Operation manual
11 EWLP012~065KAW1N
Condenserless water-cooled water chillers
4PW30043-1
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Defining the unit's serial address
To control the unit from a supervisory system, an address card
(optional module) should be installed in the unit. The unit's serial
address required for communication with the supervisory system is
defined by parameter ha. The default, limit and step values for the
serial address are:
■Default value 1
■Limit values 1to 16
■Step value 1
To define the unit's serial address, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code ha using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
TROUBLESHOOTING
This section provides useful information for diagnosing and correct-
ing certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will
save you time and money.
When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no circum-
stances safety devices may be bridged or changed to a value other
than the factory setting. If the cause of the problem cannot be found,
call your local dealer.
Symptom 1:The unit does not start, but the TLED lights up
Symptom 2:The unit does not start, but the TLED is flashing
Symptom 3:The unit does not start and the TLED does not light up
Symptom 4: One of the following safety devices is activated
When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not
correct. Check the controller setpoint.
Power supply failure. Check the voltage on the supply
panel.
Blown fuse or interrupted protection
device. Inspect fuses and protection devices.
Replace by fuses of the same size
and type (refer to chapter "Electrical
specifications" on page 2).
Loose connections. Inspect connections of the field
wiring and the internal wiring of the
unit. Tighten all loose connections.
Shorted or broken wires. Test circuits using a tester and repair
if necessary.
POSSIBLE CAUSES CORRECTIVE ACTION
The flowstart timer is still running. The unit will start after approx. 15
seconds. Make sure that water is
flowing through the evaporator.
The anti-recycling timer is still active. The circuit can only start up after
approximately 4 minutes.
The guard timer is still active. The circuit can only start up after
approximately 1 minute.
POSSIBLE CAUSES CORRECTIVE ACTION
One of the following safety devices is
activated:
•Reverse phase protector
•Overcurrent relay (K*S)
•Discharge thermal protector (Q*D)
•Evaporating temperature thermostat
(S*T)
•Flow switch (S10L)
•High pressure switch (S*HP)
Check on the controller and refer to
symptom "4. One of the following
safety devices is activated". Refer to
the explanation of the digital
controller in the chapter "Resetting
alarms" on page 7.
The unit is in anti-freeze alarm. Check on the controller and refer to
symptom "4. One of the following
safety devices is activated". Refer to
the explanation of the digital
controller in the chapter "Resetting
alarms" on page 7
The remote ON/OFF input is
enabled and the remote switch is off. Put the remote switch on or disable
the remote ON/OFF input.
The keyboard is locked. The user
parameter h9 is set to 0.
Unlock the controller keyboard.
Symptom 4.1: Overcurrent relay of compressor
POSSIBLE CAUSES CORRECTIVE ACTION
Failure of one of the phases. Check fuses on the supply panel or
measure the supply voltage.
Voltage too low. Measure the supply voltage.
Overload of motor. Reset. If the failure persists, call your
local dealer.
RESET Push the red button on the over-
current relay inside the switch box.
The controller still needs to be reset.
Symptom 4.2: Low pressure switch or anti-freeze alarm
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to water heat exchanger
too low. Increase the water flow.
Shortage of refrigerant. Check for leaks and refill refrigerant,
if necessary.
Unit is working out of its operation
range. Check the operation conditions of
the unit.
Inlet temperature to the water heat
exchanger is too low. Increase the inlet water temperature.
Flow switch is not working or no
water flow. Check the flow switch and the water
pump.
RESET After pressure rise, the low pressure
switch resets automatically, but the
controller still needs to be reset.