CyClone SV130 User manual

MINI SINGLE-ROOM REVERSIBLE
ENERGY REGENERATION VENTILATOR
Installation and Operation Instructions
Please read all instructions before installing and operating.
All wiring and installation must be in accordance with CEC, NEC and local electrical codes.
READ AND SAVE THESE INSTRUCTIONS
SV130
3166456

2SV130 SV150 Installation - English

4SV130 SV150 Installation - English
IMPORTANT SAFETY INSTRUCTIONS
• Read the user’s manual carefully prior to installing and operating the unit.
• Ful l the user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical and technical norms
and standards.
• The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.
• Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.
• After a careful reading of the manual, keep it for the entire service life of the unit.
• While transferring the unit control the user’s manual must be turned over to the receiving operator
UNIT MOUNTING SAFETY PRECAUTIONS
• Disconnect the unit from power mains
prior to any installation operations. • The unit must be grounded!
• Do not lay the power cable of the unit in
close proximity to heating equipment. • While installing the unit follow the
safety regulations specic to the use
of electric tools.
• Do not change the power cable length
at your own discretion.
• Do not bend the power cable. Avoid
damaging the power cable.
• Do not put any foreign objects on the
power cable.
• Unpack the unit with care.
• Do not use damaged equipment or
cables when connecting the unit to
power mains.
• Do not operate the unit outside the
temperature range stated in the user’s
manual. Do not operate the unit in
aggressive or explosive environments.
• Do not touch the unit controls with wet
hands.
• Do not carry out the installation and
maintenance operations with wet
hands.
• Do not wash the unit with water.
Protect the electric parts of the unit
against ingress of water.
WARNING: DISCONNECT THE VENTILATOR FROM POWER MAINS PRIOR TO ANY ELECTRIC INSTALLATION
OPERATIONS. CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A
WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL READING OF THE PRESENT USER’S MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL. ANY TAMPERING
WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
ALL THE VENTILATORS CONNECTED IN SERIES MUST BE GROUNDED!
WARNING
Symbol legend used in the manual:
WARNING!
DO NOT!
is user’s manual consisting of the technical details, operating instructions and technical specication covers the installation and
mounting of the single-room energy regeneration reversible ventilator SV130 (hereinaer «the ventilator» or «the unit» as mentioned in
the «Safety Requirements» and «Manufacturer’s Warranty» sections as well as in warnings and information blocks).

5SV130 SV150 Installation - English
PURPOSE
The ventilator is designed to ensure continuous mechanical air exchange in ats, cottages, hotels, cafes and other domestic and public premises. The
ventilator is equipped with a ceramic regenerator that enables supply of fresh ltered air heated by means of extract air heat energy regeneration.
The ventilator is designed for through-the-wall mounting. The telescopic ventilator design enables its installation in the walls with various thickness, see
the table below:
Wall thickness Ventilator model
240 mm - 425 mm (9 7/16’’ - 16 3/4”) SV130
120 mm - 300 mm (4 3/4’’ - 11 13/16’’) SV150
The unit is rated for continuous operation.
Transported air must not contain any ammable or explosive mixtures, evaporation of chemicals, sticky substances, brous materials,
coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic
germs).
DELIVERY SET
a) Ventilator 1 item
b) Fastening set 1 item
c) Remote control 1 item
d) User’s manual 1 item
e) Packing box 1 item
ABOUT THE PRODUCT
Dual Air is the single room energy ventilation system designed to continuously remove stale air from any space while simultaneously bringing in fresh air
from outside. This is especially helpful for the great white north where our windows are closed for most of the year for either heating or air conditioning
purposes. It’s simply unrealistic to have fresh air in your homes most of the time. This is a quick and easy x to freshen up your home and target specic
rooms that need the fresh air more so than others. A great reliable and long term solution for increasing the air quality in your home. Dual Air is very easy
to install. You can transform your space’s feel and comfort with our simple installation and operating instructions. Tailor-made for open concept houses,
condos or mid-size rooms with incredibly quiet operation. Once you set it you’ll forget it’s there but will always appreciate the wonderful fresh air. Cyclone,
Breath better, live better.
• Do not allow children to operate the
unit. • Disconnect the unit from power mains
prior to any technical maintenance.
• Do not store any explosive or highly
ammable substances in close
proximity to the unit.
• If the unit generates unusual sounds,
odour or emits smoke disconnect it
from power supply and contact the
Seller.
• Do not open the unit during operation. • Do not direct the air ow produced by
the unit towards open ame or ignition
sources.
• Do not block the air duct when the unit
is switched on. • In case of continuous operation of the
unit periodically check the security of
mounting.
• Do not sit on the unit and avoid placing
foreign objects on it. • Use the unit only for its intended
purpose

