or occasionally a significantly higher air pres-
sure than in the normal atmosphere.
Do not open the devices or rooms before pressure
equalisation has taken place.
Never operate the com-
pressor with open doors
or loose enclosure pan-
els.
Running the compressor with open doors or loose enclo-
sure panels is forbidden except during test runs. High
sound pressure level, risk of injury!
Normal operation only with closed enclosure.
Do not breath in any
compressed air from this
system
Use of the compressed air produced by this compressor
as breathing air is forbidden. Drawn in substances could
be harmful to health.
Do not use compressed air as breathing air.
Electrical voltage Warning of dangerous, electrical voltage.
Only a qualified electrician following electrotechnical reg-
ulations may carry out work on the electrical equipment
of the compressor.
System runs on After pressing of the stop button <O>, the compressor
runs on for 30 seconds.
Do not open the compressor enclosure before the com-
pressor is stationary.
Observe the instruction
manual
Identification of operating instructions where additional
information is to be found in the operating instructions (of
the manufacturer).
Before the device is operated, the operator (user)
must have read and understood the instruction manual
(manufacturer's usage instructions).
Wear ear defenders Identification of areas with a heightened sound pressure
level.
Only enter the area wearing suitable ear defenders.
Warning against indus-
trial trucks
Warning of in-plant industrial trucks (e.g. forklifts) trans-
porting materials.
Do not carry out any work on traffic ways that cannot
be seen to be clear and are not made safe or blocked
off. Use or crossing of this traffic way can only be imple-
mented with great care.
Warning against sus-
pended loads
Warning of suspended loads being transported.
No person may remain in the danger area during trans-
port. In particular, do not encroach into the area under
the raised compressor or place your feet beneath it.
Chart 2-1: Safety sign

2 Safety conditions
6 / 80 GB October 2013
Safety sign Meaning Use / Behaviour
Warning against moving
machine parts
During maintenance work it is necessary to check some
functions with an opened enclosure. There is a risk of
injury due to rotating or translational movements.
Maintenance work must only be carried out by specially
trained personnel.
Warning of hand injuries Danger that the hands could be crushed, drawn in or
otherwise injured.
Maintain a safe distance.
Warning of automatic
start-up
In normal operating mode, the compressor may start up
automatically at any time. The readiness for operation
of the compressor is indicated by the green LED on the
control panel.
Do not carry out any work on the compressor, if the
green LED illuminates.
Warning of hot surfaces Parts of the compressor become very hot during opera-
tion (up to 235 °C). Risk of injury due to hot surfaces.
Before starting any maintenance and repair work, the
compressor must be sufficiently cooled.
Warning of suffocation Risk of suffocation due to inadequate ventilation and
extraction in the compressor room.
The operator must provide adequate ventilation of the
compressor room.
Warning of crushing haz-
ards
Warning of crushing hazards due to working materials
(e.g. a machine) or a structural element (e.g. covers,
enclosure panels, protection devices, boundary fences).
When working on the identified workstations, increased
awareness is necessary.
Remaining under the
load is forbidden
It is not permitted to remain under a suspended load.
The driver is not permitted to drive the industrial truck if
there is a person beneath the load. Moreover, the dri-
ver is obliged to check that persons do not stand or walk
under the load.
The load must only be transported so that it is sufficiently
clear of the ground (max. 0.5 m above the ground). (In
Germany, refer to the law BGV D27 "Industrial trucks").
The driver of an industrial truck is responsible for all dri-
ving and load movements.
Lifting point Identification of the lifting points.
Only the indicated lifting points may be used for trans-
port.
Chart 2-1: Safety sign

