Concept2 SENTINEL S55 v6 User manual

SENTINEL S55 v6
INSTALLATION AND OPERATION
MANUAL
Version: November 2020

1
Thank you for purchasing a Concept Smoke Screen system. Your choice to protect your property and premises
with this equipment has given you the use of one of the most effective security systems currently available.
Concept Smoke Screen systems have been in service for over 35 years and have protected many millions of
pounds worth of property, defeating criminals and securing premises on an almost daily basis. We produce
them because we believe you have a right to feel safe and secure.
Please take the time to read and understand this guide to ensure you achieve the maximum performance from
your Smoke Screen. If you have any questions that remain unanswered, please call our experts at Concept
Smoke Screen and we will help. Once again, thank you for your decision; we hope that it is one that never
needs to be tested.
Matt Gilmartin, Managing Director

2
CONTENTS
1
General
3
1.1
1.2
1.3
1.4
1.5
Safety instructions………………………………………………………………………………………..…………………….………...............................................
How does your Smoke Screen work?………………………………….…………………………………...……………................................................
Introduction……………..………………………………………………………………………………………………………………….................................................
Overview……………………………………………………...…………………………………………………………………………….................................................
Typical installations……………….………………………………………………………………………………………………….................................................
3
3
4
4
5
2
Location
6
2.1
2.2
2.3
2.4
2.5
Positioning……………………………….…………………….………………………………..…………………………………………...............................................
Installation procedure.………………………………………………………………………….……………………………………..............................................
Servicing access.……………………………….……………………………………..………………………………………………...............................................
Mounting…………..……….……………………….………………………………………...……………………………………………...............................................
Nozzle changing…………………………………………………………………..……………………………………………………..............................................
6
7
7
7
9
3
Function
10
3.1
3.2
Controlling the smoke……………………………………....………………………………………………………………………................................................
Outputs………………………………………………………………………………………………………………..……………….……..................................................
10
11
4
Connections
12
4.1
4.2
Circuit board layout……………………………………………………………………………………………………………………...............................................
Generic connection diagram……………………….…………………………….…….………………………………………...............................................
12
13
5
Settings
14
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
Screen sensor……………….………..……………………………………………..……….…………………………………………..................................................
Energy saving mode……………………………………………………….………...………..……………………………………..................................................
Verification timer………………………………………………………………………………………………………………………...................................................
Service mode……...…….……………………………………………….…………….....……………………………………………..................................................
Inverting Triggers…..……………………………………….………………………….…..…………………………………………..................................................
Tamper……………………………………………………………..………………………..………………………………………………..................................................
Reboot………………………………………………………………………………………………………………………………………….................................................
Fluid management………..…………………………………………………………………………………………………………….................................................
Battery management………..………………………………………………………………………………………………………..................................................
Programming………..…………………………………………………………………………………………………………………….................................................
14
14
14
15
15
15
15
17
17
18
6
Commissioning
20
6.1
6.2
Operation……………………………………………………………………………………..…………………………………………….....................................................
Testing…………………………………………………………………………………………..……………………………………………....................................................
20
20
7
Servicing
21
7.1
7.2
7.3
7.4
7.5
Live status…………………………………………………………………………………………………………………………………......................................................
LCD, LED and sound indications.…………………………………………….……..……...........................................................................................
Thermal cut-out (TCO) reset……………………..……………………………..……………………………………………….....................................................
Action after every activation……………………………………………………….…………………………………………….....................................................
Servicing and fluid replenishment……………………………………………………………………………………………....................................................
21
22
23
24
24
8
Miscellaneous
25
8.1
8.2
8.3
8.4
8.5
Glossary……………………………………………………………………………………….........................................................................................................
FAQ…………………………….………………………………………………………………………………………………………………....................................................
End of product life policy…………………………………………………………..…………..…………………………………....................................................
Warranty terms and conditions……………………………………………….……………………………………………….....................................................
Installer notes……………………………..…………………………………………….………………………………………………..........................................................
25
26
26
26
29

