Cotes CR240 User manual

CR240 USER MANUAL
1/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
CR240 USER MANUAL
Original instructions
How to install, set up, operate and service
your Cotes CR240 dehumidifier
27394

CR240 USER MANUAL
2/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
TABLE OF CONTENTS
IMPORTANT INFORMATION ........................................................................................................................................- 3 -
1 / ABOUT THIS HANDBOOK......................................................................................................................................- 4 -
1.1 GENERAL BACKGROUND.....................................................................................................................................................................- 4 -
1.2 SYMBOLS USED IN THIS HANDBOOK ...........................................................................................................................................- 4 -
2 / ABOUT THIS DEHUMIDIFIER...............................................................................................................................- 5 -
2.1 INTENDED USE.......................................................................................................................................................................................- 5 -
2.2 THE PRINCIPLE OF OPERATION ......................................................................................................................................................- 6 -
2.3 MAIN COMPONENTS ............................................................................................................................................................................- 7 -
3 / HANDLING AND STORAGE..................................................................................................................................- 8 -
4 / INSTALLATION AND COMMISSIONING...........................................................................................................- 9 -
4.1 HOW TO INSTALL THIS DEHUMIDIFIER.........................................................................................................................................- 9 -
4.2 HOW TO COMMISSION THIS DEHUMIDIFIER............................................................................................................................. - 11 -
5 / OPERATION............................................................................................................................................................. - 13 -
5.1 CONTROL PANEL AND ELECTRICAL INTERFACES................................................................................................................... - 13 -
5.2 HOW TO OPERATE THIS DEHUMIDIFIER..................................................................................................................................... - 13 -
6 / SERVICE AND MAINTENANCE.........................................................................................................................- 14 -
6.1 HOW TO SERVICE THIS DEHUMIDIFIER ...................................................................................................................................... - 14 -
6.2 TROUBLESHOOTING ...........................................................................................................................................................................- 17 -
APPENDIX 1 –TECHNICAL DETAILS ...............................................................................................................................
APPENDIX 2 –OPTIONAL ACCESSORY.........................................................................................................................
ELECTRICAL DIAGRAM ........................................................................................................................................................

CR240 USER MANUAL
3/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
IMPORTANT INFORMATION
Contact information
Cotes A/S
Mariane Thomsens Gade 2f, 11.
8000 Aarhus C, Denmark
+45 5819 6322
WWW.COTES.COM
Warranty conditions
The Cotes factory warranty is only valid if a
documented programme of service and preventive
maintenance has been carried out.
Maintenance must be carried out according to the
instructions in the SERVICE AND MAINTENANCE
section. Documentation for this must be in the form
of a written log/journal, with attested entries.
All spare parts must have been purchased from Cotes
or an authorized Cotes Partner.
Copyright
All copyright to this publication belongs to Cotes A/S.
All rights reserved. You are not allowed to photocopy,
reproduce, adapt, modify, translate, display or
transfer any part of this publication to any other
media, without explicit prior written permission from
Cotes A/S.
Compliance with directives and standards
−Machinery Directive 2006/42/EC
−Eco-design 327/2011 directive 2009/125/EF as
regards the eco-design fans driven by motors
with input power between and 125W to 500kW
−EMC Directive 2014/30/EU
−RoHS 2011/65/EC
−EN60204
−EN60335
Technical information
+45 5819 6366
tech-support@cotes.com
Service and maintenance support
+45 5819 6366
tech-support@cotes.com
Terms
The information contained in this publication and
the products and equipment described herein are
subject to change at any time without prior notice.
Cotes A/S has no obligation to inform buyers of the
products and equipment of such subsequent
changes.
This publication may contain misprints. Cotes A/S is
not liable for errors or omissions in this publication
or for incidental or consequential damages in
connection with the furnishing of or the use of this
publication.
Cotes A/S is not liable for any loss or damages,
including consequential damages caused by
disregard of any advice or warnings in relation to
safety in this publication.
This publication cannot be deemed to contain any
express or implied warranties of any kind concerning
the construction or the suitability of the products
described or the fitness of the products for any
particular purpose.
This publication is subject to the provisions and
requirements laid down in Danish law.