6SV130 SV150 Installation - English
TECHNICAL DATA
The ventilator is rated for indoor application with the ambient temperature ranging from -20°C (-4 °F) up to +50°C (+122 °F) and relative humidity up to 80%.
Ingress Protection (IP) rating from solid objects and liquids IP 24.
The ventilator design is regularly improved, so some models may slightly differ from those ones described in this manual.
VENTILATOR OVERALL DIMENSIONS [MM] (INCHES)
TwinFresh Comfo RA-50-2
TwinFresh Comfo RA1-50-2
TwinFresh Comfo RA-50
TwinFresh Comfo RA1-50
213
213 240
240
120-300 100
(4")
125
(5")
100
(4")
125
(5")
144
ø 157 ø 153
(ø 6")
ø 157 ø 153
(ø 6")
300
310
260
(10 ¼")
300
280
11"
240-425
133
(5 ¼")
VENTILATOR TECHNICAL DATA
Speed I II III
Unit voltage [V /50-60 Hz] 1~100-230
Air capacity [m3/h] (CFM) 14 (8) 28 (16) 54 (32)
Power [W] 3,80 3,96 5,61
Current [A] 0,024 0,026 0,039
RPM 610 800 1450
Noise level, 1 m [dB(A)] (Sones) 22 (0,4) 29 (0,7) 32 (1,0)
Noise level, 3 m [dB(A)] (Sones) 13 (0,2) 20 (0,4) 23 (0,5)
Outdoor noise attenuation [dB(A)]
(Sones) 18 (0,4)
Heat recovery ef ciency up to 90%

7SV130 SV150 Installation - English
UNIT DESIGN AND OPERATING LOGIC
The ventilator consists of a telescopic air duct with adjustable length (inner part and outer part), a ventilation unit and an outer ventilation hood. Two lters
and a ceramic regenerator are located inside the inner duct of the telescope.
The air lters are designed to purify supply air and prevent foreign object ingress into the regenerator and the fan.
The ceramic regenerator utilizes extract air heat energy to warm up supply air ow. The cord laid inside the regenerator is designed to pull the regenerator
from the ventilator. The regenerator is heat insulated with a specially designed insulating material. The ventilation unit must be installed on inner side of
the wall.
The ventilation unit is equipped with automatic shutters that shut the air duct off during the ventilator standby and prevent air back draft.
The ventilation hood must be installed on outer side of the wall. It is used for directed air discharge and prevention of ingress of water and other objects
to the ventilator.
Mounting plate
A mounting plate for
installation of the
ventilation
unit on the wall and
connecting it to power
mains.
Air ow rectier
Eliminates air turbulence
inside the ventilator.
Filter
Cleans supply air ow
and prevents ingress of
dust and foreign objects
into the ventilator. Filters
also prevent regenerator
soiling.
Ventilation unit
Generates air ow by means of the fan.
The ventilation unit is covered with a
ventilation grille on inner side of the wall
to prevent ingress of foreign objects into
the fan.
The ventilation unit is equipped with
automatic shutters to prevent back draft
of air. The air shutters open during
operation of the ventilator and close
when the unit is turned off.
Inner air duct
Inner part of the
telescopic air duct.
Ceramic regenerator
The ceramic regenerator
utilises extract air heat
energy to warm up supply
air ow.
Outer air duct
Outer part of the
telescopic air duct.
Outer ventilation hood
Prevents direct ingress
of water and
foreign objects into the
ventilator.
AUTOMATIC SHUTTERS OPERATION
Ventilator is off (the shutters are closed) Ventilator is on (the shutters are opened)