3
General 1
1.1 SAFETY INSTRUCTIONS
Before installing and using the Smoke Screen read, follow and retain this manual and safety instructions for future
reference.
To reduce the risk of severe injury or death to persons, or damage to the Smoke Screen:
• Do not work on the Smoke Screen unless qualified by the manufacturer to do so.
• Disconnect the mains power supply before working in the heater block compartment or anywhere that
mains voltage is indicated by the warning labels shown below (this is engraved with the layout of the
PCB connections).
• Install in accordance with the instructions in this manual.
• Operate the Smoke Screen only from the type of power source indicated on the label.
• Do not modify the Smoke Screen.
• Adjust only the controls specified in this manual.
• Use only consumables and replacement parts specified by the manufacturer.
• Do not spill liquid of any type on, or inside, the Smoke Screen.
The following signs, or a variation, may be used for safety notices in this manual or on the Smoke Screen:
This type of warning note is
used to indicate possible
electrical shock hazards that
may cause serious injuries or
death.
This type of warning note is
used to indicate the possibility
of injury caused by hazards
other than electrical shock.
1.2 HOW DOES YOUR SMOKE SCREEN WORK?
Your Smoke Screen passes a non-toxic fluid through an efficient heat exchanger to create smoke, or more
accurately a thermally generated fog that obscures visibility, discouraging intruders from entering your premises.
This fog is very persistent and will stay suspended in the room for a significant length of time until it is vented by
opening the doors and windows.
The Smoke Screen uses a sophisticated electronic control system to ensure it heats up to, and maintains, its ideal
operating temperature using a minimal amount of electricity.
The control system similarly provides a flexible interface with intruder detectors, alarm systems and remote
monitoring centres to ensure that you are always protected and free of inadvertent activations.

4
1.3 INTRODUCTION
This manual covers the Sentinel S55.
Before commencing installation of the Smoke Screen ensure that you have all the following equipment supplied
in the box:
• 1 x Smoke Screen.
• 1 x Mounting bracket.
• 1 x Swift-Fit fluid reservoir (boxed).
• 2 x 12v batteries.
• 1 x Literature pack and warning sign.
• 1 x Extra 30-degree Nozzle for wall mounted installation.
You will also need:
• Mains power supply: an unswitched 13 amp fused spur connected to a dedicated breaker.
• Connections into the alarm panel or other triggering system.
• PIR (or equivalent) to provide the hold-off where required.
1.4 OVERVIEW
The Smoke Screen is designed to form part of an existing intruder alarm system but may also be configured as a
‘stand-alone’ system or as part of a centrally monitored, command and control system. A typical installation is
shown in the following schematic:

5
1.5 TYPICAL INSTALLATIONS
A typical installation can be configured in the following way:
• The Smoke Screen is wall or ceiling mounted in the appropriate location.
• A Hold-off PIR (or similar device) located within the same area as the Smoke Screen providing a
confirmation signal to the Smoke Screen to start, or restart, ‘smoke’ production.
• A Set command supplied by an alarm control panel, or equivalent, in the form of an N/C (normally
closed) or an N/O (normally open) relay changing state when the alarm system is set for operation.
• An Alarm command supplied by the alarm control panel, or equivalent, in the form of an N/C (normally
closed) or an N/O (normally open) relay changing state when the alarm system confirms an intruder
alert.
• A Panic command in the form of an N/C (normally closed) or an N/O (normally open) switch, or
equivalent clean contact, that is opened or closed when an instant activation is required.