CR240 USER MANUAL
4/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
Safety warnings
This appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been given
supervision or instruction concerning use of the appliance in a safe way and understand the hazards
involved.
Children shall not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for
commercial use by lay persons
1 / ABOUT THIS HANDBOOK
1.1 GENERAL BACKGROUND
This is the installation and service handbook for your Cotes dehumidifier.
You should read the whole handbook before installing and/or starting the dehumidifier unit for the first time.
It is important that you and your colleagues are familiar with the correct operating procedures and all
precautionary safety measures, in order to avoid any damage to the surroundings, materials or installations, as
well as to prevent any personal injury.
This handbook is mainly intended for use by technicians who install and operate this Cotes dehumidifier unit,
who carry out preventive maintenance and who replace defective parts.
Anyone using Cotes dehumidifier units, or whose responsibilities include supervising their operation, will also
benefit from reading this handbook and from consulting it as a practical help should the need arise.
1.2 SYMBOLS USED IN THIS HANDBOOK
This tells you to perform a particular action
Important to note because items in the dehumidifier
can cause injury or affect people’s health
You need to pay special attention to this
NOTE
It is each operator’s responsibility to read and understand this manual and
other information and to employ the correct operating and maintenance
procedures.

CR240 USER MANUAL
5/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
2 / ABOUT THIS DEHUMIDIFIER
2.1 INTENDED USE
Intended use of dehumidifier
The dehumidifier is designed for dehumidifying/conditioning atmospheric air only.
The air is filtered with a G4 filter.
The dehumidifier must be placed horizontally on the floor or on a table, and it should rest on the four rubber
supports.
The unit is intended for use in residential, commercial and industrial environments.
Operating conditions
NOTE
The operating conditions of the dehumidifier must be respected.
For process air supplied to the dehumidifier the following limit values must be respected:
Max. humidity ............................... 100% RH
Min./Max. temperature ............. -20°C/40°C
Max./min. pressure ..................... ambient +/- 300 Pa
Foreseeable misuse
Unless specifically stated in the user manual or in a separate agreement with Cotes or a Cotes Partner,
this dehumidifier must not be used for the following purposes:
Conditioning of gases other than atmospheric air at ambient pressure.
Conditioning air contaminated with any chemical or other aggressive/corrosive elements including salt
(sodium chloride).
Conditioning explosive or flammable air –including using the dehumidifier in ATEX-classified zones.

CR240 USER MANUAL
6/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
2.2 THE PRINCIPLE OF OPERATION
The effect of Cotes adsorption dehumidifiers basically stems from the action of two flows of air.
In this case the air is controlled by one fan, and the air is departed later in the drying process.
The drying process
The incoming moisture-laden flow of air enters one side of the cabinet and gets filtered by an air filter. The air
then passes through a slowly turning rotor whose inner surfaces are coated with desiccant silica crystals that
attract the water molecules passing through. When the moist air passes through the rotor, water molecules are
adsorbed and lodge in the pores on the surface of the silica gel. This means the air leaves the rotor containing
less moisture (humidity) than when it entered. And because the adsorption process releases energy to the air,
the temperature increases during the process. The air is then departed in to two separate airflows –Process air
and Regeneration air. Process air is the dry air.
The regeneration process
The regeneration air is then heated by heating element to reduce its relative humidity. On its way through the
rotor, this heat evaporates the moisture previously adsorbed by the silica crystals in the rotor. The resulting
water vapour now leaves the dehumidifier in the outgoing regeneration air.
The two air flows are fixed, and the rotor turns - this gives an automatic process of simultaneous water
adsorption and water extraction
Dry Air Outlet
Process and Regeneration
Air Inlet
Regeneration Air Outlet

CR240 USER MANUAL
7/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
2.3 MAIN COMPONENTS
1. Cable strap
2. Dry air outlet –125 mm female
3. Air fan
4. Drive belt
5. Gearmotor for rotor
6. Filter (Standard - G4)
7. Regeneration Air Outlet –80 mm female
8. Flexible hose
9. Desiccant rotor
10. Heater
11. Filter lid
See section 6 / SERVICE AND MAINTENANCE for information on how to access main components.
Access for service/repair
To access components inside the machine, remove the top cover.
The top cover is fastened with 4 screws on the top of the device.
1
4
5
7
10
6
3
2
9
8
11