Safety conditions 2
October 2013 GB 7 /80
Safety sign Meaning Use / Behaviour
XX bar
Safety valve Opening pressure of the safety valves (values "xx" see
sticker on the control panel).
Check the connecting
terminals and tighten if
necessary. For additional
information see the oper-
ating instructions.
Warning against loosened connecting terminals. The
clamping pressure can be released after some time.
Regularly check the terminals according to the safety
guidelines and retighten as necessary.
10 min
Electrical voltage
Residual voltage of the
capacitors
Warning of dangerous, electrical voltage.
Warning of electrical energy stores in the form of capaci-
tors. These can conduct a life-threatening electrical volt-
age.
Only open the switch cabinet (RS compressor) 10 min-
utes after switching the compressor off (zero volts).
Check the DC bus voltage of the frequency converter at
the mains connection strip of the frequency converter.
The precise position of the terminals "DC+" and "DC-"
can be taken from the supplied frequency converter
operating instructions.
Only a qualified electrician following electrotechnical reg-
ulations may carry out work on the electrical equipment
of the compressor.
Spring tension Warning of tensioned spring inside the suction regulator.
Before opening the suction regulator read the repair
manual.
Risk of microbe contami-
nation
Warning against legionella contamination of the cooling
water if an open cooling circuit is used.
Constant monitoring of the cooling water by the mainte-
nance personnel.
Attention: hot liquid Warning against hot oil or hot coolant.
Before opening coolant circuits, allow the compressor to
cool.
Chart 2-1: Safety sign
NOTE
All danger signs must be complete and legible.
Check regularly and replace if necessary.

3 Control panel and control
8 / 80 GB October 2013
3 CONTROL PANEL AND
CONTROL
Fig. 3-1: Control panel
[1] Touchscreen display
[2] Start button < I >
[3] Stop button< O >
[4] Red LED
Slow flashing: Warning
Fast flashing: Fault
[5] Yellow LED
Slow flashing: Maintenance necessary
[6] Green LED
Lit up permanently: System in operation
Flashing: System on standby
[7] Pushbutton <Emergency-stop>
About the compressor controller
Essentially, the controller regulates:
compressor starting and stopping
speed control (RS) and switching the compres-
sor between on-load and off-load in response
to variations in air demand
the monitoring of various operating parameters
such as pressures and temperatures
display of any warning/fault messages and au-
tomatic shut-down in the event of a fault
data entry for adjustment of various operating
parameters
keeping track of scheduled maintenance of the
compressor.
3.1 General handling / entry of
parameters
Input menus
If it is necessary to adjust parameters in a menu or
make other entries, the corresponding input menu
is always displayed.
The input menus are, as far as possible, self-ex-
planatory.
Selection
If it is only possible to choose between fixed de-
fined values for entry, the corresponding selection
input menus are displayed.
Control
Operating Mode
OK
Continuous Operation
Cancel
Automatic Operation
Fig. 3-2: "Selection" input menu, example "Operating
Mode"
Control
Remote Start Enabled
OK
On
Cancel
Off
Fig. 3-3: "Selection" input menu, example "Remote Start
Enabled"
If necessary, the input menus are supplemented
with an explanatory text.
Control
Periodic Start-Up
OK
Every 24 hours
Cancel
Never
Periodically starts
the motor for a few seconds.
Fig. 3-4: Input menu with an explanatory text

Control panel and control 3
October 2013 GB 9 /80
Parameters
If parameters must be entered, an appropriate soft
keypad is displayed. Alongside the statement of
the parameter that can be entered by the input,
the possible adjustment range is displayed.
Control
- Max. Power Loss Time
Setting Range
OK
Cancel
Fig. 3-5: Soft keypad
Additional information
Where necessary, information about a particular
menu is given.
Timer Control
Select a Setting
Date and Time
Timer Start/Stop
Timer Pressure Band p2
Display / Adjust
Display / Adjust
OK
This page is to set the Timer Channel
only. The Timer for
Compressor Start/Stop or activating the
second Pressure Band must be enabled
within Setpoints Menu.
Fig. 3-6: Menu with additional information
Access Code
Input menus for access codes always have an in-
dication about the status of the current access au-
thentication.
Access Code
Input Access Code
Status:
User Settings
Unlocked
Fig. 3-7: Access code input menu
Arrow keys
If the content of a menu does not fit on the display,
arrow keys are displayed with which the menu
content can be scrolled through.
Control
Select a Setting
OK
8.0 bar
Automatic Operation
Off
Off
Off
p2 Timer Enabled
Timer Control Enabled
Remote Start Enabled
p2 Target Pressure
Operating Mode
Fig. 3-8: Menu with arrow keys

