
19
and wiring. Disconnect electric power for ve seconds. If LED
remains o after restoring power, replace control.
An external lockout occurs if the integrated ignition control
determines that a measurable combustion cannot be
established within three (3) consecutive ignition attempts. If
ame is not established within the seven (7) second trial for
ignition, the gas valve is de-energized, 15 second inter-purge
cycle is completed, and ignition is reattempted. The control will
repeat this routine three times if a measurable combustion is
not established. The control will then shut o the induced draft
blower and go into a lockout state.
If ame is established but lost, the control will energize the
circulator blower at the heat speed and then begin a new ignition
sequence. If ame is established then lost on subsequent
attempts, the control will recycle for four (4) consecutive ignition
attempts (ve attempts total) before locking out.
The diagnostic fault code is 1 ash for a lockout due to failed
ignition attempts or ame dropouts. The integrated control will
automatically reset after one hour, or it can be reset by removing
the thermostat signal or disconnecting the electrical power
supply for over ve seconds. If the diagnostic LED indicates
an external lockout, perform the following checks:
• Check the supply and manifold pressures
• Check the gas orices for debris
• Check gas valve for proper operation
• Check secondary limit
A dirty lter, excessive duct static, insucient air ow, a
faulty limit, or a failed circulator blower can cause this
limit to open. Check lters, total external duct static,
circulator blower motor, blower motor speed tap (see
wiring diagram), and limit. An interruption in electrical
power during a heating cycle may also cause the
auxiliary limit to open. The automatic reset secondary
limit is located on top of the circulator blower assembly.
• Check rollout limit
If the burner ames are not properly drawn into the heat
exchanger, the ame rollout protection device will open.
Possible causes are restricted or blocked ue passages,
blocked or cracked heat exchanger, a failed induced
draft blower, or insucient combustion air. The rollout
protection device is a manual reset limit located on the
burner bracket. The cause of the ame rollout must
be determined and corrected before resetting the limit.
• Check ame sensor
A drop in ame signal can be caused by nearly invisible
coating on the sensor. Remove the sensor and carefully
clean with steel wool.
• Check wiring
Check wiring for opens/shorts and miswiring.
Important: If you have to frequently reset your gas/
electric package unit, it means that a problem exists that
should be corrected. Contact a qualied servicer for further
information.
A pressure switch stuck open can be caused by a faulty pressure
switch, faulty wiring, a disconnected or damaged hose, a
blocked or restricted ue, or a faulty induced draft blower.
If the control senses an open pressure switch during the pre-
purge cycle, the induced draft blower only will be energized.
If the pressure switch opens after ignition has begun the gas
valve is de-energized, the circulator blower heat o cycle begins,
and the induced draft blower remains on. The diagnostic fault
code is two ashes.
A stuck closed pressure switch can be caused by a faulty
pressure switch or faulty wiring. If the control encounters a
pressure switch stuck closed, the induced draft blower remains
o. The diagnostic LED code for this fault is three (3) ashes.
If the primary limit switch opens, the gas valve is immediately
de-energized, the induced draft and air circulating blowers are
energized. The induced draft and air circulator blowers remain
energized until the limit switch recloses. The diagnostic fault
code for an open limit is four (4) ashes.
A primary limit will open due to excessive supply air temperatures.
This can be caused by a dirty filter, excessive duct static,
insucient air ow, or a faulty limit. Check lters, total external
duct static, blower motor, blower motor speed tap (see wiring
diagram), and limit. This limit will automatically reset once the
temperature falls below a preset level.
Primary Limit
A primary limit will open due to excessive supply air
temperatures. This can be caused by a dirty lter, excessive
duct static, insucient air ow, or a faulty limit. Check lters,
total external duct static, blower motor, blower motor speed tap
(see wiring diagram), and limit. This limit will automatically reset
once the temperature falls below a preset level.
Auxiliary/Secondary Limit
A dirty lter, excessive duct static, insucient air ow, a faulty
limit, or a failed circulator blower can cause this limit to open.
Check lters, total external duct static, circulator blower motor,
blower motor speed tap (see wiring diagram), and limit. An
interruption in electrical power during a heating cycle may also
cause the auxiliary limit to open. The automatic reset secondary
limit is located on top of the circulator blower assembly.
Rollout Limit
If the burner ames are not properly drawn into the heat
exchanger, the flame rollout protection device will open.
Possible causes are restricted or blocked flue passages,
blocked or cracked heat exchanger, a failed induced draft
blower, or insucient combustion air. The rollout protection
device is a manual reset limit located on the burner bracket.
The cause of the ame rollout must be determined and corrected
before resetting the limit.
Flame Detected with Gas Valve Closed
If flame is detected with the gas valve de-energized, the
combustion and air circulator blowers are energized. The
diagnostic fault code is ve (5) ashes for this condition. The
control can be reset by removing the power supply to the unit
or it will automatically reset after one hour. Miswiring is the
probable cause for this fault.
Low Flame Signal (Two-Stage Models ONLY)
Under some conditions, the fuel or air supply can create a
nearly invisible coating on the ame sensor. This coating acts
as an insulator causing a drop in the ame signal. If the ame
signal drops below a predetermined value, the ignition control
will display an error code of (1) ash on the amber diagnostic
LED. The unit will continue to operate until the control can no
longer detect ame.