Cooper Menvier Scantronic 714r User manual

Introduction
The 714r Passive Infra Red (PIR) is an indoor detector designed to work with Scantronic
868MHz receivers. The PIR detects movement of body heat. The detector has a fan
shaped sensitive area approximately 15 metres in radius. The case is protected by an in-
ternal tamper switch. The back of the case can be modified by removing a cutout to pro-
vide a wall tamper.
Specification
Part No. 714rEUR-00
Power Supply 1 x AA 3.6V Lithium cell
Battery Life Approximately 14 months
Operating temp: -10 to +55 °C
Environmental Class I (tested -10 to +55°C)
Low voltage alarm: 2.4V nominal
Lens: Standard 15m x 90 deg.
White light filter: greater than 2000 Lux
RF Immunity: 10V/m
Dimensions: 82mm x 71mm x 47mm x (HxWxD)
Operating Frequency: 868,6625 MHz
Security Grade II
INCERT C016xxxxx
Specification subject to change without notice.
Siting
You can mount the unit either flat against the wall, or in a corner. The area covered by the
detector is shown below.
2.4m
(max) 15m
DO mount the unit between 1.8 and 2.4 metres high for the best general coverage in an
average room.
Do NOT mount the unit:
Facing a fire, boiler or window.
Over a radiator.
Near the floor.
Close to or on large metal structures.
Closer than one metre to mains wiring and metal water or gas pipes.
Inside steel enclosures.
Next to electronic equipment, particularly computers, photocopiers or other radio
equipment.
Closer than 30mm to a ceiling (to allow space for dismounting the unit in the future).
Installation
Open the detector by lifting the flap at the top of the case and removing the screw con-
cealed underneath.
Install one ‘AA’ size 3.6V lithium battery (supplied).
Note: If the transmitter shows a continuously pulsing glow from the activity LED then a
fault has occurred or the battery is totally exhausted. Replace the battery and
check that the activity LED is working normally.
Pet Alley
1. Remove the PCB from the sensor funnel.
2. Swing down the pet alley mirror . This deletes all but the top row of the detector
zones.
Note: When using the pet alley mirror mount the detector at 1.6m height in order to main-
tain correct coverage with the upper detector zones. Pet immunity extends for
10m. Do not use this facility in larger areas.
3. Refit the pcb to the sensor funnel .
Mount the back
The 714r is designed for mounting by any of the methods shown below. The case back
contains a number of possible fixing holes, marked by mouldings in the plastic. Chose two
to suit the location you have selected, and drill them out carefully.
1. Hold the back in location and mark and drill 5mm fixing holes in the wall.
2. Secure the back to the wall with 16mm countersunk head screws and wall plugs.
3. Clip the body of the detector to the back.
Fitting a Wall Tamper
If you wish to fit a wall tamper:
1. Cut out the large circle indicated in the back of the case (see Figure below).
Make sure that you remove enough material so that the head of the tamper
switch can pass freely through the back of the case.
2. Mark the position of this circle on the wall at the place where the case back will be
fitted.
3. Drill and plug a hole in the wall at the marked position, and insert a M3 (No 4)
screw. Make sure the head of the screw is no more than 2.5 mm from the wall.
Caution: Do not allow the head of the screw to
protrude more than 2.5mm from the wall
or you may damage the PIR.
4. Mount the case back so that the head of the screw protrudes through the cut out
and engages the tamper switch when the body of the detector is fitted (see Figure
below).
You may have to adjust the height of the screw until it operates the tamper switch. The
body of the PIR should fit easily into the case back without force.
Fitting a Corner Wall Tamper
If you want to fit the 714r in a corner and also fit a wall tamper then you should use the
Scantronic Corner Wall Tamper Bracket (Part No. 235385). The Figure below shows the
item.
To fit a wall tamper in a corner mounting:
1. Fit the bracket into the corner. Make sure that it is the correct way up. The stud
on the end of the arm should be at the left.
2. Cut out the large circle indicated in the back of the PIR case. Make sure that you
remove enough material so that the stud of the Wall Tamper Bracket can pass
freely through the back of the case.
3. Fit the PIR case back into the corner on top of the Corner Wall Tamper Bracket.
Make sure the stud on the bracket passes through the hole in the back of the PIR
case (see Figure above).
4. Fit the body of the PIR to the case back. The body of the PIR should fit easily into
the case back without force.