4 Menus
10 / 80 GB October 2013
4 MENUS
4.1 Menu Structure
Home
On-Load
0rpm
260
Hours Run
Hours On-load
Hours to next Service
Remote Start Enabled
Timer start enabled
Auto. Restart Enabled
(1) Home
(2) Trends
Statistics on-load hours
Statistics Weekly Profile
Volume flow
Network pressure
Motor Speed (RS)
(3) Settings
Hour Meters
Control system
Timer Control
Programmable Inputs and Outputs
Communication
Configuration
Factory Settings
SD-Card
(4) Fault History
List of alarms with display of
Alarm details
(5) Access code
Input menu
„
Input Access Code“
(6) Base Load Sequencing (optional)
2
3
4
5
6
1
Date and time / language selection
Operating display (pictogram with
measurement and setpoints)
Status-/ message area
Hours run / service hours
Status switch on functions
Switch on/off base load sequencing
Settings:
- Setpoints
- Behavior
- Timer control
- Configuration
Additionally under the maintenance level:
- Final compression pressure
- Output temperature
- Heatsink temperature (RS)
- VSD Output Current (RS)
Additionally in base load sequencing:
- Volume Flow (BLS)
- Statistics Weekly Profile (BLS)
S
Water circuit control
Fig. 4-1: Menu Structure
4.2 Menu "Home"
The menu "Home" is the basic screen that is displayed during normal operation.
It is called via the <Home> tab.
If no entry is made for five minutes, this menu appears automatically.

Menus 4
October 2013 GB 11 /80
Hours On-load
Home
Hours Run
Hours to next Service
Remote Start Enabled
Timer start enabled
Auto. Restart Enabled
1
2
3
4
5
6
7
8
9
10
On-load 2600rpm
Mo.
Fig. 4-2: Menu "Home"
[1] time and date [6] Status-/ message area
[2] Direct access <"Language selection"> [7] Status switch on functions
[3] Volume flow [8] Tabs
[4] Network pressure [9] Service information
[5] Pressure band [10] Pictogram
[1] Date / Time
Display of the current date and time.
[2] Direct access <"Language">
Tapping the globe symbol opens the menu
"Choose Language" directly. See also the chapter
"Configuration / Set language".
[3] Volume flow
Display of the currently supplied volume flow.
The current volume flow is calculated based on
the motor speed (RS) and the delivered air quanti-
ties set in the menu "Configuration".
[4] Network pressure
Display of the current air pressure in the com-
pressed air network.
[5] Pressure band
Display of information about the current pressure
band, within which the compressor attempts to
maintain the set air pressure in the compressed
air network. See chapter "Configuration / Set pres-
sure bands".
123
4
Fig. 4-3: Information about the current pressure band
[1] Current pressure band
[2] International pressure symbol
[3] Upper pressure value
[4] Lower pressure value
[5.1] Current pressure band
Display of the currently used pressure band.

