
SE Engineering Manual | 2
Energy from the boiler steam is transferred to the fresh water tank through a heat exchanger
inside of the unit. This causes the water to boil. Full boil from a cold tank can take up to 15
minutes. On SETC models, the Keepwarm feature can be activated to reduce boil time.
Once the humidifier has reached full boil, the humidifier will modulate the actuator,
controlling the flow of steam into the unit. This will allow the unit to reduce its output level
as the humidity levels in the conditioned environment are satisfied.
During the boiling process minerals are left behind from the water. The unit will occasionally
activate the drain pump to flush out some of the minerals in the water and reduce the
concentration in the tank. The fill valve will also be activated periodically to replace water
that is boiled off during normal operation.
When the demand to the unit stops, the unit will close the control valve and steam
production will stop. The unit will enter standby mode and await a call for humidity. If
Keepwarm is activated (SETC only), the control valve will be opened periodically to heat the
tank.
Drains
As steam is produced minerals are left behind in the SE’s tank. The SE performs periodic
drains to reduce the amount of minerals that will precipitate as scale.
In general more frequent drains result in less maintenance. The amount of water drained to
control mineral concentration in the tank can be configured in the SETC’s software.
To cool drain water the SE activates the fill valve whenever the drain pump is activated.
Cool fill water flows down from the fill box and blends with hot tank water in the lower mixing
box before being drawn into the drain pump. The drain cooling feature can be deactivated
via software.
Steam Distribution
Steam generated by the humidifier may be introduced into the conditioned environment in
several different ways. The most common method for introducing steam into the conditioned
environment is to mount a steam distributor tube in a supply air duct as shown in Figure 1:
Humidifier Schematic. For larger ducts or larger loads it is also common to use a steam
manifold with a single steam line connection and multiple tubes for distributing the steam. For
introducing steam directly into a room, remote mounted blower packs are used. (see Steam
Distribution on page 41)
Steam Line
The steam line connects the atmospheric steam outlet of the humidifier to the atmospheric
steam distributor. The SETC is an atmospheric steam generator so it is very important no
restrictions are present in the steam line and that the steam line is sized to carry the full output
capacity of the humidifier. Length of these lines must be minimized to reduce the efficiency loss
of the humidification system.
Whenever steam is distributed, condensate is formed in the distribution system. Insulating
steam lines is one important way to reduce the amount of condensate formed. Steam lines
must be sloped so that condensate does not collect in the lines and create a restriction to
steam flow.