Consilium Salwico MCP-C WP User manual


1(3) DATA SHEET
The specifications described herein are subject to change without notice. Data sheet no. 5200014-01A MCP-C WP.12 1.ME
www.consilium.se
Manual Call Point IP67
Salwico MCP-C WP
(GB)
Part no. 5200014-01A
System: Salwico Cargo, Salwico Cruise, Salwico Workboat,
Salwico Yacht, Salwico RoPax, CS4000, ServoFighter, C300,
C303, C308, C316
General Description
The MCP-C is a manual call point for outdoor
environment and is designed for the Salwico
conventional fire alarm systems.
The selected material PC/ABS and the
encapsulation, with ingress protection IP67, makes
it very suitable for harsh environment.
Pressing the glass causing it to crack activates the
fire alarm. A protective plastic coating on the glass
prevents operator injury.
The call point can be tested with a special key
included in the delivery.
Data
Nominal voltage 24 VDC
Working voltage 16-30 VDC
Supervising current 0 mA
Alarm current ~90 mA
Ingress protection IP67
Temperature range -25ºC to +70ºC
Ambient humidity 0 to 95% RH
Material PC/ABS
Colour Red
Weight 240 g
Cable dimension Ø6-14 mm
Certified according to
0832
Spare glasses (10pcs.) Part no.
5200075-00A
Connection
NOTE!
After the last section unit, add an End of
line resistor between terminals 2 and 4 or
6 and 8 (for servofighter) according to
system specification.

DATA SHEET 2(3)
The specifications described herein are subject to change without notice. Data sheet no. 5200014-01A MCP-C WP.12 1.ME
www.consilium.se
Test
Cover removal
Remove the four cover fixing screws. Place the edge of a large flat bladed screwdriver into the slot between
the cover and back box, as shown in picture, and gently twist until the latches are disengaged. Pull cover
away from the back box.
Change Glass

3(3) DATA SHEET
The specifications described herein are subject to change without notice. Data sheet no. 5200014-01A MCP-C WP.12 1.ME
www.consilium.se
Dimensions (mm)

Specifications may be subject to change for improvement without prior notice
ÇConsilium Consilium Marine AB
P.O. Box 8763 SE-402 76 Göteborg Sweden
Phone +46 31 710 77 00 Fax +46 31 710 78 00
www.consilium.se
IP55 base
Salwico 2IP55
Part no. 46950
System: All Salwico fire alarm systems
Description
The 2IP55 is a base for all Salwico IP55 detector adapters.
Together with the adapters it is possible to install smoke,
heat and flame detectors in harsh environment with an
ingress protection up to IP55.
It can be used for both addressable and conventional fire
alarm systems.
Data
able diameter Ø6-14 mm
Ingress protection IP55
Fire class V1
Temperature range -30º to +100º
Material Polyamide/glass (PA666, 15% GW)
olour White
Weight ~100 g
Data sheet no: 46950.03.1.E
Dimensions (mm)

Optical Smoke Detector
Salwico DOS3
Part no. N1115
System: Salwico conventional fire alarm systems
Description
The DOS3 is a low profile conventional optical smoke detector
designed to combine optimal response to smoke with a strong
immunity to false and unwanted alarms.
The sensor employs an alarm verification function, which
requires two successive pulses before an alarm is given.
The detector design provides strong immunity to air velocities,
contamination and EMC. By means of a special protective mesh it
is ensured that smoke can enter the detector easily whilst
accessibility to insects and airborne contaminants is eliminated.
The DOS3 detector can be mounted on bases for use in both dry
spaces and in harsh environments.
The DOS3 is compatible with the OD-5 smoke detector.
Data
Operating principle Conventional, optical,
light scattering type, infrared
Nominal voltage 24VDC
Working voltage 17-30VDC
Operating current
- supervising max 40 µA at 24 VDC
- alarm max 55 mA
- extra LED max 20 mA at 6 V
Alarm resistance 430Ω
Temperature range -25ºC to +70ºC
Ambient Humidity 0 – 95% RH
Ingress protection IP42 / IP55 depending on base
Weight (head only) 95 g
Colour White
Detector Bases
For information about suitable base plates, see separate
document “Base matrix for Salwico units”.
Dimensions (mm)
Connection
L3
C6
P1
R4
L3
C6
P1
R4
+
–
+
–
+
–
– + – +
10 kΩ
LAST UNIT
Fire alarm
system
Output to
external LED
Output to
external LED
Specifications may be subject to change for improvement without prior notice Data sheet no: N1115.06.1.E
ÇConsilium Consilium Marine AB
P.O. Box 8763, SE-402 76 Göteborg
Phone +46 31 7107700 Fax +46 31 7107800
www.consilium.se