4 Menus
12 / 80 GB October 2013
"p1" is the normal pressure band that is used as
standard.
"p2" is a second pressure band that can be used
if a different line pressure is required. The second
pressure band can be switched to using the inte-
grated timer control (see chapter "Timer control
operation") or using an external contact (see chap-
ter "Programmable Inputs and Outputs".
[5.3] Upper pressure values
The air pressure at which the controller switches
the compressor to off-load operation (RS: The
drive motor runs at minimum speed). The run-on
timer is activated and the compressor switches in
"x" seconds to standby mode, if no pressure de-
mand is applied before the end of the run-on time.
[5.4] Lower pressure values
RS: "Target pressure"; Air pressure which the
controller attempts to maintain.
FS: "Cut-In Point."; Air pressure at which the con-
troller switches the compressor to on-load opera-
tion.
NOTE
If the pressure band is controlled via other
sources, this is indicated by symbols.
Symbol Explanation
Control of the pressure band via
the RS485:1 port (RS)
Control of the On-/Off-load com-
mands via the RS485:1 port (FS)
Control of the pressure band via
the optional base load sequencing
function.
Chart 4-1: Symbols when using other pressure band
sources
[6] Status-/ message area
The status of the compressor is indicated in the
top row in defined status messages.
Compressor warnings are displayed in the bottom
row.
The possible status warnings and explanations are
summarised in a table in the appendix to these op-
erating instructions.
[7] Status switch on functions
The following switch on functions are available:
Remote Start
Timer Control
AutomaticRestart
[7.1] Status remote start
The status of the switch on functions is indicated
in the checkbox.
I: Remote start activated. Remote start possible.
O: Remote start deactivated. No remote start pos-
sible.
Details and setting, see chapter "Configuration /
Advanced Settings".
[7.2] Status timer control-start
The status of the timer control enable is indicated
in the checkbox.
I: Timer control activated. Start/Stop via timer con-
trol possible.
O: Timer control deactivated. No Start/Stop via
timer control possible.
Details and setting, see chapter "Configuration /
Advanced Settings".
[7.3] Status Auto. Restart Enabled
The status of the function "Auto. Restart Enabled
After a Power Failure" is indicated in the check-
box.
I: Function activated. The compressor can auto-
matically restart after a power failure.
O: Function deactivated. The compressor must be
manually restarted after a power failure.
Details and setting, see chapter "Configuration /
Advanced Settings".
[8] Tabs
The main menus of the controller are called from
the tabs.
The following tabs are available:

Menus 4
October 2013 GB 13 /80
Symbol Name Description
<Home>Normal operating
display.
<Trends>Display of various
compressor sta-
tistics or trends
over a defined time
period.
<Settings>Display and option
for editing various
compressor oper-
ating settings.
<Fault his-
tory>
Listing of the most
recent faults and
warnings (maxi-
mum 64) and fur-
ther information
about each event.
<Access
Code>
Display of the soft
keypad for entry of
codes for enabling
particular settings.
<Base Load
Sequencing>
(Option)
Display of the
menu for control
of the base load
sequencing func-
tion.
Chart 4-2: Tabs
[9] Service information
The following service information is displayed:
Operating hours
Load hours
Hours until the next maintenance is due
[9.1] Operating hours
Display of the drive motor running hours.
[9.2] Load hours
Display of compressor on-load running hours.
[9.3] "Hours to next Service..."
Indicates how many hours until the next service is
due.
[10] Pictogram
Display of measured values. To display other
readings, the pictogram view can be changed.
See the next chapter for a description.

4 Menus
14 / 80 GB October 2013
4.3 Pictogram
1
2345
6
7
8
9
10
11
12
Fig. 4-4: Pictogram
[1] Air Filter [7] Time until the next water change
[2] Airend [8] Water level display
[3] Temperature outlet airend [9] Pressure tank
[4] Pressure in the pressure vessel [10] Drive motor
[5] Air delivery [11] Drive motor speed markings (standstill, off-
load, max.)
(only for a speed-controlled compressor
system)
[6] Pressure retaining and non-return valve [12] Drive motor speed (graphical and numerical)
(only for a speed-controlled compressor
system)
4.4 Menu "Trends"
The menu "Trends" comprises four graph screens
(FS) or five graph screens (RS).
The following graph screens are available:
Statistics on-load hours
Statistics Weekly Profile
Volume flow
Network pressure
Motor speed(RS)
It is called via the <Trends> tab.
Changing between the individual graph screens
is undertaken using the <arrow keys> in the top
screen edge.
Statistics on-load hours
Trends
Statistics On-Load Hours
Volume Flow
Average Volume Flow
Since Re-Set on 20.Mar.2013 at 13:39.
Re-Set
Statistics
Fig. 4-5: Graph Screen "Statistics On-Load Hours" (RS)