CR240 USER MANUAL
8/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
3 / HANDLING AND STORAGE
Incoming goods inspection
Cotes recommends that customers:
•Inspect incoming goods for visible damage
•Photograph goods with obvious or suspected damage
•Verify that the incoming goods comply with either the delivery note or sales order
•If the delivery is found to be non-compliant, a written objection must be made immediately to the
delivery driver and the delivery company
•The delivery driver must countersign any objection letter
•Provide a copy of any objection letters to the delivery driver and keep the original.
If you do not inspect the delivery, but accept and sign the transporters receipt, then you will be liable to any
product damage or missing products.
If you do not sign the transporters receipt, but still are accepting the transporters unloading of his deliveries,
you are also liable to any product damage or missing products.
Handling
When ordering multiple dehumidifiers, they can be delivered on a pallet.
If the dehumidifiers have been delivered on a transport pallet, they can be moved using a forklift
Cotes dehumidifiers are built to be very durable so there is no need for any special handling other than normal
reasonable care and attention.
Do not stand on it or use it as a stool/staircase!
Storage conditions
NOTE
The storage conditions of the dehumidifier must be respected.
For storing the dehumidifier, the following conditions must be respected:
Relative humidity 0–90%
Temperature -25°C to 55°C
It is only possible to deviate from these ranges if such deviations were specifically mentioned when the order
was placed, and special considerations have been incorporated into the unit in order to deal with this.
Removing the packaging
The packaging must be disposed of in accordance with applicable regulations.
Please dispose of this packaging responsibly and recycle it if possible.

CR240 USER MANUAL
9/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
4 / INSTALLATION AND COMMISSIONING
4.1 HOW TO INSTALL THIS DEHUMIDIFIER
Safety precautions
NOTE
Electrical work should only be carried out by an authorised electrician,
and in accordance with national wiring regulations.
Electrical fuse size in the connected electrical installation:
Min. 10 A / Max. 16 A.
Any duct connections to and from the dehumidifier should only be carried out by authorised ventilation installer.
Also only use appropriate power cable and accessories made for this dehumidifier.
Where to mount this dehumidifier
NOTE
The dehumidifier must be placed indoors in stationary installations
and protected against rain and water on the cabinet.
The dehumidifier should be installed indoors, placed on a horizontal based surface.
It should be placed on the four rubber supports underneath the cabinet.
Also the dehumidifier must not be mechanically affected by other adjacent structures.
Minimum distance to other structures: 10 cm
Installation above sea level: Max. 3000 meter.
Where not to mount it
Unless it has been arranged with Cotes and special considerations have been made, the unit should not be
placed outdoors.
The unit should not be placed inside an office or in other locations where the sound pressure level must be kept
to a minimum.

CR240 USER MANUAL
10/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
Connections needed –electrical
NOTE
Make sure power is switched off before installing and servicing.
First, make sure that the selector switch is in position 0.
Now the power cable can be connected to the mains.
Connections needed –ductwork
NOTE
To ensure low pressure drop and low sound pressure levels,
please request assistance from a company that specializes in ventilation
systems.
NOTE
The regeneration air outlet duct should be directed at least a few degrees
downwards to allow for drainage of the condensed water.
If this is not possible, drill a ø6mm hole in the lowest part of the duct.
The main air to be dried is normally drawn from the room and through the main air filter. As standard, the
dehumidifier is delivered with a frame covering the filter.
If the installation is for normal room dehumidification at 50 - 100% RH, it is acceptable for the dehumidifier is
free blowing (no regulation). If lower dew points are desired, the dry air flow must be adjusted with a damper.
The regeneration air inlet should be equipped with a Ø80mm duct and a built-in filter. The regeneration air
outlet should be equipped with Ø80mm duct directed at least a few degrees downwards to allow for drainage
of the condensed water. If this is not possible, a Ø6mm hole should be drilled in the lowest part of the duct.
In order to adjust the regeneration air flow a damper must be installed on the regeneration air outlet.
If not, the regeneration air flow will –in most cases –be too high, making it impossible to reach the desired
temperature for the regeneration air and thus making the unit less efficient.
In general, ducts of the same size or larger as those placed on the dehumidifier should be used.