6
Location 2
2.1 POSITIONING
The Smoke Screen should ideally be sited in a covert position away from prying eyes and thereby reducing the
possibility of tamper or an attack. The ideal place for the Smoke Screen is above a ceiling from where the smoke
plume is used to its best effect, bursting on the ground and spreading outwards and upwards through 360°. If no
suitable ceiling location is available then the next best location is a wall mounting as close to ceiling height as
possible.
Wall-mounting
The optimum wall mounting position for the Smoke Screen is 2.5 metres above the floor facing the area to be
protected and using the 30-degree angle nozzle. The maximum recommended mounting-height above floor
level is 3 metres, the minimum is 1 metre and there should be no obstacle within 1 metre of the smoke output
nozzle. Also, leave a minimum of 150mm clearance to the ceiling.
Ceiling-mounting
The optimum ceiling mounting position for the Smoke Screen is 2.5 metres above the floor facing the area to be
protected and using the standard straight nozzle. The maximum recommended mounting-height above floor level
is 3 metres, the minimum is 1 metre and there should be no obstacle within 1 metre of the smoke output nozzle.

7
2.2 INSTALLATION PROCEDURE
1. Site the Smoke Screen and fix to the wall or ceiling as appropriate.
2. Select the “Service Mode” dip switch to “On”.
3. Make connections as required to the alarm panel, hold-off PIR and, if used, the Panic input.
4. Make connection to the Smoke Screen Interface (if used) and set the key switch to isolate.
5. Connect and turn on the mains power.
6. Turn on the internal battery back-up.
7. The Smoke Screen will heat up to operating temperature in approximately 20 minutes.
8. Set correct time/date and smoke timing for the specified room size.
9. Ensure the “Service Mode” dip switch is selected to “Off”.
10. Insert a Swift-fit fluid reservoir.
11. Make sure all tamper switches are closed.
12. If fitted set the Smoke Screen Interface key switch to ‘Ready’ and you are ready for test.
2.3 ACCESS
To access the PCB connections, programming panel, mounting holes, batteries and fluid, remove the front cover
by unscrewing the set screws on either side and unhooking it from the top of the case; refitting is the reverse
process. Installation cable entry is through the serrated grommet on the right side of the back plate.
2.4 MOUNTING
The Smoke Screen can be mounted on a ceiling or a wall using the simple standard bracket supplied with the
unit. This flush-fitting bracket maximizes security by concealing all the mounting fastenings such that they can
only be accessed, or the Smoke Screen dismounted, by dismantling the unit. Moreover, the Smoke Screen has a
tamper protection switch to provide an alert in the unlikely event that it is disturbed. In all cases, the installer must
attach the Smoke Screen to the building structure using appropriate fasteners.
NB: When mounting the Smoke Screen ensure that the airflow through the vent holes in the rear of the unit is not
obstructed.
Wall and ceiling mounting
Ceiling or wall mounting is the same process except that rather than fixing the Smoke Screen direct to a ceiling
an intermediate unistrut section may be used or it can be suspended as described in the next section.
Attach the bracket to the wall or ceiling
using appropriate fixings.
Carefully hook the slots on the back of
the Smoke Screen onto the bracket (for
clarity, shown above not attached to the
ceiling/wall). Slide along to align the
screw fixing holes. The unit will now
hang on the bracket.
Fit, and ensure tight, 1x M6 set screw
with washer in the hole in the back of
the Smoke Screen alongside each of
the two mounting slots. Access to
the fixing holes is through the fluid
and heater block compartments.
a
c
b

8
Suspension mounting
Suspending the Smoke Screen is achieved using a ‘Suspension Kit’ comprising a length of unistrut, two sections
of threaded bar and fixings.
Suspension Kit Contents (all M8)
Unistrut 1 x 1 metre
Threaded bar 2 x 1 metre
Fixings:
1 x ceiling hole surround
2 x drop-in anchors
6 x full nuts
4 x 25mm washers
2 x 38mm washers
2 x channel nuts
Prepare the Smoke Screen by fitting
the angle brackets. Fix the required
length of M8 threaded bar to the
bracket using 4 x nuts and 4 x 25mm
washers.
Fix the unistrut into place. There are
a range of fixings to accommodate
concrete ceiling, girders etc. if in
doubt contact the fixing supplier.
Attach the threaded bar to the
unistrut using the channel nuts,
38mm washers and M8 nuts. Once
this is done the Smoke Screen can
be lifted into position and the set
screws tightened as above.
Any fine adjustments can be made
at this stage as the nuts and the
threaded bar will take the weight of
the Smoke Screen.
The final assembly viewed ‘through
the ceiling’ is in the photo. Any hole
made in the ceiling below can be
made good with a cosmetic hole
surround.
b
g
e
f
d