1(3) DATA SHEET
The specifications described herein are subject to change without notice. Data sheet no. 5200010-01A MCP-C.12 1.ME
www.consilium.se
Manual Call Point IP24
Salwico MCP-C (GB)
Part no. 5200010-01A
System: Salwico Cargo, Salwico Cruise, Salwico Workboat,
Salwico Yacht, Salwico RoPax, CS4000, ServoFighter, C300,
C303, C308, C316
General Description
The MCP-C is a manual call point for indoor
environment and is designed for the Salwico
conventional fire alarm systems.
Pressing the glass causing it to crack activates the
fire alarm. A protective plastic coating on the glass
prevents operator injury.
The call point can be tested with a special key
included in the delivery.
Data
Nominal voltage 24 VDC
Working voltage 16-30 VDC
Supervising current 0 mA
Alarm current ~90 mA
Ingress protection IP24
Temperature range -10ºC to +55ºC
Ambient humidity 0 to 95% RH
Material PC/ABS
Colour Red
Weight 160 g
Cable dimension Ø6-14 mm
Certified according to
0832
Spare glasses (10pcs.) Part no.
5200075-00A
Connection
NOTE!
After the last section unit, add an End of
line resistor between terminals 2 and 4 or
6 and 8 (for servofighter) according to
system specification.

DATA SHEET 2(3)
The specifications described herein are subject to change without notice. Data sheet no. 5200010-01A MCP-C.12 1.ME
www.consilium.se
Test
Change Glass
Dimensions (mm)

3(3) DATA SHEET
The specifications described herein are subject to change without notice. Data sheet no. 5200010-01A MCP-C.12 1.ME
www.consilium.se
Mounting Dimensions (mm)

1(3) DATA SHEET
The specifications described herein are subject to change without notice. Data sheet no. 5200236-00A_Salwico AC-IR-3Fq_M_EN_2014_E
www.consilium.se
Addressable/Conventional
IR Flame Detector
Salwico AC-IR-3Fq
Part no. 5200236-00A
System: Depends on base. See Datasheet for: 5200235-00A
Salwico AC-IR-3Fq Conventional Base and 5200237-00A
Salwico AC-IR-3Fq Addressable Base
General Description
The AC-IR-3Fq is a triple frequency conventional
infrared flame detector produced using the latest
in manufacturing technology. It is supplied with an
array of advanced features, making it ‘better by
design’.
The Detector is using infrared elements suitable
for the detection of smokeless combustible liquid
and gas fires, as well as smoke-forming open fire
involving carbonaceous materials as contained in
wood, plastics, gases, oil products etc.
The Fire evaluation process is done by triple
Infrared (3Fq) sensor, protected by a sapphire
glass filtering >6.0µm wavelength radiation.
Sensor measures the hot carbon dioxide in a
specific flame wavelength; the B and C sensors
simultaneously measure the interference radiation
in near wavelengths.
This technique together with intelligent signal
processing through microprocessor and custom
algorithms, achieves excellent detection reliability
while maintaining the highest immunity to
interference radiation and sunlight.
Testing
For functional test, use Salwico IR Test lamp, part
no. 001156. Due to the detectors high immunity
to unwanted alarms, it is difficult to test the
detector without the IR test lamp.
Features
•Triple Frequency IR Detector
•Low current draw
•Suitable for installation in damp environment
•Easy Maintenance
•Remote LED Option
•Approved to UNI EN54-10 Ed. 2002
Data
Electrical Specifications
Operating Voltage Range 24 V DC
Supply Voltage 24 V DC
Max Current (Normal) 450 µA
Max Current Detector 700 µA (Alarm)
Addressable Mode 1 mA (Alarm incl. Base)
Conventional Mode 30 mA (Alarm Incl. Base)
Environmental Specifications
Application Temperature
Range
-25 °C to +75 °C
Humidity Up to 95%
Mechanical Information
Height 69 mm (including base)
Diameter 103 mm
Weight 250 g
Weight with IP65 Base 380 g
Wire Gauge for Terminals 2.5 mm2
Colour White RAL9010
Material Polycarbonate Flame
Retarded Cl. UL94V0
IP Rating IP65 (IP67 with locking
screws)
Certified according to 0474/yy
yy = year of production
Detector Base
5200235-00A Salwico AC-IR-3Fq Conventional Base
5200237-00A Salwico AC-IR-3Fq Addressable Base
Test Equipment
001156 Salwico IR Test lamp