8SV130 SV150 Installation - English
VENTILATOR OPERATION MODES
The ventilator has four ventilation modes:
• Natural Air Supply - the automatic shutters are opened, the fan does not run.
• Air Supply - the ventilator supplies fresh air to the premise.
• Ventilation - the ventilator operates in permanent supply or extract mode at set speed depending on CN7 jumper position.
• Regeneration - the ventilator operates in reversible mode with heat and humidity regeneration.
In Regeneration mode the ventilator operates in two cycles, 70 seconds each.
Cycle I. Warm stale air is extracted from the room. As it ows through the ceramic regenerator, it heats and moisturizes the regenerator,
transferring up to 91 % heat energy. In 70 seconds as the ceramic regenerator gets warmed the ventilator switches to Air Supply mode.
Cycle II. Fresh intake air from outside ows through the ceramic regenerator, absorbs accumulated moisture and is heated to the room
temperature. In 70 seconds as the ceramic regenerator gets cooled down, the ventilator switches to air extract mode and the cycle is
renewed.
A
I
R
E
X
T
R
A
C
T
I
O
N
A
I
R
S
U
P
P
L
Y
CYCLE I
CYCLE II
7
0
s
e
c
7
0
s
e
c
(+14 ˚F)
(+14 ˚F)
(+68 ˚F)
(+68 ˚F)
(+63 ˚F)
(+19.4 ˚F)
(+19.4 ˚F)
(+63 ˚F)
MOUNTING AND SETUP
READ THE USER’S MANUAL PRIOR TO MOUNTING THE VENTILATOR.
WARNING
WARNING
THEVENTILATORMUSTNOTBEINSTALLEDINSITESWHERETHEAIRDUCTMAYBECLOGGED
BY THE BLINDS, CURTAINS, DRAPES, ETC. TO PREVENT THE ROOM DUST DEPOSITION AND
ACCUMULATION. BESIDES, CURTAINS CAN IMPEDE THE NORMAL CIRCULATION OF AIR IN
THE ROOM, MAKING THE OPERATION OF THE VENTILATOR INEFFECTIVE.

9SV130 SV150 Installation - English
VENTILATOR MOUNTING
1. Prepare a round through hole in the outer wall. The hole size is shown in the gure below. While preparing the holes consider the method of laying the
power cable.
Ø170
min 500
min 500
min 500
A
Ø170
A-AA
Inner side of the wall
Outer side of the wall
While preparing the hole provide a recess for the cable layout to enable connection of several ventilators in series.
2. Install the telescopic air duct inside the wall, centre the air duct using the mounting plate and seal it with mounting foam.
35 A
Inner side of
the wall
Outer side of
the wall
Seal the centred
air duct using the
mounting foam
3. Install the mounting plate using the dowels (included in the delivery set).
Lean the mounting box
against the wall and mark
four holes for dowels
Lean the mounting box
with screws
Drill the holes and insert the
dowels

10 SV130 SV150 Installation - English
OUTER HOOD MOUNTING
4. Consecutively install the lter, the ceramic regenerator, the second lter and the distance ring. Then attach the ventilation unit to the mounting plate.
Filter
Distance ring
Ceramic regenerator Ventilation unit
Filter
1. Mark the fastening holes for the outer ventilation hood and drill holes for the dowels. For convenience of marking use the back part of the ventilation
hood.
200 mm
(7 7/8")
Ø6 mm (1/4")
4 holes
220 mm
(8 11/16")
2. Insert the dowels from the delivery set into the holes.
3. Disassemble the outer ventilation hood to enable access to the fastening holes.
Take off the front part of the outer ventilation hood. Remove 5 screws and take off the front part of the ventilation hood.
1 2

11SV130 SV150 Installation - English
4. Fix the back part of the ventilation hood on the wall with the screws from the delivery set.
5. Install the front part of the ventilation hood.

12 SV130 SV150 Installation - English
CONNECTION TO POWER MAINS
DISCONNECT THE VENTILATOR FROM POWER MAINS PRIOR TO ANY ELECTRIC INSTALLATION OPERATIONS.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A WORK PERMIT
FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL READING OF THE PRESENT USER’S MANUAL. THE RATED
ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL. ANY TAMPERING WITH THE
INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
WARNING
LN
In
LN
Out
In Out
1~100-230 V / 50-60 Hz
Ground
terminals
The ventilator is rated for connection to a single-phase AC
1~100-230 V / 50-60 Hz. For this purpose the power cable with a
plug is connected by the manufacturer. Connect the ventilator to
power mains through the external automatic circuit breaker with a
magnetic trip integrated into the xed wiring system.
i
k
d
a
H
H
k
i
k
d
a
H
H
k
Ventilator
controller
TB2
CN7
N
O
P
Q
R
S
VENTILATION MODE SETTING
The jumper between the contacts 1 and 2 or 2 and 3 of CN7 socket connector determines air ow direction
in Ventilation mode. The circuit board of the controller is located inside the ventilation unit.
• If the jumper connects the contacts 1 and 2, air is extracted from the room in the Ventilation mode
(factory setting).
• If the jumper connects the contacts 2 and 3, air is supplied in the Ventilation mode.
CONNECTION OF SEVERAL VENTILATORS IN SERIES
When the ventilators are connected in series, all the connected ventilators are controlled with the rst ventilator and a remote control. To connect the
ventilators in series refer to the wiring diagram below. Connect the second ventilator with the third ventilator in the same way, etc. Up to 10 ventilators may
be connected in series.
For easy electric installations use a 3G AWG18 (3G 1,0) cable and a 2xAWG23 (2х0,25) cable (not included in the delivery set). The cable must be rated
for operation in an alternating current power supply with the country-specic mains voltage.
Disconnect the power cable while connecting the second, third, etc. ventilator in series.
L N L N