9
2.5 NOZZLE CHANGING
To change the nozzle, first remove the front cover then remove and replace the nozzle using a 10mm ring
spanner, sealing it with PTFE tape and ensuring that an angled nozzle is seated in the correct orientation. The
Smoke Screen is delivered with a single-hole straight nozzle plus an extra 1-hole 30 deg angle down nozzle. The
following are also available – 2-hole horizontal, 3-hole horizontal, 1-hole 30° angle down and 2-hole 30° angle
down.
Be aware of high voltage
in the block area. The
electrical supply should be
switched off before
working in the heater
block compartment.
This operation is usually carried out during
installation. If the Smoke Screen has been in
service the nozzles will be extremely hot and
will cause injury if touched. Therefore, the
Smoke Screen should be switched off and
time should be allowed for the nozzles to cool.

10
Function 3
3.1 CONTROLLING THE SMOKE
Alarm Panel activation
There are 3 sets of input connections on the Smoke Screen (Set, Alarm and Hold-off) that should be connected to
clean contacts. For the Smoke Screen to produce ‘smoke’ all 3 sets of connections must be ‘open circuit’ (this can
be changed to ‘closed = activate’ – see the “Inverting Trigger Mode” Section but note that ‘open = activate’ is
used in this manual). We recommend using the default setting ‘open circuit = activation’ to ensure that the Smoke
Screen will activate in case the alarm cables are tampered from the outside. If one set of connections is ‘closed
circuit’ then the Smoke Screen is prevented from producing smoke. Hence the production of smoke is controlled
using one or a combination of the following:
•Set – a normally closed relay connected across the alarm panel ‘Set’ output connections, which is
open when the alarm panel is ‘Set’ and closed when the panel is ‘Unset’.
•Alarm – a normally closed relay connected across the alarm panel ‘Intruder’ output connections, which
is open when the alarm panel or controlling device is in ‘Alarm’.
•Hold-off – usually a PIR / movement sensor normally closed output, which opens when the sensor
detects movement, connected to the Smoke Screen “Hold-off” normally closed connections.
•Additional hold-off – any form of normally closed relay / micro switch can be connected to the “Hold-
off” connections. Where fitted in parallel as an addition to a PIR both devices must be ‘open’ to
produce ‘smoke’.
Panic activation
The Smoke Screen has a Panic input that should be connected to a clean contact going ‘open circuit’ to activate
(this can be changed to ‘closed = activate’ – see “Invert Trigger Mode” in the Programming section).
It is recommended that the Panic is activated by a momentary, non-latching, button to avoid the situation where a
Panic activation is not reset before a standard activation is required.
NB:
The Panic trigger mode is delivered set to n/o and the Panic Smoke Time is set to 0 seconds to prevent
inadvertent activation if the facility is not used.
WARNINGS:
•Service Mode should be selected to on if the Panic trigger mode is changed when the Smoke Screen is
at operating temperature.
•Always restore a Panic input after it has been used. Failure to do so will result in the Smoke Screen not
subsequently activating on an Alarm Panel (Set, Alarm and Hold-off) demand.
Smoke and Panic Time
The Smoke Screen should be set to produce fog for a time (Smoke Time) that is suitable for the volume of the
location to be protected. As a guide, an S55 set to 60 seconds Smoke Time will reduce the visibility to 1 metre*
in a 175 m3volume room. The Smoke Time is changed in the settings; see Section 5.9.
(* as defined by the test requirements of EN50131-8)