DATA SHEET 2(3)
The specifications described herein are subject to change without notice. Data sheet no. 5200236-00A_Salwico AC-IR-3Fq_M_EN_2014_E
www.consilium.se
Installation
For featured wiring the detector is installed on a
base, provided in IP65 proof version.
The detector is connected to the base through a
fast bayonet clutching and a flying connector.
Certain factors need to be considered when
designing an installation:
•The sensors should be mounted so that
objects do not block their field-of-view (FOV).
This includes glass, Plexiglas and other visibly
transparent materials. Contact Consilium for
more information.
•Whenever possible, sensors should be
mounted so their ranges and fields-of-view
overlap.
•Sensors should be mounted so their FOV
cannot be choppered by moving machinery or
human operators during normal operations
within the area. Therefore they should be
installed as high as possible or on the ceiling.
•Detector window should not be exposed to
hot or cold intermittent airflow which could
change the temperature of the detector itself
or detector FOV background.
•To ensure optimum sensitivity and
performance, sensors should be mounted so
they do not look at hot surfaces: if this is
necessary first follow procedure to ensure no
chopper is present.
•The sensors should be mounted so that they
are easily and safely accessible for inspection
and maintenance.
•If mechanical, high-temperature damage, or
window contamination is likely to occur in the
installed location, then the sensor should be
protected. However the protection method
cannot obstruct the sensors FOV with any
material, including visibly transparent materials,
such as glass and Plexiglas.
•The sensor can be mounted in any
orientation, as long as captive screws are
removed or can be removed.
•Mounting the sensor so that it points
downwards is recommended as this generally
results in minimal window contamination.
•Care must be taken to avoid that sensor
installation exceeds environmental approvals
such as temperature, shocks, vibrations.
•Care must be taken to avoid that sensor
installation exceeds electromagnetic
interference approval: in particular install
detectors in places out-of-reach of personnel
(including contractors and crew members).
•It is important NOT to leave any extra cable
slack when installing this detector.
•Cable shield shall be connected to the ground
on one side only.
•The DIP-Switch Setting recommended by
Consilium is to turn Sw.No.2 ON for the
highest sensitivity. For more details, see
Settings.
For more details, see Flame Detector Installation
manual 5100512.
Hint!
For outdoor mounting: Fit the detector
screws on the base to ensure IP67
Protection Index.
Angle of Reception
Dimensions (mm)

3(3) DATA SHEET
The specifications described herein are subject to change without notice. Data sheet no. 5200236-00A_Salwico AC-IR-3Fq_M_EN_2014_E
www.consilium.se
Settings
S1 DIP-Switch setup
Figure 1. DIP-Switch Setting.
Use the 4-ways Dip-switch S1 to set the detector
as Conventional or Addressable and preset
sensitivity threshold (Class):
Table 1. DIP-Switch Setting
Sensitivity
class Sw.No.1 Sw.No.2 Sensitivity
Class 1* OFF ON High up to 27 m
Class 2 ON OFF Medium up to 17 m
Class 3** OFF OFF Low up to 12 m
Table 2. Conventional Mode
Mode Sw.No.3 Sw.No.4
Conventional ON ON
Only when used with Base 5200235-00A.
Table 3. Addressable Mode
Mode Sw.No.3 Sw.No.4
Addressable** OFF OFF
Only when used with Base 5200237-00A.
* Recommended setting by Consilium
** Default factory setting

1(2) DATA SHEET
The specifications described herein are subject to change without notice. Data sheet no. 046916_SPB-ADAPT_I0_EN_2013_C
www.cnsystem.se
Base Adapter
SPB-ADAPT
Part no. 046916
System: All Salwico Fire Alarm Systems
General Description
SPB-ADAPT is an adapter for the bases 2IP55
(part. no. 046950) and NS-2IP55 (part no.
046900).
SPB-ADAPT is developed to replace the adapters
SPB-1 (part no. 046915) and NS-ADAPT (part
no. N1421).
Smoke, heat and flame detectors can be
connected to this adapter. For more information
about suitable bases, see separate document
“Base matrix”.
The adapter can be used for all Salwico fire alarm
systems.
Data
Cable terminals 2.5 mm2
Ingress protection IP55 (mounted on a base)
Material PC/ABS
Colour White
Weight ~110 g
Important Mounting Instructions
The mounting screws shall be fitted with the following
torque:
Min. 1.3 Nm
Recommended 1.7 Nm
Max. 2.0 Nm
Dimensions (mm)

DATA SHEET 2(2)
The specifications described herein are subject to change without notice. Data sheet no. 046916_SPB-ADAPT_I0_EN_2013_C
www.cnsystem.se
Connection
Connection of addressable detectors IA, OA, TDT and EV-PP series:
Connection of addressable detectors NS, CN and EV-series** (EV-PP excluded):
Connection of conventional detectors DIS3, DOS3, HC100,NS-DIR and NS-DUV:
Connection of conventional flame detectors EVC-IR (not NS-DIR or NS-DUV):
* All types of detectors do not have the remote output. Please refer to the data sheet for the detector in
question.
** For loop units with short circuit isolators, see connection on data sheet for that unit.
This manual suits for next models
1
Table of contents
Other Consilium Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Plymovent
Plymovent Shield 5k1 Installation and user manual

LST
LST FI750/RF/PA instructions

LY International Electronics
LY International Electronics M-9000 Series user manual

Faraday
Faraday 15220A owner's manual

Fireboy- Xintex
Fireboy- Xintex FR-1000 installation manual

Notifier
Notifier AVL-1 Operation and installation manual

Siemens
Siemens SFPO-11 Installation instructions manual

UniPOS
UniPOS IFS7002 instruction manual

System Sensor
System Sensor 22051TLE-RF Installation and maintenance instructions

Wheelock
Wheelock RSS-24MCW installation instructions

Fusion
Fusion FBUS Series Installation & commissioning manual

Wheelock
Wheelock Series RSS specification