13SV130 SV150 Installation - English
CONNECTION OF SEVERAL VENTILATORS IN SERIES
(BACKSIDE VIEW, THE TERMINAL BLOCK IS SHOWN SCHEMATICALLY)
Input
L
G
-
D
N
Output
L
G
-
D
N
Ventilator no.2
Input
L
G
-
D
N
Output
L
G
-
D
N
Input
L
G
-
D
N
Output
L
G
-
D
N
Ventilator no.1
Control cable
2xAWG23
Control cable to the
next ventilator
Power cable
3G AWG18
(3G 1,0)
Power cable to the
next ventilator 1~100-230 V / 50-60 Hz
CONNECTION OF MORE THAN 10 VENTILATORS IN SERIES
In case of connection of more than 10 ventilators, power is supplied to the 11th ventilator not from the previous ventilator but from power mains (L and N
terminals).
The control signals G and D from the 10th ventilator are transferred through the cable 2xAWG23 (2х0,25).
The ventilators no. 12…20 are connected to the ventilator no. 11 in the same way as the ventilators no. 1…10.
All the connected ventilators are controlled with the ventilator no. 1.
ALL THE VENTILATORS CONNECTED IN SERIES MUST BE GROUNDED!
WARNING
VENTILATOR CONTROL
The ventilator is operated with a remote control or the buttons on the ventilator casing, see the gure below.
The operation buttons on the ventilator casing have limited functionality: Only the second and the third speed can be activated. Three of the four modes of
ventilation may be set. The remote control has wider control capabilities.
Guaranteed range of the remote control is 1m. The receiver is located on the casing of the ventilator in the area of the control buttons, it is necessary to
take into account while using the remote control.
The ventilator stores the current operation mode and in case of power failure returns to this mode when power is restored.
Speed switch
Ventilation mode switch
Third speed
The ventilator operates with maximum air capacity.
The fan is OFF:
The ventilator does not operate. The shutters are closed.
Second speed:
The ventilator operates with 50% air capacity
Ventilation mode:
The ventilator operates at the selected speed either in extract
or supply mode depending on the CN7 jumper position.
Regeneration mode:
In this mode the ventilator switches between supply and
extract modes each 70 seconds with heat regeneration.
Supply mode:
All the ventilators connected in series operate in supply
mode irrespective of the CN7 jumper position.

14 SV130 SV150 Installation - English
REMOTE CONTROL
1- operation of all the ventilators connected in series is determined by the CN7 jumper position.
Speed selection
Natural Air Supply
The shutters are open, the fan does not
run.
Night mode
in the darkness.
Air supply
The ventilator continually supplies fresh
air to the room irrespective of the CN7
jumper position.
Regeneration
The ventilator switches between supply
and extract modes each 70 seconds with
heat regeneration.
The ventilator operates at the selected
speed either in extract or supply mode
depending on the CN7 jumper position.
Humidity Set Point Setting
Set the speed switch to position and the ventilation mode switch to position to enable remote control of the ventilation unit.
1. Turning the ventilator on / off .
ON/OFF
ON/OFF
If the Night mode is activated, the ventilator switches to the rst speed in the darkness when the light is turned off. Activation of the Night
mode is conrmed by a long sound signal. Exiting the Night mode is conrmed by a short sound signal.
3. Speed selection.
- First speed
- Second speed
- Third speed
4. Operation mode.
- Natural Air Supply mode. The room is ventilated in the natural way, the fan is off.
- Air Supply mode. Air is supplied to the room at a set speed. All ventilators connected in series operate in air supply
mode no matter of CN7 jumper position.
- Ventilation mode. Air is extracted (factory setting) or supplied at a selected speed. All the ventilators connected in
series operate depending on position of CN7 jumper.
- Regeneration mode. The ventilator operates 70 seconds in supply mode and then 70 seconds in extract mode with
heat regeneration.
5. Humidity Control mode.
Humidity control is possible only in Regeneration mode by pressing one of the buttons that allow to select the humidity set point. In the
Humidity Control Mode the ventilator measures the humidity of the extract air. If the humidity exceeds the selected set point the ventilator
switches to a higher speed. After reaching the required level of humidity the ventilator switches to a lower speed. Press one of the speed
switches to deactivate the Humidity Control mode.
- Setting humidity set point - 45%
- Setting humidity set point - 55%
- Setting humidity set point - 65%
HUMIDITY CONTROL MAY BE ACTIVATED WITH THE REMOTE CONTROL ONLY!