11
Hold-off settling time
A “Settle Timer” can be programmed for a period between 0 and 60 seconds (in 1 second intervals) during which
the Smoke Screen will not react to a hold-off input after receiving a ‘Set’ command.
Delaying an activation
After the Smoke Screen has received the required 3 inputs to produce smoke, an activation can be delayed for a
period between 0 and 60 seconds (in 1 second intervals). This can be used to sequence activations in a multi-
machine installation. See “Smoke Delay” in the Programming section.
NB: The Delay Timer and Settle Timer are cumulative, ie if a Delay Time of 5 seconds and a Settle Timer of 30
seconds are set the Smoke Screen will not activate for 35 seconds after it receives a “Set” input.
Re-triggering
If a Smoke Delay time has been set the menu gives the option to select the following options for subsequent re-
triggers initiated by a hold-off if the Set and Alarm remain in alarm:
•
Delay:
Repeat activations are delayed by the Delay Time set.
•
Instant:
Repeat activations are instantaneous.
Stopping an activation
Once activated the Smoke Screen will stop producing ‘smoke’ before the end of the programmed smoke time
only if the ‘Set’ is restored to a non-alarm state.
A Panic activation can be stopped before the end of the programmed smoke time only if the ‘Set’ is cycled to
alarm and back to restore.
Preventing an activation
To prevent the Smoke Screen from making smoke during a service inspection under any circumstances select
the “Service Mode” dip switch to on (see separate section)
3.2 OUTPUTS
Clean contact outputs are provided for connection to the alarm panel for ‘Mains Fail’, ‘Temp Status’, ‘Empty Fluid’,
‘Battery Output’, ‘Tamper’, ‘Verification Output’ and ‘Low Fluid’. See the notes on the “Generic Connection
Diagram” for the function of these outputs.

12
Connections 4
4.1 CIRCUIT BOARD LAYOUT

13
4.2 GENERIC CONNECTION DIAGRAM

14
Settings 5
5.1 SCREEN SENSOR
A Concept Smoke Screen “Screen Sensor” can be connected to the Sentinel. When this is integrated the system
detects a drop in the fog density in the protected area and will re-trigger the Sentinel to maintain the fog level.
When fitted the Screen Sensor is connected to the Hold Off input pins and, consequently, it prevents the use of a
hold-off detector.
NB: It is critical that the Screen Sensor is installed in an area that receives the maximum fog coverage. It will not operate
correctly if this is not achieved
5.2 ENERGY SAVING MODE (ESM)
The Smoke Screen has 3 options for ESM:
•
ESM Disable.
The Smoke Screen maintains its normal running temperature.
•
ESM.
When ESM is selected and the alarm panel input to the Smoke Screen is “Unset” the Smoke
Screen lowers its running temperature to a standby level to reduce power consumption and cost. When
the Smoke Screen receives an ‘Alarm Set’ input it automatically heats to its normal operating
temperature.
NB
:If the Smoke Screen is in ESM mode and is activated as soon as the alarm is set, ie before it has
heated to normal operating temperature, it will still produce smoke but the length of time of the initial
burst of fog will be shortened.
•
Extreme.
When Extreme is selected and the alarm panel input to the Smoke Screen is “Unset” the
Smoke Screen heater is not operated, and its temperature reduces to ambient. When the Smoke Screen
receives a ‘Set’ input it automatically heats to its normal operating temperature.
NB:
This will introduce a period where the Smoke Screen cannot produce fog as it heats up.
WARNING: ESM and Extreme should not be used if the Smoke Screen is being used with a Panic input.
5.3 VERIFICATION TIMER
If the “Verify Timer” is set to 0 seconds the verification output changes state during an activation for the set
“Smoke Time”. If the “Verify Timer” is set above the set Smoke Time the verification output maintains the
changed state for that time after an activation starts.
NB: The Live Status verification display (V) is shown only during the production of fog, not for any subsequent
time set by the “Verify Timer”.

