Consilium Salwico CS4000 User manual

Fire Alarm System
Salwico CS4000
Service & Maintenance manual
çConsilium

The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Consilium assumes no legal responsibility for any error
or damage resulting from the usage of this document.
Edition 6, 10 1 E, Oct 2010.
Document no. S-4-010.968
Part no: 465002
© 2005-2008, Consilium Fire & Gas AB
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
E-mail: [email protected]
Internet: www.consilium.se

Service & Maintenance manual Chapter 1: CS4000 block diagram
Salwico CS4000
Contents
Chapter 1: CS4000 block diagram .........................................................................................2
Chapter 2: Testing....................................................................................................................3
TEST A FIRE-DETECTING ZONE................................................................................................. 3
Heat detectors ....................................................................................................................3
Smoke detectors..................................................................................................................4
Flame detectors..................................................................................................................4
TEST FAULT CONDITIONS ........................................................................................................4
Removed detector fault.......................................................................................................4
Fuse fault............................................................................................................................4
Battery fault........................................................................................................................5
Earth fault ..........................................................................................................................5
Loop cable break................................................................................................................5
Power supply......................................................................................................................5
RESET TEST MODE ...................................................................................................................6
TEST THE CONTROL UNIT DISPLAY...........................................................................................6
Chapter 3: Cleaning of fire detectors.....................................................................................7
SMOKE DETECTORS .................................................................................................................7
HEAT DETECTORS.................................................................................................................... 7
FLAME DETECTORS..................................................................................................................7
Chapter 4: Replacing/Adding/Deleting fire detectors...........................................................8
REPLACING FIRE DETECTORS...................................................................................................8
Instruction ..........................................................................................................................8
ID address on DIP switches...............................................................................................8
HOT PLUG&PLAY (ADDING/DELETING LOOP UNITS)................................................................9
Change configuration file from the fault list......................................................................9
Change configuration file from the service menu............................................................11
Chapter 5: Replacing battery................................................................................................13
INSTRUCTION.........................................................................................................................13
Chapter 6: Software...............................................................................................................14
CONFIGURATION PROGRAM...................................................................................................14
TO UPLOAD A CONFIGURATION FILE FROM CS4000............................................................... 14
Upload configuration file to a PC....................................................................................14
Upload configuration file to Salwico Memory StickTM ....................................................14
TO DOWNLOAD A CONFIGURATION FILE TO CS4000..............................................................15
Download configuration file from a PC...........................................................................15
Download configuration file from the Salwico Memory StickTM .....................................16
UPDATE THE BASE BOARD SOFTWARE ................................................................................... 17
Update the software version in the base board................................................................17
Possible errors during update of base board...................................................................18
Chapter 7: Service menu in CS4000 (access level 4)...........................................................19
1SYSTEM DETAILS................................................................................................................20
2SYSTEM BOARDS................................................................................................................21

Service & Maintenance manual Chapter 1: CS4000 block diagram
Salwico CS4000
1
3DISPLAY UNITS ..................................................................................................................25
4ZONES ................................................................................................................................26
5LOOPS.................................................................................................................................28
6RELOAD CONFIGURATION ..................................................................................................32
7LOAD CONFIG FROM MEMORY STICK .................................................................................33
8UPLOAD CONFIG TO MEMORY STICK..................................................................................34
9SAVE CHANGES TO CONFIGURATION...................................................................................35
10 UPLOAD SYSLOG TO MEMORY STICK ...............................................................................36
Appendix A: Fault codes & Fuses.........................................................................................37
FAULT LIST............................................................................................................................ 37
FUSES....................................................................................................................................41
Fuse list............................................................................................................................41
Fuse locations on base board, BB....................................................................................41
Fuse locations on rectifier board, RB..............................................................................41
Appendix B: Connections for loop units..............................................................................42
Appendix C: System modules................................................................................................45

Service & Maintenance manual Chapter 1: CS4000 block diagram
Salwico CS4000
2
Chapter 1: CS4000 block diagram
7
PQRS WXYZ
9
TUV
8
4
GHI MNO
6
JKL
5
1
' ' DEF
3
ABC
OK
Mute Next
DISC.FAULT FIRE
Reset
Menu
SALWICO
SG-6728
Pre-Alarm
OK
Warning
2
Zone/Unit
Alarm Delay
Alarm Transfer
Power
Alarm Device
Test
Disc.Home
System Fault 0

