
InsTallaTIon and applICaTIon InformaTIon
www.DaikinApplied.com 11 IOM 1206-7 • TRAILBLAZER™MODEL AGZ CHILLERS
Water Flow Limitations
Constant Evaporator Flow
The evaporator ow rates and pressure drops shown on page
33 for various system designs. The maximum ow rate and
pressure drop are based on a 6°F temperature drop. Flow
rates above the maximum values will result in unacceptable
pressure drops and can cause excessive erosion, potentially
leading to failure.
The minimum ow and pressure drop is based on a full load
evaporator temperature drop of 16°F. Evaporator ow rates
below the minimum values can result in laminar ow causing
low pressure alarms, scaling and poor temperature control.
Variable Evaporator Flow
Reducing evaporator ow in proportion to load can reduce
system power consumption. The rate of ow change should be
a maximum of 10 percent of the ow per minute. For example,
if the maximum design ow is 200 gpm and it will be reduced to
a ow of 140 gpm, the change in ow is 60 gpm. Ten percent of
200 gpm equals 20 gpm change per minute, or a minimum of
three minutes to go from maximum to desired ow. The water
ow through the evaporator must remain between the minimum
and maximum values listed in Table 11 on page 33. If ow
drops below the minimum allowable, large reductions in heat
transfer can occur. If the ow exceeds the maximum rate,
excessive pressure drop and tube erosion can occur. See unit
set point information in See Variable Evaporator Flow on page
61.
System Water Considerations
All chilled water systems need adequate time to recognize
a load change, respond to the change and stabilize to avoid
undesirable short cycling of the compressors or loss of
temperature control. In air conditioning systems, the potential
for short cycling usually exists when the building load falls
below the minimum chiller plant capacity or on close-coupled
systems with very small water volumes. Some of the things
the designer should consider when looking at water volume
are the minimum cooling load, the minimum chiller plant
capacity during the low load period and the desired cycle time
for the compressors. Assuming that there are no sudden load
changes and that the chiller plant has reasonable turndown,
a rule of thumb of “gallons of water volume equal to two to
three times the chilled water gpm ow rate” is often used. A
storage tank may have to be added to the system to reach the
recommended system volume. Refer to AG 31-003 for method
of calculating “Minimum Chilled Water Volume”.
The water quality provided by the owner/occupant/operator/
user to a chiller system should minimize corrosion, scale
buildup, erosion, and biological growth for optimum efciency
of HVAC equipment without creating a hazard to operating
personnel or the environment. Water systems should be
cleaned and ushed prior to the chiller installation. Water
testing and treatment should be veried during initial chiller
installation/commissioning and maintained on a continuous
basis by water treatment professionals (see Limited Product
Warranty on inside of back cover).
CAUTION
The use of detergents, chemicals, and additives in the chiller
system water may adversely affect chiller performance and
potentially lead to repair costs not covered by warranty.
Any decision to use these products is at the discretion of
the owner/occupant/operator/user as such they assume full
liability/responsibility for any damage that may occur due to
their use.
Evaporator Freeze Protection
Evaporator freeze-up can be a concern in the application of
air-cooled water chillers in areas experiencing below freezing
temperatures. To protect against freeze-up, insulation and an
electric heater are furnished with the evaporator. Models 030
through 180 have an external plate heater and thermostat.
Models 190 through 240 have immersion heaters with a
thermostat. These heaters help protect the evaporator down to
-20°F (-29°C) ambient air temperature. The evaporator heater
cable is factory wired to the 115 volt control circuit transformer
in the control box. A 115V power source for the heater and
controls may also be supplied from a separate power feed to
maximize unit protection if desired. Refer to the eld wiring
diagram on page 35 for additional information on supplying a
separate 115V power feed.
Operation of the heaters is automatic through the sensing
thermostat that energizes the evaporator heaters for protection
against freeze-up. Unless the evaporator is drained in the
winter or contains an adequate concentration of anti-freeze, the
disconnect switch to the evaporator heater must not be open.
Although the evaporator is equipped with freeze protection,
it does not protect water piping external to the unit or the
evaporator itself if there is a power failure or heater burnout, or
if the chiller is unable to control the chilled water pumps. Use
one of the following recommendations for additional freeze
protection:
1. If the unit will not be operated during the winter, drain the
evaporator and chilled water piping and ush with glycol.
2. Add a glycol solution to the chilled water system. Burst
protection should be approximately 10°F below minimum
design ambient temperature.
3. Insulate the exposed piping.
4. Add thermostatically controlled heat by wrapping the
lines with heat tape.
5. When glycol is added to the water system for freeze
protection, the refrigerant suction pressure will be lower,
cooling performance less, and water side pressure drop
greater. If the percentage of glycol is high, or if propylene
is used instead of ethylene glycol, the added pressure
drop and loss of performance could be substantial. When
Glycol or Ice are selected as Unit Mode, the MicroTech®
III control will automatically reset the available range
for the Leaving Water Temperature, Freezestat and
Evaporator Pressure settings.