Menus 4
October 2013 GB 15 /80
This bar graph shows how many hours the RS
compressor has been operated with various vol-
ume flows. It also shows the average total volume
flow since the last reset.
Trends
Statistics On-Load Hours
Hours Run
Average Volume Flow
Since Re-Set on 20.Mar.2013 at 13:39.
Re-Set
Statistics
Hours On-load
Fig. 4-6: Graph screen "Statistics On-Load Hours" (FS)
This bar graph shows how many hours the FS
compressor has been running (total hours and on-
load). It also shows the average volume flow since
the last reset.
Statistics Weekly Profile
Trends
Average Volume Flow
We. Th. Fr. Sa. Su. Mo. Tu. We.
20 Feb.
Statistics Weekly Profile
Fig. 4-7: Graph screen "Statistics Weekly Profile"
This bar graph shows the average hourly volume
flow over the last 8-days.
Volume flow
Trends
Volume Flow
Fig. 4-8: Graph screen "Volume Flow" (Example RS)
This graph shows the variation in the volume flow
over a specified period.
Network pressure
Trends
Line Pressure
Fig. 4-9: Graph screen "Line Pressure"
This graph shows the variation in pressure in the
compressed air network over a specified period.
Motor speed(RS)
Trends
Motor speed
Fig. 4-10: Graph screen "Motor Speed"

4 Menus
16 / 80 GB October 2013
This graph shows the variation in the motor speed
over a specified period.
Contents of line graphs
X-axis; time axis
Y-axis; parameter value axis: the actual value is
displayed on the left alongside the graph
<Button> on the X-axis; scale the X-axis.
<Button> on the Y-axis; scale the Y-axis.
Scaling the Y-axis
Adjust the upper limit of the graph.
1Tap the Y-axis <Upper button>.
–The input menu "Trend Upper Limit" ap-
pears.
2Tap the <Number buttons> to enter the Trend
Upper Limit.
3Tap the <OK> button.
– The entries are accepted.
– The Y-axis scale is accordingly adjusted.
Data entry can be cancelled by tapping the button
<Cancel>.
Adjust the lower limit of the graph.
1Tap the Y-axis <Lower button>.
–The input menu "Trend Lower Limit" ap-
pears.
2Tap the <Number buttons> to enter the Trend
Lower Limit.
3Tap the <OK> button.
– The entries are accepted.
– The Y-axis scale is accordingly adjusted.
Data entry can be cancelled by tapping the button
<Cancel>.
Scaling the X-axis
Adjust the width of the graph.
1Tap the X-axis <Button>.
–The input menu "Trend Time Axis" appears.
2Tap the desired option.
– The entries are accepted.
3Tap the <OK> button.
– The X-axis scale is adjusted accordingly.
Data entry can be cancelled by tapping the button
<Cancel>.
4.5 Menu "Settings"
NOTE
All specific settings should be recorded, so that
if necessary they are available (e.g. for setting
up a replacement controller).
The settings can be entered in the "Adjustment
values" table in the appendix to these operating
instructions.
The menu "Settings" offers a selection of options
that can be individually adjusted so that the com-
pressor is used in accordance with requirements.
The menu is called via the tab <Settings>.
Hour meters...
.
Control...
Timer Control...
Programmable
Inputs and Outputs...
Communication...
Configuration...
Factory Settings...
SD-Card...
Select Menu
Settings
Control system
Water circuit...
Fig. 4-11: Menu "Settings"
The following sub-menus can be called from the
"Settings" menu:
"Hour Meters..."; to adjust the service intervals
"Control..."; to adjust the compressor operating
behaviour
"Timer Control..."; to set the date and time plus
time management
"Programmable Inputs and Outputs..."; to con-
figure functions and connected devices
"Communication..."; to configure RS485
interface(s)
"Configuration..."; to configure compressor
data, language, etc.
"Factory Settings..."; view for customer service
"SD-Card..."; switching-on and –off of data
recording
"Water circuit control..."; to set the cycle time
and the remaining time until the next water
change