Service & Maintenance manual Chapter 1: CS4000 block diagram
Salwico CS4000
3
Chapter 2: Testing
Consilium recommends that the fire alarm system is tested at least
once a year to assure correct function.
The CS4000 has a special test mode, which makes the testing easier.
Characteristics for a zone in test mode:
It will not activate any external alarm devices or controls in
case of a fire (this function can be turned off).
The alarm level is lowered to give quick response to test gas.
Detectors and manual call points in the zone will blink.
Each tested detector and manual call point will indicate
activation with a red LED.
The units in alarm are automatically reset when the heat or
smoke concentration is under the alarm level or if the manual
call point is reset.
Fire alarms from zones not in test mode will be handled normally by
the system.
Note: The tested zone will automatically return to normal operation
after two hours.
Test a fire-detecting zone
Put the zone into test mode: Menu/ 3 Disconnections/ 1 New
disconn./ 5 Test Mode. Enter the zone number and confirm with OK
button
The indications DISC., TEST and ZONE/UNIT will be lit to confirm
the test mode.
It is now safe to test each detector, manual call point etc in this fire
zone during two hours. Use suitable testing equipment, available
from Consilium.
All alarms will be listed under: Menu/ 7 History/ 1 Fire History List
Heat detectors
Heat detectors are preferably tested with heat detector tester VDT-1,
part. no. 9300, available from Consilium.
Apply heat to the sensing element until alarm is indicated by
a red indication.
Important:
If other test equipments are used, for example cigarette lighter or
heating gun, make sure not to over-heat the detector by holding the
heat-source to close to the detector. This will damage the detectors,
for example causing the plastic to melt.

Service & Maintenance manual Chapter 1: CS4000 block diagram
Salwico CS4000
4
Smoke detectors
Smoke detectors are preferably tested with test gas equipment Solo
330, available from Consilium.
Spray test gas on to the detector during 0.5 second. Wait 10
seconds until new gas is sprayed during 1 second. Repeat this
procedure until the detector indicates alarm with a red
indication.
If other test methods are used, make sure not to damage the detector.
Flame detectors
Flame detectors may be tested with an ordinary cigarette lighter.
Turn up the flame to a height of approximately 5 cm. Hold it
in front of the detector at a distance of about 2-5 meters.
Move the lighter slowly during the test to obtain a flickering
flame until alarm is indicated with a red indication.
Test Fault conditions
The fire alarm central continuously monitors the
system components and will report any fault
condition on the control panel with both optical and
audible indication.
It is possible to test fault indications by following the
below procedures:
Please note that a fault condition is only possible to
reset when the cause is remedied.
Removed detector fault
1. Remove a detector.
2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. Reinsert the detector
4. Reset the fault condition on the control panel.
Fuse fault
Note: Before a fuse is removed, make sure which functions
that will be affected by the removal.
1. Remove a fuse.
2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. Reinsert the fuse.
4. Reset the fault condition on the control panel.

Service & Maintenance manual Chapter 1: CS4000 block diagram
Salwico CS4000
5
Battery fault
1. Remove a battery fuse.
2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. Reinsert the fuse.
4. Reset the fault condition on the control panel.
Earth fault
1. Connect one of the loop cables to earth via a
2,7kOhm resistor.
2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. Remove the earth connection.
4. Reset the fault condition on the control panel.
Loop cable break
1. Open up the loop cable.
2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute).
3. If the detector loop is double fed: Verify that
each of the two branches can detect fire alarms
by testing a detector on each branch.
4. Close the loop cable.
5. Reset the fault condition on the control panel.
Power supply
Test the back up power supply (emergency 230VAC
or batteries).
1. Removing the mains power supply.
2. Verify that the fault is indicated on the control
unit (this may take up to 1 minute), and that
the system remains operational.
3. If there is an emergency power supply in
addition to the batteries, remove this also. The
system should now operate on the batteries
only.
4. Connect all disconnected power supplies.
5. Reset the fault condition(s) on the control
panel.