CR240 USER MANUAL
11/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
4.2 HOW TO COMMISSION THIS DEHUMIDIFIER
NOTE
Only trained/authorised electricians are allowed to carry out any work
required in the electrical parts of this Cotes dehumidifier.
When the cover of the electrical box is open, the power supply must be
switched off at the mains switch.
Commissioning procedure
1. Check the electrical installation before starting the dehumidifier, switch on the mains switch.
•230V –Check the voltage between the terminals L1, N
•Is the ground cable connected, and of the correct specifications?
•Is any hygrostat (if fitted) correctly connected?
2. Check the connected duct system
•Is the recommended damper installed in the regeneration air outlet duct?
•Is the optional damper installed in the process air outlet duct?
•Do the regeneration air outlet ducts drain away from the dehumidifier, to make sure that any
condensed water flows away?
•If the regeneration air outlet does not drain away from the dehumidifier, check whether there
is a 6 mm-diameter hole drilled in the lowest part of the duct, so that any accumulated water
can drain away.
3. Suggested damper positions/air flow settings at commissioning
•Dampers/settings should be set in the following positions.
oDamper at process air outlet: Fully open.
oDamper at regeneration air outlet: Fully open.
4. Once the dehumidifier is operating, adjust the air flows.
How to adjust air flows
NOTE
Check the regeneration air duct for free blowing
and draining of the condensed water.
The dry air flow can be adjusted when a damper Ø125 is installed in the dry air outlet duct.
If only a short duct is installed, the opening should be reduced on the damper to obtain the nominal air flow.
The dry air flow should be adjusted to the nominal value for obtaining data from the capacity diagram.
The regeneration air flow must be adjusted with a damper installed in the regeneration air outlet.
Start-up with the damper in the open position and close it until the Ammeter indicates 4,5A (at 230V).

CR240 USER MANUAL
12/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
Check the value again after approximately 15 minutes of operation, one more adjustment might be necessary.
Regeneration air flow must always be controlled. Check the regeneration air duct for allowing free blowing of
the regeneration air. Check that the regeneration air duct is installed draining from the dehumidifier.
Check the air flows using a suitable instrument (pitot pipe/thermo-anemometer or similar) in the duct.
Use a standardised tool for measuring the velocity according to specifications.
With the electrical settings and air flows are adjusted, the dehumidifier will then operate automatically by
means of the internal control - and safety functions –controlled by an external hygrostat.
Once the commissioning procedure has been completed and the air flows have been adjusted, the dehumidifier
will operate automatically thanks to the internal control, including the safety function, controlled by an external
hygrostat.
Regulations by hygrostat
The dehumidifier is prepared for external regulation by a hygrostat. To be connected the hygrostat connector,
using the corresponding male socket, part no 112002 (option). Hygrostat ex Cotes DR10.
Electric connection
The dehumidifier CR240 is connected 230V, 1PH+N+PE. The dehumidifier is supplied with build in socket for
different cable length and plug for the power supply. This cable is connected to the left socket (Power) on the
control panel. Connection of hygrostat, see “Regulations by hygrostat”, above, on this page.
Power consumption & airflows
NOTE
Do not touch the electric heater when switched on, as it is an uninsulated
live wire.
The energy consumption of the PTC-heater is depending on the air flow passing through. At the nominal
regeneration air flow of 40 m3/h the energy consumption of the heater is 966W, which is equivalent to
indication of 4,5A on the Ammeter (whole machine consumption).
Air flow and energy consumption are regulated by a damper installed in the regeneration air duct system.
NOTICE: the energy consumption of the electric heater in the first seconds is up to 8,6A

CR240 USER MANUAL
13/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
5 / OPERATION
5.1 CONTROL PANEL AND ELECTRICAL INTERFACES
1. Power cable connector
2. Hygrostat connector
3. Hour counter
4. Potentiometer (Fan adjustment)
5. Program selector switch
5.2 HOW TO OPERATE THIS DEHUMIDIFIER
The CR240 is designed for maximum dehumidification and the standard setting is that it runs all the time.
This configuration is as simple as possible, therefore there is no dehumidification management installed.
Starting and stopping the dehumidifier
NOTE
Avoid frequent switching on / off the selector switch as this may damage
the contact element or the connected hygrostat.
The dehumidifier is started and stopped using the selector switch. The selector switch has four positions:
•Man = Manual, continuous operation
•0 = Switched off
•Auto = Automatic, operation with connected hygrostat
•Auto + Fan = Automatic, operation with connected hygrostat and fan always on.
Turn the selector swich to the appropriate position to start the dehumidifier in the selected operating mode.
When the selector switch is set to 0, the machine is turned off and all components are without power.
1
2
3
5
4