15SV130 SV150 Installation - English
TECHNICAL MAINTENANCE
DISCONNECT THE VENTILATOR FROM POWER MAINS PRIOR TO ANY MAINTENANCE OPERATIONS WITH THE UNIT.
WARNING
Maintenance of the ventilator means regular cleaning of the ventilator surfaces of dust and cleaning or replacement of the lters
VENTILATOR MAINTENANCE
1. Fan inspection (once per year).
sedalbrellepmiehtnaelCtinunoitalitnevehtevomeR
Take off the ventilation unit and clean the fan blades. To
remove dust use a soft brush, cloth or a vacuum cleaner. Do
not use water, abrasive detergents, solvents, sharp objects.
Clean the impeller blades once a year.
2. Regenerator and lter maintenance (3-4 times per year).
Filter
Distance ring
Ceramic regenerator
Filter
• Remove the air ow rectier.
• Remove the lter upstream of the regenerator.
• Pull the specially designed cord to remove the regenerator from the air duct.
• Be careful while removing the regenerator to avoid its damage.
• Remove the lter downstream of the regenerator.
Clean the lters as they get soiled, but not less than once in three months.
• After 90 days of operation the ventilator generates a sound signal after which
it is necessary to switch off the ventilator and to replace or clean
the lters.
• Wash the lters and let them get dry. Install dry lters in the air duct.
• Vacuum cleaning is allowed.
• The lter rated service life is 3 years.
• For new lters contact the Seller
Some dust may accumulate on the regenerator block even in case of regular
maintenance of the lters.
• Clean the regenerator regularly to ensure its high heat recovery efciency.
• Vacuum clean the regenerator not less than once a year.
To reset the hour meter install the lters and the regenerator into the ventilator and then press and hold the button for 10 sec. until you hear
a long sound signal.

16 SV130 SV150 Installation - English
3. Ventilation hood maintenance (once per year).
The ventilation hood may get clogged with leaves and other objects which may reduce the unit performance.
Check the ventilation hood twice per year and clean it as often as required.
To clean the ventilation hood disassemble it, then clean the ventilation hood and the air duct.
4. Replacement of the remote control battery (if necessary).
Replace the battery of the remote control after prolonged use. If the ventilator
does not respond to the commands from the remote control it is a signal to
replace the battery.
Battery type: CR2025.
To replace the battery of the remote control remove the battery holder with a
battery.
Replace the battery and install the holder with a new battery back to the remote
control.
+
CR2025
3V
+
CR2025
3V
ISSUE CAUSE SOLUTION
When switching on the
ventilator the fan does not
start.
No power supply. Make sure the power supply line is connected correctly,
otherwise troubleshoot the connection error.
The motor is jammed, the impeller
blades are soiled.
Turn the ventilator off. Troubleshoot the motor jam and the
impeller clogging. Clean the blades. Restart the ventilator.
Circuit breaker tripping during
the ventilator startup.
Overcurrent as a result of short circuit in
the electric line. Turn the ventilator off. Contact the Seller.
Low air ow.
Low set fan speed. Set a higher speed.
The lter, the fan or the regenerator is
soiled
Clean or replace the lter, clean the fan and the regenerator.
Refer to Technical maintenance, clause 1,2.
The ventilator generates
sound signals.
The hour meter is activated to inform of
the need to replace the lters. Refer to Technical maintenance, clause 2.
Noise, vibration.
The impeller is soiled. Clean the impeller
The ventilator casing or ventilation hood
screw connections are too loose. Tighten the screws of the ventilator or the outer ventilation hood.
TROUBLESHOOTING