Service & Maintenance manual Chapter 1: CS4000 block diagram
Salwico CS4000
6
Reset test mode
After testing it is important to return the tested zone into normal
condition again. Make sure that there are no detectors or manual call
points still in alarm before leaving test mode.
The zones in test mode are listed in the disconnection list, found
under: Menu/3 Disconnections /2 Disconnection list.
Choose the zone in the disconnection list and then press RESET.
Test the control unit display
It is possible to test the alphanumerical display, all indications on the
control panel and the local buzzer with the function Test display,
found under: Menu/ 5 Settings/ 4 Test display.

Service & Maintenance manual Chapter 3: Cleaning of fire detectors
Salwico CS4000
7
Chapter 3: Cleaning of fire detectors
The CS4000 fire alarm system continuously monitors the
detectors and will give early warnings if they are polluted or
malfunctioning in other ways. The methods for cleaning
detectors depends of the type of detector, see below.
If the cleaning is initiated by a “dirty sensor” fault in the
control panel, then try to reset this fault after cleaning. If this
does not succeed, replace the detector.
Smoke detectors
Clean the detector with a vacuum cleaner or by blowing
high-pressure instrument air on it.
The detector house is cleaned with a damp cloth.
Note: The high-pressure air must be of instrument type
(clean, not containing oil etc.)
Heat detectors
The sensor part does normally not need to be cleaned.
The detector house is cleaned with a damp cloth.
Flame detectors
Clean the protective glass over the sensor by a grease solvent
such as soap or alcohol.
The detector house is cleaned with a damp cloth.

Service & Maintenance manual Chapter 4: Replacing/Adding/Deleting fire detectors
Salwico CS4000
8
Chapter 4: Replacing/Adding/Deleting fire detectors
Replacing fire detectors
Instruction
1. Disconnect the faulty detector and remove it from the
base plate.
Note: Some bases have a lock mechanism on the side.
This lock shall either be pulled or pressed (depends on
base model).
2. Check the ID settings on the address switch for the faulty
detector. See section “ID address on DIP switches” for
explanation of the ID address.
3. Set the corresponding ID on the address switch for the
new detector.
4. Seal the address switch on the detectors with the attached
label after the address has been set.
5. Connect and mount the new detector.
6. Check and reset any fault codes generated by the
replaced faulty detector.
7. Perform a function test of the detector according to the
chapter Testing.
ID address on DIP switches
All addressable loop units must be given an address between
1-254 to be operational. The loop units located on the same
physical loop must all have unique addresses. The address is
set either by a 8 pole DIP switch located on each addressable
unit, or (for units without physical address switch) with the
address programming tool EV-AD. (See separate instruction)
The DIP switch values follow the binary system.
12345678
O
N
1 2 4 8 16 32 64 128
The value of the address is set according to the switches set
to ON position. For example:
12345678
O
N
=47
The switches numbered 1,2,3,4 and 6 are set to ON position.
The values for these switches are 1+2+4+8+32=47.
Important: Seal the address switch on the detectors with the
attached label after the address has been set.

Service & Maintenance manual Chapter 4: Replacing/Adding/Deleting fire detectors
Salwico CS4000
9
Hot Plug&Play (adding/deleting loop units)
The CS4000 system is equipped with a Hot Plug&Play
function enabling the user to add or delete detectors during
normal operation without the need to change the
configuration file with a PC and restarting the system.
The configuration file may be updated during normal
operation from service menu 6:5 or direct from the fault list,
menu 1.1.
This function is very useful, especially during installation. If
the CS4000 central detects additional or missing loop units,
they are simply added to/deleted from the configuration file
during normal operation.
Note: The changes to the configuration file is updated in the
RAM memory, but will not saved permanently until it has
been saved under: Menu/ 6 Service menu/ 9 Save changes to
configuration. If the configuration file is not changed
permanently, any changes done will be lost if the system is
re-started.
Change configuration file from the fault list
Adding a loop unit from the fault list
If the CS4000 detects additional or missing loop units
compared to the configuration file, they are added to the fault
list.
1. Open the fault list: Menu/ 1 Fault alarms/ 1 Fault list
2. Select the detector to add from the list (fault no. 3 is
selected in the below example).
Loop Units generating fault no 152 (present not
configured) can be added to the systems
configuration.
FAULT ALARM 4(5)
________________________________________
3 LOOP 603 SMOKE HEAT 2 PRESENT NOT
CONFIGURED, FAULT(152) .
Unit not found .
4 ZONE 111 UNKNOWN LOOP DEVICE 3 NO
ANSWER, FAULT(128)
txt
5 LOOP ANALOGUE 601 CABLE BREAK
POSITIVE, FAULT(141)
Loop 1 on LB3 6
________________________________________
0=Add Loop Unit to configuration
OK=Details, 1=Print item, 2=Print all
3. Press 0=Add Loop Unit to configuration