Menus 4
October 2013 GB 17 /80
Hour Meters
Select a Setting
Hour Meters
Hours Run
OK
Hours On-load
Hrs to next Service
Fig. 4-12: Sub-menu "Hour Meters"
The menu "Hour Meters" indicates:
"Hours Run"; display of the drive motor running
hours.
"Hours On-load", display of compressor on-
load running hours.
"Hours to next Service"; time until the next ser-
vice (service interval).
The time until the next service can be set by
the service personnel. See chapter "Advanced
operation / Setting the service interval".
Control
Select a Setting
p1 Cut-Out Point
p1 Target Pressure
p2 Cut-Out Point
p2 Target Pressure
Operating Mode Automatic Operation
OK
Control
Fig. 4-13: Sub-menu "Control" (example RS)
The "Control" menu is used to configure the com-
pressor operating behaviour. The following sub-
menus are available.
The display can be scrolled using the arrow keys
to permit display of other points.
"p1 Cut-Out Point"; to configure the pressure
band. See chapter "Configuration / Set pres-
sure bands".
"p1 Cut-In Point" (FS) / "p1 Target
Pressure" (RS); to configure the pressure band.
See chapter "Configuration / Set pressure
bands".
"p2 Cut-Out Point"; to configure the second
pressure band. See chapter "Configuration /
Set pressure bands".
"p2 Cut-In Point" (FS) / "p2 Target
Pressure" (RS); to configure the second pres-
sure band. See chapter "Configuration / Set
pressure bands".
"Operating mode"; to set the operating mode.
See chapter "Operating / Operating modes".
"Enable Remote Start"; to enable the remote
start option. See chapter "Configuration / Set
Remote Start and Stop".
"Timer start enabled"; to enable timer control
operation. See chapter "Configuration / Timer
Control Operation".
"p2 Timer Enabled"; to enable timer control
operation for the second pressure band. See
chapter "Configuration / Timer Control Opera-
tion".
"Automatic re-start"; to enable automatic
restart after a power failure. See chapter "Con-
figuration / Setting Automatic Restart After a
Power Failure".
"- Max. Power Loss Time"; to configure the be-
haviour upon automatic restart after a power
failure.
"- Restart Delay"; to configure the behaviour
upon automatic restart after a power failure.
"Dryer Pre-Run Time"; to configure the com-
pressor for operation with an external dryer.
See chapter "Configuration / Setting the Dryer
Pre-Run Time".

