CREVIS FnIO G-Series User manual

1FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
Version 1.00
2018 CREVIS Co.,Ltd
GN-9231
User Manual
CC-Link Network Adapter

2FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
DOCUMENTCHANGE SUMMARY
REV
PAGE
REMARKS
DATE
EDITOR
1.0
New Document
2019/1/31
CH Hong

3FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
CONTENTS
1. Important Notes.......................................................................................................................... 5
1.1. Safety Instruction................................................................................................................ 6
1.1.1. Symbols.........................................................................................................................6
1.1.2. Safety Notes..................................................................................................................6
1.1.3. Certification................................................................................................................... 6
2. Specification................................................................................................................................7
2.1. The Interface.........................................................................................................................7
2.1.1. GN-9231........................................................................................................................7
2.2. Specification..........................................................................................................................8
2.2.1. General Specification.................................................................................................... 8
2.2.2. Interface Specification...................................................................................................9
2.3. LED Indicator...................................................................................................................... 10
2.3.1. L RUN LED (L RUN)....................................................................................................10
2.3.2. L ERR LED (L ERR).................................................................................................... 10
2.3.3. RD LED (RD)...............................................................................................................10
2.3.4. SD LED (SD)............................................................................................................... 10
2.3.5. Field Power Status LED.............................................................................................. 11
2.3.6. Expansion Module Status LED (I/O)........................................................................... 11
3. Dimension................................................................................................................................. 12
3.1. GN-9231............................................................................................................................. 12
4. Mechanical Set Up....................................................................................................................13
4.1. Total Expansion...................................................................................................................13
4.2. Plugging and Removal of the Components........................................................................ 13
4.3. Internal FnBus/Field Power Contacts................................................................................. 14
5. CC-Link Electrical Interface...................................................................................................... 15
5.1. FnBus System.....................................................................................................................15
5.2. CC-Link Network Installation.............................................................................................. 17
5.2.1. GN-9231 Cable Specification......................................................................................17
5.2.2. Connector....................................................................................................................18
5.2.3. Minimum radius of bending cable............................................................................... 19
5.2.4. Terminator Resistor..................................................................................................... 19
5.2.5. CC-Link Setting........................................................................................................... 21

4FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
5.2.6. CC-Link Network Setup...............................................................................................22
5.3. Example (Connect with MELSEC)......................................................................................26
5.4. Process Image.................................................................................................................... 30
5.4.1. Remote input area.......................................................................................................30
5.4.2. Remote output area.................................................................................................... 30
5.4.3. RWr/RWwarea............................................................................................................30
5.4.4. System area................................................................................................................ 31
5.4.5. Reaction on network error...........................................................................................31
5.4.6. Service Message.........................................................................................................32
5.4.7. Service Message request............................................................................................32
5.4.8. Service Message response.........................................................................................33
6. Trouble Shooting.......................................................................................................................34
6.1. How to diagnose by LED indicator......................................................................................34
APPENDIX A....................................................................................................................................36
A.1. Product List........................................................................................................................... 36
A.2. Glossary................................................................................................................................ 38

5FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
1. Important Notes
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls describes some
important differences between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for solid state equipment, all
persons responsible for applying this equipment must satisfy themselves that each intended application of
this equipment is acceptable.
In no event will CREVIS be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, CREVIS cannot assume responsibility
or liability for actual use based on the examples and diagrams.
If you don't follow the directions, it could cause a personal injury, damage to the equipment or
explosion
Do not assemble the products and wire with power applied to the system. Else it may cause an electric arc,
which can result into unexpected and potentially dangerous action by field devices. Arching is explosion
risk in hazardous locations. Be sure that the area is non-hazardous or remove system power
appropriately before assembling or wiring the modules.
Do not touch any terminal blocks or IO modules when system is running. Else it may cause the unit to an
electric shock or malfunction.
Keep away from the strange metallic materials not related to the unit and wiring works should be controlled
by the electric expert engineer. Else it may cause the unit to a fire, electric shock or malfunction.
If you disobey the instructions, there may be possibility of personal injury, damage to equipment or
explosion. Please follow below Instructions.
Check the rated voltage and terminal array before wiring. Avoid the circumstances over 50℃of
temperature. Avoid placing it directly in the sunlight.
Avoid the place under circumstances over 85% of humidity.
Do not place Modules near by the inflammable material. Else it may cause a fire.
Do not permit any vibration approaching it directly.
Go through module specification carefully, ensure inputs, output connections are made with the
specifications. Use standard cables for wiring.
Use Product under pollution degree 2 environment.
Warning!
Caution!

6FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
1.1 Safety Instruction
1.1.1 Symbols
Identifies information about practices or circumstances that can cause an explosion
in a hazardous environment, which may lead to personal injury or death property
damage or economic loss.
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal
injury, property damage, or economic loss.
Attentions help you to identity a hazard, avoid a hazard, and recognize the
consequences.
1.1.2 Safety Notes
The modules are equipped with electronic components that may be destroyed by
electrostatic discharge. When handling the modules, ensure that the environment
(persons, workplace and packing) is well grounded. Avoid touching conductive
components, e.g. FnBUS Pin.
1.1.3Certification
c-UL-us UL Listed Industrial Control Equipment, certified for U.S. and Canada
See UL File E235505
CE Certificate
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions

7FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
2. Specification
2.1 The Interface
2.1.1 GN-9231

8FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
2.2 Specification
2.2.1 General Specification
General Specification
System Power
Supply voltage : 24Vdc nominal
Supply voltage range : 15~32Vdc
Protection : Output current limit (Min. 1.5A)
Reverse polarity protection
Power Dissipation
70mA typical @24Vdc
Current for I/O Module
1.5A @5Vdc(When using in 60℃~70℃’ temperature environment,
the power dissipation is limited to 0.8A.)
Isolation
System power to internal logic : Non-isolation
System power I/O driver : Isolation
Field Power
Supply voltage : 24Vdc nominal(Max. 32Vdc)
*Field Power Range is differnt depending on IO Module series.
Refer to IO Module`s Specification.
Max. Current Field Power
Contact
DC 10A Max.
Weight
<165g
Module Size
54mm x 99mm x 70mm
Environment Condition
Refer to Environment Specification
Environmental Specifications
Operating Temperature
60℃~70℃: Power dissipation is limited to 0.8A.
-40℃~60℃: 1.5A full load is allowed.
UL Temperature
-20℃~60℃
Storage Temperature
-40℃~85℃
Relative Humidity
5%~90% non-condensing
Operating Altitude
2000m
Mounting
DIN rail

9FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
2.2.2 Input Specification
Input Specification, GN-9231
Adapter Type
Slave node (CC-Link Version 1)
Max. Expantsion Module
63slots
I/O Data size
System area : 16 points
RX/RY : 112 points(4station occupied)
RWr/RWw : 16 points(4station occupied)
Max. Nodes number
42 Node/Max
Baud Rate
156/625/2500/5000/10000Kbps
Interface Connector
5 Pin open connector
Other Serial Port
RS232 for MODBUS/RTU, Touch Pannel or IOGuide
Serial Configuration (RS232)
Node : 1 (Fixed)
Baud Rate : 115200 (Fixed)
Data bit : 8 (Fixed)
Parity bit : No parity (Fixed)
Stop bit : 1 (Fixed)
Indicator
6 LEDs
1 Green/Red, Module Status (MOD)
1 Green, Current Running Status (NET)
1 Green, Error Status (ERROR)
1 Green/Red Expansion I/O Module Statsus (IOS)
1 Green, Field Power Status
1 Green, System Power Status
Module Location
Starter module left side of G-bus system
Field Power Detection
About 14Vdc
Station class
Remote Device station

10 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
2.3 LED Indicator
2.3.1 MOD (Module Status LED)
Status
LED is :
To indicate :
Not Powered
OFF
Not power is supplied to the unit.
Normal, Operational
Green
The unit is operating in normal condition.
Devicce in Standby
RED
The EEPROM parameter is not initialalized yet.
Serial Number is zero value (0x00000000)
2.3.2 RUN (Network State LED)
Status
LED is :
To indicate :
Init / No Communication
Red
No Communication / Communication Disconnection
Communicaion
Green
Normal Communication
Communication Error
Off
Communication Error / Token passing
2.3.3 ERROR (Error State LED)
2.3.4 IOS LED (G-Bus Status LED)
Status
LED is :
To indicate :
No Error
Off
Invalid Configuration
Flashing Red
TBD
Status
LED is :
To indicate :
Not Powered
No Expansion Module
OFF
Device has no expansion module or may not be powered.
No Expansion Module
Flashing Red
Adapter has no expansion module
Internal Bus Connection,
Run Exchanging I/O
Green
Exchanging I/O data.
Expansion Configuration
Failed
Red
One or more expansion module occurred in fault state.
- Detected invalid expansion module ID.
- Too many expansion module
- Initialization failure
- Overflowed Input/Output Size
- Communication failure.
- Changed expansion module configuration.
- Mismatch vendor code between adapter and expansion
module.

11 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
2.3.5 Field Power LED (Field Power, LED)
2.3.6 Expansion Module Status LED (I/O)
Status
LED is :
To indicate :
Not Supplied Field
Power
Off
Not supplied 24Vdc field power
Supplied Field Power
Green
Supplied 24Vdc field power
LED ON
Constantly ON
LED OFF
Constantly OFF.
LED flickering
Equal ON and OFF times with a frequency of approximately 10 Hz: ON for
approximately 50ms and OFF for approximately 50ms.
LED blinking
Equal ON and OFF times with a frequency of approximately 2, 5Hz: ON for
approximately 200ms followed by OFF for approximately 200ms.
LED single flash
One short flash (approximately 200ms) followed by a long OFF phase
(approximately 1000ms)
LED double flash
A sequence of two short flashes (approximately 200ms), separated by an OFF
phase (approximately 200ms).
The sequence is finished by a long OFF phase (approximately 1000ms)
LED triple flash
A sequence of three short flashes (approximately 200ms), separated by an OFF
phase (approximately 200ms).
The sequence is finished by a long OFF phase (approximately 1000ms)