Service & Maintenance manual Chapter 4: Replacing/Adding/Deleting fire detectors
Salwico CS4000
10
4. Enter the data required for the new loop unit in dialog
box Add loop unit.
Central, Board, Loop and Zone must exist in the
Systems Configuration to be valid.
Physical Unit Address may NOT exist on the physical
loop already.
Logical Zone number may NOT exist on the chosen
Zone.
T1 and T2 are supplementary Text 1 and 2, and are
entered as on a Mobile Telephone.
ADD LOOP UNIT
________________________________________
Physical Central addr.: 1 (valid) .
Physical Board address: 6 (valid)
Physical Loop address : 2 (valid)
Physical Unit address : 0 (invalid)
Logical Zone number : 0 (invalid)
Logical Unit address : 0 (invalid)
Type: 202 (invalid)
T1:
T2:
________________________________________
Enter value with numeric keyboard.
UP/DOWN=New field,OK=Add Unit,'<'=Exit
5. Press OK. The configuration file is now updated in
the RAM memory. Wait approx. 20 sec. before reset.
6. Reset the fault. The fault will only be resettable if the
system succeeded to add the loop unit.
Deleting a loop unit from the fault list
1. Open the fault list: Menu/ 1 Fault alarms/ 1 Fault list
2. Select the detector to delete from the list. Loop Units
generating fault no 128 (no answer) can be erased
from the systems configuration.
3. Press 0=Erase Loop Unit from configuration. The
configuration file is now updated in the RAM
memory.
4. Reset the fault. The fault will only be resettable if the
system succeeded in adding the loop unit.

Service & Maintenance manual Chapter 4: Replacing/Adding/Deleting fire detectors
Salwico CS4000
11
Change configuration file from the service
menu
Adding a loop unit from the service menu
1. Open the service menu: Menu/ 6 Service menu/ 5
Loops
2. Select an analogue loop from the loop list (loop no. 2
is selected in the below example). Press 3=Add Unit.
LOOP 2(19)
________________________________________
1 LOOP ANALOGUE 601
Loop 1 on LB3 6
24 Loop Units Expected
2 LOOP ANALOGUE 602 .
Loop 2 on LB3 6 .
11 loop Units Expected .
3 LOOP ANALOGUE 603
Loop 3 on LB3 6
0 Loop Units Expected
________________________________________
OK=Details, 0=Disconnect, 1=Print List
2=Loops Units,3=Add Unit,4=Scan loop
3. Enter the data required for the new loop unit in dialog
box Add loop unit.
Central, Board, Loop and Zone must exist in the
Systems Configuration to be valid.
Physical Unit Address may NOT exist on the physical
loop already.
Logical Zone number may NOT exist on the chosen
Zone.
T1 and T2 are supplementary Text 1 and 2, and are
entered in the same way as on a Mobile Telephone
with the alpha-numerical keyboard.
ADD LOOP UNIT
________________________________________
Physical Central addr.: 1 (valid) .
Physical Board address: 6 (valid)
Physical Loop address : 2 (valid)
Physical Unit address : 0 (invalid)
Logical Zone number : 0 (invalid)
Logical Unit address : 0 (invalid)
Type: 202 (invalid)
T1:
T2:
________________________________________
Enter value with numeric keyboard.
UP/DOWN=New field,OK=Add Unit,'<'=Exit
4. Press OK. The configuration file is now updated in
the RAM memory.