4 Menus
18 / 80 GB October 2013
Timer Control
Timer Control
Select a Setting
Date and Time
Timer Start/Stop
Timer Pressure Band p2
Display / Adjust
Display / Adjust
OK
This page is to set the Timer Channel
only. The Timer for
Compressor Start/Stop or activating the
second Pressure Band must be enabled
within Setpoints Menu.
Fig. 4-14: Sub-menu "Timer Control"
In the menu "Timer Control" settings can be made
for timer control operation; in addition date and
time can be set.
The following sub-menus are available.
"Date and Time"; to set the date and time. See
chapter "Configuration / Set Date and Time".
"Timer Start/Stop"; to configure timer control
operation. See chapter "Configuration / Timer
Control Operation".
"Timer Pressure Band p2"; to configure timer
control operation in the second pressure band.
See chapter "Configuration / Timer Control Op-
eration".
Programmable Inputs and Outputs
Input 1
Select a Setting
OK
Programmable Inputs and Outputs
Free
Input 2 Free
Input 3 Free
Input 4 Free
Input 5 Free
Fig. 4-15: Sub-menu "Programmable Inputs and Out-
puts"
Programmable inputs can be used to monitor con-
nected devices, or functions can be set up that in-
fluence compressor operation.
Programmable outputs can be used to forward
status messages from compressors, e.g. to a
higher level control room.
The menu "Programmable Inputs and Outputs" is
used to allocate inputs and outputs. See chapter
"Configuration / Programming Inputs and Outputs"
for details on configuring inputs and outputs.
Communication
RS485:1 Address
RS485:1 Baudrate
RS485:3 Address
RS485:3 Baudrate
Select a Setting
Communication
OK
Fig. 4-16: Sub-menu "Communication"
In the menu "Communication" you can specify the
communications settings for the RS485 port (des-
ignation: RS485:1). Optionally a further RS485 in-
terface (designation: RS485:3) is available.
To configure the interfaces, see chapter "Configu-
ration / Setup RS485 Communication".
Configuration
Language
Temperature Unit
Pressure Unit
Volume Flow Unit
Maximum Volume Flow
Select a Setting
Configuration
OK
Fig. 4-17: Sub-menu "Configuration"
In the menu "Configuration" the compressor data
can be set to the preferred measurement units.
The following sub-menus are available.
The display can be scrolled using the arrow keys
to permit display of other points.
"Language"; to set the display language. See
chapter "Configuration / Set language".
"Temperature Unit"; to set the temperature
unit. See chapter "Configuration / Setting Mea-
surement Units".

Menus 4
October 2013 GB 19 /80
"Pressure Unit"; to set the pressure unit. See
chapter "Configuration / Setting Measurement
Units".
"Volume Flow Unit"; to set the volume flow
rate. See chapter "Configuration / Setting Mea-
surement Units".
"Maximum Volume Flow"; to set the maximum
volume flow, which is used in the calculation for
the volume flow rate display. Ex works this set-
ting is pre-set to a mean value. Dependent on
the actually set line pressure, the value can be
finely adjusted here.
"Minimum Volume Flow" (RS); to set the mini-
mum volume flow, which is used in the calcula-
tion for the volume flow rate display. Ex works
this setting is pre-set to a mean value. Depen-
dent on the actually set line pressure, the value
can be finely adjusted here.
"Ext. Speed Limit (min)" (RS); if necessary, this
adjustable speed limit can be switched on via a
programmable input. See chapter "Configura-
tion / Programmable Inputs".
"Ext. Speed Limit (max) (RS); Via a program-
mable input this speed limit can be switched
on, if required. See chapter "Configuration /
Programmable Inputs".
Factory Settings
Select a Setting
Compressor Rated Pressure
Minimum Start Temperature
Run-On Time
Soft Stop Time
Warn. Starting Vacuum min.
OK
Factory Settings
Fig. 4-18: Sub-menu "Factory Settings"
The menu "Factory Settings" shows the factory
settings of the control.
Some values can be changed at the service level,
see chapter "Advanced operation / maintenance
Level".
The display can be scrolled using the arrow keys
to permit display of other points.
"Operating pressure"; rated operating pressure
that can be produced using the compressor.
"Start Requ. Approval"; below the set tank
pressure, the compressor can be restarted.
"Heavy Startup"; if the tank pressure reaches
this value during the start phase, the compres-
sor is stopped. (compressor without speed con-
trol)
"Discharge Temp. Warning"; air temperature
warning limit at the airend outlet.
"Discharge Temp. Fault"; if the airend temper-
ature reaches the set value, the compressor is
stopped.
"Minimum Start Temperature"; minimum tem-
perature (water temperature jacket cooling), at
which the compressor can be started.
"Run-On Time"; drive motor off-load period be-
fore the compressor is stopped and switched to
standby mode.
"Soft Stop Time"; off-load period of the drive
motor before the compressor is stopped. For
manual or remote stop.
"Star-Delta"; factory set star-delta switchover
time (compressor without speed control)
"Software version"; software version of the
controller.
"Controller Ref.-No."; serial number of the con-
troller.
"Compressor Ref.-No."; serial number of the
compressor.
SD-Card
SD-Card
Record Data
State of SD-Card
OK
Off
File Name
Ready
Before Removing SD-Card switch
Record Data to Off.
Fig. 4-19: Sub-menu "SD-Card"
The controller has a data recording (data logger)
function by recording of data to an SD-Card.
The record data function is switched on and off
via this menu. See chapter "Advanced operation /
Data Recording".