17SV130 SV150 Installation - English
CYCLONE LIMITED WARRANTY
Cyclone Range Hoods Inc. (hereunder called “e Company”) provides a warranty that its products are free from defects in workmanship
and materials for a period of ve (5) years from the date of purchase for the following models: DV160 and SV130, and for a period of
three (3) years for the following models: CG180, CG110. During that time period, e Company will, at the Company’s option, repair
or replace without charge any parts or complete unit found to be defective. Further, the warranty for the motor extends for an additional
eight (8) years, with labor costs extra. is warranty is not transferrable from the original purchaser. e company reserves the right to
use functionally equivalent reconditioned parts or products as warranty replacement or as part of warranty service.
THE COMPANY WILL NOT BE HELD RESPONSIBLE FOR ANY CLAIMS OVER THE ORIGINAL PURCHASE PRICE OF
THE PRODUCTS NOR BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN
CONNECTION WITH PRODUCT USE OR PERFOR¬MANCE.
Some provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may
not apply to you.
e unit removal and reinstallation works are under the customer responsibility.
is warranty does not cover any costs related to the products including but not limited to:
a) Normal maintenance service required for the products; b) lters, roof caps, wall caps and other accessories for ducting; c) natural
wear of the nish of the products or wear caused by improper maintenance, use of corrosive and abrasive cleaning products; d) products
or parts which have been subject to freight damage, misuse, negligence, accident or any other circumstances beyond the control of e
Company.
e warranty will be automatically void if any of the following apply:
• Commercial use of the products or use otherwise inconsistent with its intended purpose;
• e function of part or the complete assembly has been modied or repaired by unauthorized person;
• Faulty installation or installation contrary to recommended installation instructions:
• Ventilation system has not been vented to the outside or ventilation system stuck;
• Less than 5” round or equivalent ductwork has been used anywhere in the venting system;
• e venting duct blocked anywhere in the venting system;
• Wrong electrical wire connection for the fan.
To qualify for warranty service you must: (a) notify us at the address telephone number stated below within 2 days of the discovery of the
defect; (b) provide the model number and serial number; and (c) describe the nature of any defect in the product or part.
At the time of requesting for service, you must present evidence of your proof of purchase and proof of the orig¬inal purchase date. If
we determine that the warranty exclusi ons listed above apply or if you fail to provide the necessary documentation to obtain service,
customer will be responsible for all shipping, travel, labor and other costs related to the service
For warranty services or repair, please contact the dealer from whom you purchased the product or the address shown below.
North America Range Hoods Inc.
1361 Huntingwood Drive, Unit 16
Scarborough, ON M1S 3J1
Tel: 1-888-293-5662 or (416) 293-0933 Fax (416) 293-4793
Email: Info@CycloneRangeHoods.com
Website: www.CycloneRangeHoods.com

VENTILATEUR DE RÉCUPÉRATION D’ÉNERGIE
RÉVERSIBLE POUR PIÈCE UNIQUE PETIT
SV130
Instructions d’Installation et d’Utilisation
Veuillez lire toutes les instructions avant d’installer et d’utiliser la hotte.
Les travaux d’installation et les branchements électriques doivent satisfaire aux exigences du Code
canadien de l’électricité (CCE) et du National Electric Code (NEC) ainsi que des codes municipaux.
LISEZ ET CONSERVEZ CES INSTRUCTIONS.
3166456

2Installation d’une SV130 SV150 - Français

3
Installation d’une SV130 SV150 - Français
TABLE DES MATIÈRES
Instruction de sécurité importantes 4
À propos du produit 5
Objectif 5
Ensemble à la livraison 5
Données techniques 6
Conception et logique de fonctionnement 7
Montage et mise en place 8
Connexion au réseau électrique 12
Contrôle du ventilateur 13
Entretien des composants techniques 15
Dépannage 16
Garantie Limitée de Cyclone 17
Table of contents
Languages:
Other CyClone Fan manuals
Popular Fan manuals by other brands

Kichler Lighting
Kichler Lighting Monarch II Select instruction manual

Savoy House
Savoy House 56-5075-5CN-11 owner's manual

Vortice
Vortice VORT NRG HP Instruction booklet

Perel
Perel CFANAM8 user manual

Sharper Image
Sharper Image EV-FAN44T Instruction manual and warranty information

EUROM
EUROM HVF 16-P user manual