12 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
3. Dimension
3.1 GN-9231

13 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
4. Mechanical Set Up
4.1 Total Expansion
The number of the module assembly that can be connected is 32. So the maximum length is 426mm
Exception.
ST-2748 is excepted to calculate maximum length because that is double width module.
4.2 Plugging and Removal of the Components.
Before work is done on the components, the voltage supply must be turned off.
As above figure in order to safeguard the FnIO module from jamming, it should be fixed onto the DIN rail
with locking level. To do so, fold on the upper of the locking lever.
To pull out the FnIO module, unfold the locking lever as below figure.

14 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
4.3 Internal FnBus/Field Power Contacts
Communication between the NA series and the expansion module as well as system / field power
supply of the bus modules is carried out via the internal bus. It is comprised of 6 data pin and 2 field
power pin.
Do not touch data and field power pins in order to avoid soiling and damage by ESD
noise.

15 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
5. CC-Link Electrical Interface
5.1 G-Bus System
• NetworkAdapter Module
The Network Adapter Module forms the link between the field bus and the field devices with the
Expansion Modules.
The connection to different field bus systems can be established by each of the corresponding
Network Adapter Module, e.g. for SyncNet, PROFIBUS, CANopen, DeviceNet, Ethernet/IP, CC-Link,
MODBUS/Serial, MODBUS/TCP etc.

16 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
• Expansion Module
The Expansion Modules are supported a variety of input and output field devices.
There are digital and analog input/output modules and special function modules.
• Two types of G-Bus Message
- Service Messaging
- I/O Messaging
•G-Bus Pin Description
No.
Name
Description
1
Vcc
System supply voltage (5V dc).
2
GND
System Ground.
3
Token Output
Token output port of Processor module.
4
Serial Output
Transmitter output port of Processor module.
5
Serial Input
Receiver input port of Processor module.
6
Reserved
Reserved for bypass Token.
7
Field GND
Field Ground.
8
Field Vcc
Field supply voltage (24Vdc).

17 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
5.2 CC-Link Network Installation
5.2.1 GN-9231 Cable Specification
CC-Link dedicated cable shall be used in CC-Link system. Specification of CC-Link dedicated cable is
as follow.
Item
Specifications
Cable Type
Shield twisted cable
Finish outer diameter
8.0mm or less
Drain line
20 lines/0.18 mm or 24 lines/0.18mm
Insert separately or in a bundle between the
ground cable bundle and aluminum tape.
Conductor resistance (20℃)
37.8Ω/km
Insulation resistance
10000MΩㆍkm or more
Withstand voltage
500VDC 1minute
Electrostatic capacity(1kHz)
60nF/km or less
Characteristic impedance
1 MHz
110±15Ω
5 MHz
110±6Ω
Attenuation amount
1 MHz
1.6dB/100mor less
5 MHz
3.5dB/100mor less
The use of an incorrect supply voltage or frequency can cause severe damage to the
component.

18 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
5.2.2 Connector
Recommended specifications of connector relaying between CC-Link dedicated cables are as
followings.
M12(Micro) type(4 cores)
M12 (Micro) Type
Pin Position
Resistance of
conductor
5mΩ or less
Thickness of Gold
plate
0.1 µm or more
Type of water proof
IP67 (JIS C 0920)
Pin Position
1 pin : SLD
2 pin : DB
3 pin : DG
4 pin : DA
Easy connection water proof type (4 cores)
Easy connection water
proof type
Pin Position
Resistance of
conductor
5mΩ or less
Thickness of Gold
plate
0.5 µm or more
Type of water proof
IP67 (JIS C 0920)
4 conductors
1 pin : SLD
2 pin : DB
3 pin : DG
4 pin : DA

19 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
5.2.3 Minimum radius of bending cable
Please keep the minimum radius of bending in using CC-Link dedicated cable.
When it is used with less than min. radius by constraint, it may cause pulling out from connector and
cable, breaking of cable, etc..
Minimum radius of
Bending cable
Connecting
Major diameter of cable × 10 or more
Stable
Major diameter of cable × 4 or more
connecting : Minimum radius of bendingcable permitted in only connecting
stable : Minimum radius of bending cable at stable permits the characteristic for long period.
5.2.4 Terminator Resistor
Specification of terminator Resistors are as follows Resistance Spec.:
- CC-Link dedicated cable 110Ω±5% 1/2W
- CC-Link dedicate high performance cable 130Ω±5% 1/2W

20 FnIO CC-Link Network Adapter GN-9231 FnIO G-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4506 URL : www.crevis.co.kr
Easy connection water proof type (4 cores)
- When repeater is not used
Please connect terminal resister, 110Ω±5% 1/2W between DA and DB on each edge of trunk line.
(Do not use CC-Link dedicated high performance cable)
- When repeater is used
Please use Terminal resistor included in Repeater unit.