4 Menus
20 / 80 GB October 2013
Water circuit control...
Select a Setting
Replacement cycle
Replacement remaining
Water circuit control
OK
Fig. 4-20: Sub-menu "Water circuit control"
Setting options for the cycle time and the remain-
ing time until the next water change.
4.6 Menu "Fault History"
The controller stores the last 64 alarms (faults and
warnings) which have occurred.
The alarms are displayed in a list, with the most
recent appearing at the top. If the list exceeds 64
alarms, the oldest alarm will be overwritten.
A flashing symbol to the left alongside the alarm
shows that this alarm is still active (not yet reset).
Additionally the symbol flashes on the tab <Fault
History>.
Fault overview
Fault History
Reset
Fault E419
Water level min.
Warning A626
Level control inlet
Fault E415
No Press. Build-Up
Fault E401
Emergency Stop Activated
Fault E400
Power Supply Failure
Fault E504
VSD Communication
Fault E400
Power Supply Failure
Fault E504
VSD Communication
Fig. 4-21: Menu "Fault History"
Each alarm is saved with the date and time of its
occurrence.
The alarm list can be scrolled using the arrow
keys.
The button <i> on the right side of the menu row is
used to display the readings recorded at the time
of occurrence of the alarm alongside other infor-
mation about the alarm.
Fault History
Fault E419:
Water level min.
When 29.Jan.2013, 15:53:23
Hours Run 2h
TotalCount 1
Status on-load 2700rpm
Final pressure 7.7bar
Final temperature 36°C
Line pressure 7.5bar
Water level 5%
Speed 2700rpm
Heatsink Temperature 20°C
Motor current 111.1AMP
Fig. 4-22: Information about the selected alarm
The contents can be scrolled using the arrow
keys.
Alarm acknowledgement
After the cause of the alarm has been cleared, the
alarm must be reset in the controller.
1Clear the cause of the alarm.
2Tap the <Fault History> tab.
3Tap the <Reset> button.
✓The outstanding alarm(s) is (are) reset.
– The flashing alarm symbol disappears.
–The symbol on the <Fault History> tab
stops flashing.
Alarms that are still uncleared cannot be reset.
The alarm symbol and the symbol on the <Fault
History> tab continue to flash.
4.7 Menu "Access Code"
Codes for particular operating options can be en-
tered in the menu "Access Code".
The following access codes are available to the
customer's personnel.
Code Operator function
1234 Activate and deactivate base load
sequencing (option).
3031 Enable and block user entries; if blocked,
no parameter entry is possible.
3100 Enable and block the maintenance level;
advanced operator functions.
Chart 4-3: Customer access codes
NOTE
The maintenance level is automatically blocked
after five minutes, the controller automatically
activates the user level.
This manual suits for next models
1
Table of contents
Other CompAir Controllers manuals
Popular Controllers manuals by other brands

CNC
CNC AC-CNC2017-2S operating instructions

USA Technologies
USA Technologies VendingMiser VM150 installation instructions

YASKAWA
YASKAWA motoman NX100 manual

Roger Technology
Roger Technology B70/1DC Instruction and warnings for the installer

Elmes Electronic
Elmes Electronic STM-2K VER 4 quick start guide

KaVo
KaVo EWL 9045 operating instructions