Service & Maintenance manual Chapter 4: Replacing/Adding/Deleting fire detectors
Salwico CS4000
12
Deleting a loop unit from the service menu
1. Open the service menu: Menu/ 6 Service menu/ 5
Loops.
2. Select an analogue loop from the loop list (loop no. 2
is selected in the below example). Press 2=Loop
Units.
LOOP 2(19)
________________________________________
1 LOOP ANALOGUE 601
Loop 1 on LB3 6
24 Loop Units Expected
2 LOOP ANALOGUE 602 .
Loop 2 on LB3 6 .
11 loop Units Expected .
3 LOOP ANALOGUE 603
Loop 3 on LB3 6
0 Loop Units Expected
________________________________________
OK=Details, 0=Disconnect, 1=Print List
2=Loops Units,3=Add Unit,4=Scan loop
3. Select a loop unit to delete from the list Loop units.
Press 3=Erase Loop Unit
LOOP UNITS 1(11)
_________________________________
1 LOOP 602 MCP 1 (A/B)
2 LOOP 602 SCI 2 (A/B)
3 LOOP 602 MCP 3 (A/B)
4 LOOP 602 SCI 4 (A/B)
5 LOOP 602 MCP 5 (A/B) .
6 LOOP 602 MCP 7 (A/B)
7 LOOP 602 SCI 8 (A/B)
8 LOOP 602 MCP 9 (A/B)
9 LOOP 602 SCI 10 (A/B)
10 LOOP 602 MCP 11 (A/B)
11 LOOP 602 SMOKE 201 (A/B)
________________________________________
OK=Details, 0=Disconnect, 1=Print List
2=Set In Fire, 3=Erase Loop Unit
4. The configuration file is now updated in the RAM
memory.

Service & Maintenance manual Chapter 5: Replacing battery
Salwico CS4000
13
Chapter 5: Replacing battery
When replacing the batteries, make sure to use batteries with
the same specification as the original. System is tested and
approved according to EN 54-2 and EN 54-4 with two Yuasa
2.3 Ah type NP-12 batteries connected in series.
The maximum current draw from the battery is 2.5A and it is
fused to 4A.
The maximum internal battery circuitry resistance is 0.47
Ohm.
Instruction
1. Remove both battery fuses at the rectifier board.
See Appendix A for fuse locations.
2. Remove the battery cables from the battery.
3. Exchange the battery.
4. Verify the correct polarity and connect the battery
cables to the new battery.
5. Verify that the voltage is approx. 24VDC at the
battery terminals on the rectifier board.
6. Reinsert the battery fuses.
7. Reset the battery fault at the control unit.

Service & Maintenance manual Chapter 6: Software
Salwico CS4000
14
Chapter 6: Software
Configuration program
The CS4000 central is delivered pre-programmed with a
standard configuration file. See the separate manual
CS4000 Configuration program manual for information on
how to create and update a configuration file.
To upload a configuration file from CS4000
When you want to view or make changes in an existing
configuration file you can get it from the CS4000 central.
The configuration file can be uploaded in two ways:
Direct to PC via USB cable
To Salwico Memory StickTM
(the system must be equipped with an USB
Expansion Board)
Upload configuration file to a PC
1. Connect a PC via an USB cable to the USB
port on the Base Board (not the USB
Expansion Board, if present).
2. The CS4000 will now present itself as an
extra “drive” in your PC. Open the extra
drive.
3. You will find a file with the file extension
“.c4d”, which is the configuration file used by
the CS4000 system.
Example of file name: SG12345.C4D
4. Copy the “.c4d” file to your local disc before
working with it.
Upload configuration file to Salwico Memory
StickTM
1. Connect the Salwico Memory StickTM to one of the
USB ports on the USB expansion board (piggyback
board located on the BaseBoard).
2. Choose Menu/ 6 Service/ 8 upload config to Memory
Stick
3. Choose the current “.c4d” configuration file from the
list and press OK.
4. The system will now upload the configuration file.
5. When the upload is complete, disconnect the Salwico
Memory StickTM and copy the configuration file to a
PC.