CR240 USER MANUAL
14/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
6 / SERVICE AND MAINTENANCE
6.1 HOW TO SERVICE THIS DEHUMIDIFIER
Safety instructions
WARNING
Before opening the dehumidifier, make sure that the electric power
is switched off on the main switch (or pull the plug!).
Before opening the dehumidifier, make sure the power is turned off at the mains before you open any cover of
the dehumidifier. Otherwise, there will be a risk of electric shock. Also be aware that the heater element may be
hot if the lid is removed right after the dehumidifier is turned off.
Service and maintenance work on this dehumidifier
Cotes designs its dehumidifier units so that they are as robust as possible, and only need a minimum of service
and maintenance. None of the components require lubrication or adjustment.
The only maintenance work you need to do is listed below.
Service area must be clear at all times. Diagrams and manual must be kept near the machine.
Machine will automatically start-up in case of power loss and recover of electricity.
Service and maintenance in wind turbine installation
Only three things should be done during normal operation and following the normal service intervals
for installation in the nacelle / tower of a wind turbine.:
•Replace air filters.
•Check the rotation of the rotor.
•Check the power consumption of the electric heater (reading 4,5A on the Ammeter, during operation).
If the rotor rotates during operation, and the energy consumption of the complete machine shows app. 4,5A,
you can be almost sure that the dehumidifier is operating at an optimum.
We nevertheless recommend some periodic verification of the entire dehumidifier, to see if all internal functions
are OK and checking of cables to be well fixed, and for damage of the insulation.

CR240 USER MANUAL
15/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
At least once a year or more frequently as needed
Check or replace the air filter.
Once a year
We recommend the following annual checks.
Check that the fans are working (by listening to check if they are turning).
Check the working hours of any component inside. See time-to-change limits table below.
External humidity sensor should be calibrated or replaced (with calibrated instrument).
Check the inside of the cabinet for any signs of dirt or corrosion. Check that the drive belt for the rotor
is still tight and that no parts of it are too worn or close to the breaking point.
Check that the insulation on all electrical cables is intact, with no mechanical or heat damage.
Check that the insulation on the electric heater is intact.
Check that all cables attached to the dehumidifier are properly attached and all components are intact.
Test that all electric components are working as intended –for example by following the instructions in
section 4.2 HOW TO COMMISSION THIS DEHUMIDIFIER.
Table 1 Time-to-change limits
COMPONENT
TIME-TO-CHANGE LIMIT
Air filter
Depends on the working environment.
Specified for 8,700 hours under normal conditions
Air fan
30,000 hours
Gearmotor for rotor
25,000 hours
Electrical heaters
50,000 hours
Drive belt for rotor
25,000 hours
Rotor
50,000 hours

CR240 USER MANUAL
16/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
Air filter replacement
Access to the filter is done by tipping the finger tap (1) to the right and remove the filter lid. Once accessed the
filter (2) can be removed and replaced. The filter can be replaced without turning the dehumidifier off, but it is
easier when turned off. Replacement filter (no. 650009) fits into the shape of the filter lid. When reattaching
the filter lid make sure the lid is proper installed. No unnecessary force should be used, but the lock should be
pressed back in to place to lock the filter lid.
Air fan replacement
To replace the fan, disconnect the fan electrical connectors, and then unscrew the screws securing the fan. The
screws (4 pcs) are located inside the air filter box and can be accessed from the outside by removing the filter
cover. For easier access remove the 2 rubber feet’s that holds the fan section. Then the fan section can be
separated from the bottom shell.
Rotor, drive belt, gearmotor and electrical heater replacement
To replace the rotor, drive belt or gear motor, but also the electrical heaters, you need to:
1. Disconnect the flexible hose from the Rotor section and the Fan section.
2. Disconnect the ground connection, 1x power, 1x Selector, 1x Potentiometer, and 2x fan - connectors
3. Lift up the complete rotor section and place it on a flat horizontal surface.
Now all components are easily accessible for replacement.
Reassembly of the dehumidifier
Reverse the workflow and be observant when refitting the rotor section back in the bottom shell. Take care that
the sheet metal is correct fitted in to the bottom rib, and ribs on the control panel, and grabs the plastic part
on each side. No unnecessary force should be used.
When refitting the lid, take care that the lid does not grab the “Air trap foil” placed on the inside of the bottom
shell.
1
2