15
5.4 SERVICE MODE
Setting dip switch No 4 (see diagram under “Circuit Board Layout”) to “On” puts the Smoke Screen into “Service
Mode”. This setting prevents the Smoke Screen from making smoke whilst work is conducted with power applied.
To highlight that the Smoke Screen is in “Service Mode” the Tamper output is put into an alarm state.
FAILURE TO DISABLE SERVICE MODE WHEN NO LONGER REQUIRED WILL PREVENT THE SMOKE SCREEN
OPERATING.
5.5 INVERTING TRIGGERS
The Smoke Screen triggers, Set, Alarm, Hold-off and Panic should be connected to clean contacts changing state
in alarm. The triggers can be set to ‘open = activate’ or ‘closed = activate’. We recommend using the default
setting ‘open circuit (n/c in menu) = activation’ to ensure that the Smoke Screen will activate in case the alarm
cables are tampered from the outside.
The Smoke Screen is delivered with the Set, Alarm and Hold-off triggers set to n/c, ie ‘open = activate’. The Panic
trigger is set to n/o to avoid an inadvertent activation if the facility is not used and the Panic input is left open.
5.6 TAMPER
There are internal tamper circuits on all the Smoke Screen covers and an external tamper input on PCB terminal
block “B”. A “Tamper Status” output is provided on PCB terminal block “F”. To prevent unwanted tamper signals
the external tamper input can be disabled if not in use by selecting dip switch 2 to “On”, which bridges the input
pins on the PCB.
NB: A tamper ‘open’ state provides only an indication of the event; it does not automatically activate the Smoke
Screen or prevent it from activation.
5.7 REBOOT
The Smoke Screen can be rebooted without removing mains and battery power by selecting “Yes” in the Reboot
menu item that is available when the Smoke Screen is in Service Mode. Any settings entered in the menu will be
retained. This facility can be used to clear any critical faults.

16
5.8 FLUID MANAGEMENT
The Smoke Screen has a replaceable 1 litre Swift-Fit fluid reservoir (also known as product code SFL-1000) that is
accessed by removing the cover on the right-hand side of the unit. The fluid level is monitored using sensors in
the fluid reservoir to give a “Low Fluid” indication output when the Swift-Fit is approximately 50% full and an
“Empty Fluid” output when the bottle is empty. The Smoke Screen will not produce fog when there is an “Empty
Fluid” indication.
Be aware of high voltage in
the Smoke Screen. The mains
electrical supply should be
switched off before changing
the fluid consumable.
If the generator has been in
service the heater block and
connected parts will be
extremely hot and will cause
injury if touched. Switch off
and allow the heater block to
cool.
Changing a fluid consumable
Obtain a replacement fluid reservoir from your Smoke Screen supplier. Open the right-hand access panel. Lift
the reservoir out of the compartment by removing the upper end first.
Disconnect the fluid monitoring cable.
Disconnect the fluid feed pipe (pull collar to release).
Connect the monitoring cable and feed pipe to a new fluid
reservoir.
Insert the reservoir into the fluid compartment base first
ensuring that the pipe connection is not accidentally
released.
Make sure the notch in the reservoir is on the outside of the
Smoke Screen or the compartment door will not fit. This
orientation ensures that the fluid feed is correct for both
upright and face-down installations.

17
External reservoir
A 5000ml external reservoir can be used with Smoke Screen, please contact Concept Smoke Screen if you wish
to use this function.
5.9 BATTERY MANAGEMENT
Operation
The Smoke Screen is fitted with a battery to provide power to the electronic circuits and pump (not to the fluid
heater) in the event of a mains power failure. This ensures that the Smoke Screen can provide an effective
activation for at least 1 hour after a mains power failure (further detail is on the relevant Smoke Screen datasheet).
The Smoke Screen is capable of activating in the event of a battery fault or if the batteries are not fitted; in the
latter case, to avoid battery fault indications, the facility should be disabled (see “Programming”). The Smoke
Screen is supplied with a set of batteries and replacement batteries may be obtained from your Smoke Screen
distributor or Concept Smoke Screen.
Battery protection
To prevent damage to the batteries caused by
running them to a completely discharged state, the
Smoke Screen will switch off the battery power 1.5 hours
after a mains power failure, at which time the unit is too
cold to activate; the Smoke Screen will start up normally
as soon as mains power is re-applied.
Battery switch
The Smoke Screen has a switch on the PCB to permit the batteries to be disconnected from the system whilst
remaining in place (see the picture above). The delivery setting is “Off”; select to “On” if intending to use the
battery facility.
Removal and replacement
Disconnect the mains power supply. Take off the Smoke Screen front cover, the battery compartment cover on
the left side and the mains power cover on the PCB. Disconnect the battery plugs from the PCB. Slide out the
old batteries, replace with new units and refit the plugs and covers
THE SMOKE SCREEN WILL NOT FUNCTION AT ALL DURING A MAINS POWER FAILURE IF THE BATTERIES ARE
DISABLED.
Be aware of high voltage in the
Smoke Screen. The electrical
supply should be switched off
before changing the batteries.
If the generator has been in
service the heater block and
connected parts will be
extremely hot and will cause
injury if touched. Switch off and
allow the heater block to cool.
PCB mains power cover
Battery Switch