Learning
Consult the relevant section in the receiver’s Installation and Programming Guide.
Wall tamper
knock out
M3 (No4) screw no
more than 2.5 mm
proud from wall
Pet Alley mirror raised
Vertical
corner
mount
Flat wall
mount
Look down zone
Pet Alley mirror lowered

714r
Passive Infra Red
Installation Guide
Testing.
1. Put the control unit into walk test.
2. Hold the detector in place.
3. Trigger the detector.
4. Make sure the panel receives the alarm.
5. Chose another site for the detector if the panel does not receive the signal.
6. Stop the walk test at the control unit.
PIR Testing and Lockout
In normal use the 714r uses a lockout timer in order to extend battery life. The lockout
timer works like this:
a) The unit detects movement, signals the panel, and starts the lockout timer.
b) When the lockout timer expires the unit signals the panel the next time it detects
movement.
Cooper Security Ltd set the lockout timer to three minutes when the 714r leaves the fac-
tory. If you wish to change the lockout timer to one minute then remove the jumper link on
the back of the PCB. (Replace the link to restore the lockout timer to three minutes.) Coo-
per Security Ltd recommends that you leave the jumper fitted. Removing the jumper for
long periods will reduce the life of the battery.
If you want to test a 714r in normal use you should leave the protected area and wait at
least four minutes between activations (two minutes if you have removed the link). To
make testing easier the detector changes the lockout period to 10 seconds for the first half
hour after you put the battery in, or after you trigger its tamper.
Note: Make sure the control unit is in programming mode before you open or move any
of the detectors. This will avoid setting the tamper alarm off.
When you have fitted and adjusted the 714r test the operation of the complete detector as
follows:
1. Put the control unit into walk test.
2. Clear the protected area and make four random direction walk tests. Using an adult
human, walk at a rate of one normal step per second within the detection pattern.
The unit should alarm within three out of the four walk tests.
3. Stand outside the protected pattern and operate any potential cause of false alarm,
e.g., operate lights, open doors, etc. If the unit detects the deliberate cause of false
alarm, try readjusting the detector pattern.
4. Stand outside the detection pattern and observe the detector operation for three to
five minutes without doing anything. The detector should not alarm. If the detector
does alarm, locate the cause and correct it.
Note: When walk testing, cross the sensitive zones at right angles in an upright position.
The LED remains off if the battery has been in for longer than 30 minutes, or if
you have not triggered the detector tamper within the last 30 minutes.
Maintenance
Inspect the 714r one or more times a year. The inspection should consist of , but be not
limited to, the mounting, the battery, cleaning dust from the lens with a soft cloth, walk
testing and unit operation.
Service
If the transmitter shows a continuously pulsing glow from the activity LED then a fault has
occurred or the battery is totally exhausted. Replace the battery and check that the activity
LED is working normally.
If the activity LED still gives a pulsing glow after inserting a good battery then the unit has
a fault. Return the unit to your supplier.
© Cooper Security Limited 2004
Every effort has been made to ensure that the contents of this leaflet are correct .
However, neither the authors nor Cooper Security Limited accept any liability for loss or
damage caused or alleged to be caused directly or indirectly by this leaflet. The contents
of this leaflet are subject to change without notice.
Printed and published in the U.K.
Product Support (UK) Tel: +44 (0)870 757 5400
Available between:
08:15 and 17:00 Monday to Thursday,
08:15 to 12:45 Friday,
Emergency service only 12:45 to 17:00 Friday
Product Support Fax: (01594) 545401
Part No. 496939 Issue 1
EC DECLARATION OF CONFORMANCE
Cooper Security Ltd
Security House
Vantage Point Business Village
Mitcheldean
Gloucestershire
GL17 0SZ
Declares that the product known hereinafter as:
714r Passive Infra Red
manufactured by Cooper Security Ltd. fully complies with the require-
ments of the following European Directive:
1995/5/EC
(Radio &Telecommunications Terminal Equipment Directive):
In accordance with the standards set out in:
EN 301 489 1 & 3 EN 50131-1
EN 50131-2-2 EN 50131-3
EN 50131-5-3 EN 60950
ETS 300 220
Signed
Stewart Taylor, Technical Director
Date: 11 March 2004
This manual suits for next models
1
Other Cooper Menvier Security Sensor manuals