CR240 USER MANUAL
17/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
6.2 TROUBLESHOOTING
Before contacting the Cotes Technical Support, please review the list of possible problems below.
The list is helpful in identifying faults that are easy to remedy without the assistance of qualified personnel.
Table 2 Troubleshooting
PROBLEM
POSSIBLE CAUSE
SOLUTION
The dehumidifier
does not start
when connected
to the power
supply.
1. The external fuse has
turned off.
2. The external hygrostat
has switched off. This is
a normal situation when
the desired
relative humidity is
obtained.
3. The internal fuse has
turned off.
1. Check the external fuse.
2. Adjust hygrostat to the lowest value.
The dehumidifier should start operating.
Adjust again to the desired humidity.
3. Replace the internal fuse.
Desired
humidity is not
obtained
The problem may be the
dehumidifier - or other parts
of the entire installation
(airtightness, hygrostat ...).
1. Check that the fans are moving air.
If not, replace the broken fan.
2. Check that the rotor is turning
as intended.
If not, replace the gearmotor.
3. Check that the dry air outlet
is warmer than the inlet.
4. Check that the regeneration air outlet is warmer
than the inlet by approx.
40-60 °C depending on temperature conditions
of inlet.
5. Check that the value on the ammeter
is approx. 4,5A.
If fans and rotor are working, replace the
heating element.

APPENDIX TO CR240 USER MANUAL
1/3
Cotes dehumidifier: 650000
Manual number: 140772 –appendix 1
Revision: B
COTES.COM
APPENDIX 1 –TECHNICAL DETAILS
SERIAL NUMBER/IDENTIFICATION
The nameplate with the serial number of this specific model is located on the control panel of the dehumidifier.
SPECIFICATIONS
Please note that specifications and controls given in this handbook are in some situations approximate.
Table 1 Technical data
SPECIFICATIONS
Dry air, free blowing
m3/hour
300
Dry air, nominal
m3/hour
240
Regeneration air, nominal
m3/hour
40
External pressure, dry air, nominal
Pa
75
External pressure, regeneration air, nominal
Pa
150
Capacity at 20C, 60% RH
Kg/24h
19,2
Power consumption, Nominal
kW
1,04
Power consumption max., Free blowing
kW / (A)
1,3 / (5,7)
Voltage/Phases
V / Ph
220-230 / 1PH+N+PE
Internal thermal fuse
°C
84
External fuse in connected installation
A
Min. 10 / Max. 16
Type of distribution system
TN-S
IP rating (With both outlet ducts connected)
IP33
650000
CR240
YY.XXXXXX
10,0
230 PH+N+P
50
0,97
1,3
Serial number example:
22.12345
12345 = Serial number
22 = Year of production

APPENDIX TO CR240 USER MANUAL
2/3
Cotes dehumidifier: 650000
Manual number: 140772 –appendix 1
Revision: B
COTES.COM
STANDARD SPARE PARTS
Table 2 Standard spare parts
SPARE PART
ARTICLE NUMBER
1
Air fan (Service pack kit)
777434
2
Air filter - Not visible (Service pack kit 10 pcs.)
777417
3
Drive belt for rotor (Just the belt)
132104
4
Rotor (Just the rotor)
124060
5
Gear motor for rotor (Service pack kit)
777471
6
Internal thermal fuse (Just the fuse)
650023
7
Electrical heater (Just the heater)
111457
7
6
5
4
1
3
2

APPENDIX TO CR240 USER MANUAL
3/3
Cotes dehumidifier: 650000
Manual number: 140772 –appendix 1
Revision: B
COTES.COM
MEASUREMENTS
Standard variants
Table 3 Measurements
MEASUREMENTS
Model
CR240
W x D x H cabinet
mm
444 x 382 x 374
W x D x H total
mm
450 x 382 x 374
Process and regeneration air inlet
mm
202x208
Process air outlet (Female)
mm
Ø125
Regeneration air outlet (Female)
mm
Ø80
Weight (without power cable)
kg
10
Sound level (Nominal free blowing / Max. free blowing) @ 1 meter
dB(A)
59 / 67
This manual suits for next models
1
Table of contents
Other Cotes Dehumidifier manuals