18
5.10 PROGRAMMING
LCD illumination
Pressing any button illuminates the LCD back-light; it automatically extinguishes after 1 minute of inactivity.
Setting the time and date
In the Smoke Screen Status or Current Time display:
• Press and hold
Function/Escape
for 3 seconds until the date and time are shown with the Day flashing.
• Change the value with the
Up
and
Down
buttons.
• Press
Enter/Back
to save a change and move to the next parameter.
• Press
Function/Escape
to return to the previous parameter without saving any changes.
• Repeated presses of
Function/Escape
will return the LCD to the Live Status display.
Viewing and setting the functions and variable parameters
In the Smoke Screen Status or Current Time display:
• Press
Function/Escape
to access the programmable functions.
• Press
Up
or
Down
buttons to scroll through the available functions.
• Press
Enter/Back
to view the current function setting.
• Press
Up
or
Down
buttons to scroll through the available parameters.
• Press
Enter/Back
to select and save the value shown and return to the list of functions.
(Note: if the change results in a Live Status change the display will return to the Live Status display).
• Press
Function/Escape
to return to the list of programmable functions without saving any changes.
• Repeated presses of
Function/Escape
will return the LCD to the Live Status display.

19
Parameter settings
MENU ITEM
DELIVERY
SETTING
AVAILABLE SETTINGS
REMARKS
Event Log
-
Read-only.
See Section 7.2 for a list of the major events
Setting Smoke Time
5 seconds
5 to 360 seconds in 1
second intervals.
See Section 3.1.
Setting Panic Smoke Time
0 seconds
5 to 360 seconds in 1
second intervals.
See Section 3.1.
Invert Trigger Mode
Set, Alarm &
Hold-off
N/C Mode.
Panic
N/O Mode
N/O Mode
N/C Mode
Trigger inputs can be individually set to:
N/O Mode = unit detects a normally open
circuit going closed to activate.
N/C Mode = unit detects a normally closed
circuit going open to activate.
See Section 5.5.
Enable/Disable Battery
Enable
Disable
Enable
The PCB-mounted battery switch is “Off” on
delivery.
See Section 5.8.
Enable/Disable ESM
Disable
Disable
ESM
Extreme
Energy Saving Mode.
See Section 5.2.
Smoke Delay
0 seconds
0 to 60 seconds in 1
second intervals.
See Section 3.1.
Re-triggering
Delay
Delay
Instant
Available if Smoke Delay set to > 0 seconds.
Select Delay to apply set Smoke Delay time
to every re-trigger by the Hold-off.
Instant = no delay.
See Section 3.1.
Settle Timer
0 seconds
0 to 60 seconds in 1
second intervals.
See Section 3.1.
Verify Timer
0 seconds
0 to 3600 seconds in 5
second intervals.
See Section 5.3.
EN Mode
-
Nil.
Manufacturer-only setting.
Live Temperature
-
Read only.
Displays the current heater block
temperature.
Manufacturer Setting
-
Nil.
Manufacturer-access only.
Reboot System
No
No
Yes
Available only if “Service Mode” active.
Reboots the Smoke Screen (all settings are
retained).
Table of contents
Other Concept2 Security System manuals