Service & Maintenance manual Chapter 6: Software
Salwico CS4000
15
To download a configuration file to CS4000
When the configuration file is finished it is time to download
it to the CS4000 system. The configuration file must have the
file extension “.c4d”.
If only supplementary texts has been updated in the “.c4d”
file it is possible download them separately, see below
instructions.
The configuration file can be downloaded in two ways:
Direct from PC via USB cable
From Salwico Memory StickTM
(the system must be equipped with an USB
Expansion Board)
Note:
Make sure to work with the latest “.c4d” file when making
changes. The latest “.c4d” file may be uploaded from the
CS4000 system, see instruction above.
In Base Board software versions before 1.0.18 the definition
file must be named “current.c4d”
Download configuration file from a PC
1. Connect a PC via an USB cable to the USB port on
the Base Board (not the USB Expansion Board, if
present).
2. The CS4000 will now be displayed as an extra
“drive” in your PC. Open the extra drive.
3. Change the file extension on the current configuration
file to “.old” and save it as a back-up file.
4. Copy the new configuration file with the file
extension “.c4d” from the PC to the extra drive.
5. When the file copy is completed, remove the USB
cable from the Base Board.
6. Use the CS4000 control panel to update the system
with the new configuration file by choosing:
-Menu/ 6 Service menu/ 6 Reload Configuration/
1 Load entire configuration
or
-Menu/ 6 Service menu/ 6 Reload Configuration/
2 Load supplementary texts only
7. If 1 Load entire configuration is selected above, the
Base Board will re-start and load the new
configuration file.
If 2 Load supplementary texts only are selected, the
system will use the new texts without having to re-
start. Any other changes made to the “.c4d” file will
be ignored, but will come into effect the next time the
system is re-started.

Service & Maintenance manual Chapter 6: Software
Salwico CS4000
16
Download configuration file from the Salwico
Memory StickTM
1. Connect the Salwico Memory StickTM to one of the
USB ports on the USB expansion board (piggyback
board located on the Base Board).
2. Choose Menu/ 6 Service/ 7 load config from Memory
Stick
3. A list of the available “.c4d” files on the Salwico
Memory StickTM will be presented. Choose the
appropriate “.c4d” configuration file from the list and
press OK.
4. The new configuration file is downloaded to the
CS4000.
The old configuration file is automatically renamed
by the system and saved on the Salwico Memory
StickTM.
5. Disconnect the Salwico Memory StickTM
6. Use the CS4000 control panel to update the system
with the new configuration file by choosing:
-Menu/ 6 Service menu/ 6 Reload Configuration/
1 Load entire configuration
or
-Menu/ 6 Service menu/ 6 Reload Configuration/
2 Load supplementary texts only
7. If 1 Load entire configuration is selected above, the
Base Board will re-start and load the new
configuration file.
If 2 Load supplementary texts only is selected, the
system will use the new texts without having to re-
start. Any other changes made to the “.c4d” file will
be ignored, but will come into effect the next time the
system is re-started.

Service & Maintenance manual Chapter 6: Software
Salwico CS4000
17
Update the base board software
There are two flash memories in the base board:
flash1 containing bootloader and the software for the
base board (flash1.img).
flash2 containing the definition file (current.c4d)
Update the software version in the base board
Follow the below instructions to update the software version
in the base board by using an USB cable.
1. Please note how the DIP switch on the base board
(see figure below) is set, since this setting shall be
restored after the update of the software.
2. Set the base board in “bootloader” mode by setting
the DIP switch address to 0 (all switches in OFF
position).
3. Reboot the base board with the reset button.
LED1 will indicate that the base board is in
“bootloader” mode by flashing light.
4. Connect the PC to the base board via an USB cable.
The base board will appear in Windows Explorer as
an extra USB drive.
5. Copy the new software file named “flash1.img” from
the PC to the USB drive (drag & drop).
6. Close the extra USB drive in Windows Explorer. The
base board will now start to download the new file
into flash1. LED2 will indicate this by flashing light.
The download process is finished when LED2 turns
into steady light.
7. Restore the original address on the DIP switch.
8. Reset the base board with the reset button. The base
board will now re-start, using the new updated
software.
Description of the LEDs during update of software:
Flashing LED on LED off
Led1,
Yellow Bootloader
mode
Led2,
Yellow Writing to flash Writing to flash
completed Writing to flash has not started
Led3, Red Checksum error Checksum OK
DIP switch
CP
Led1 Reset button
Led2
Led3
I
llustration base board
Other manuals for Salwico CS4000
2
Table of contents
Other Consilium Fire Alarm manuals