Daikin EWWP045KAW1M User manual

Operation manual
1
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
C
ONTENTS
Page
Introduction ....................................................................................... 1
Technical specifications ............................................................................. 1
Electrical specifications ............................................................................. 2
Description ........................................................................................ 2
Function of the main components.............................................................. 3
Safety devices............................................................................................ 4
Internal wiring - Parts table........................................................................ 4
Before operation................................................................................ 5
Checks before initial start-up ..................................................................... 5
Water supply.............................................................................................. 5
General recommendations ........................................................................ 5
Operation 16~24Hp........................................................................... 5
Digital controller......................................................................................... 5
Working with the 16~24Hp units................................................................ 6
Advanced features of the digital controller................................................. 8
Operation 32~72Hp......................................................................... 12
Digital controller....................................................................................... 12
Working with the 32~72Hp units.............................................................. 12
Advanced features of the digital controller............................................... 14
Troubleshooting............................................................................... 19
Maintenance.................................................................................... 20
Important information regarding the refrigerant used .............................. 20
Maintenance activities ............................................................................. 20
Disposal requirements............................................................................. 20
I
NTRODUCTION
This operation manual concerns packaged water-cooled water
chillers of the Daikin EWWP-KA series. These units are provided for
indoor installation and used for cooling and/or heating applications.
The units can be combined with Daikin fan coil units or air handling
units for air conditioning purposes. They can also be used for
supplying water for process cooling.
This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local dealer.
Technical specifications
(1)
EWWP045KAW1M ECB1MUW
EWWP055KAW1M ECB2MUW
EWWP065KAW1M ECB3MUW
Packaged water-cooled water chillers
Operation manual
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW THIS MANUAL AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
Read the chapter "User settings menu" on page 14 before
changing the parameters.
Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in "Checks before initial
start-up" on page 5.
(1) Refer to the engineering data book for the complete list of specifications.
General
Hp 16 20 24 32 36 40 44 48 52 56 60 64 68 72
Nominal cooling
capacity
(a) (kW)
43.0 56.0 65.0 86 99 112 121 130 142 155 168 177 186 195
Nominal input
(b) (kW)
12.1 16.0 18.3 24.2 28.1 32.0 34.3 36.6 40.2 44.1 48.0 50.3 52.6 54.9
Dimensions HxWxD
(mm)
600 x 600 x 1200 1200 x 600 x 1200 1800 x 600 x 1200
Machine weight
(kg)
300 320 334 600 620 640 654 668 920 940 960 974 988 1002
Connections
•water inlet (inch)
2x FBSP 1.5" 2x 2x FBSP 1.5" 3x 2x FBSP 1.5"
•water outlet (inch)
2x FBSP 1.5" 2x 2x FBSP 1.5" 3x 2x FBSP 1.5"
Compressor
Type hermetically sealed scroll
Qty x model
2x
JT212DA-YE 2x
JT300DA-YE 2x
JT335DA-YE 4x
JT212DA-YE
2x
JT212DA-YE
+ 2x
JT300DA-YE
4x
JT300DA-YE
2x
JT300DA-YE
+ 2x
JT335DA-YE
4x
JT335DA-YE
4x
JT212DA-YE
+ 2x
JT300DA-YE
2x
JT212DA-YE
+ 4x
JT300DA-YE
6x
JT300DA-YE
4x
JT300DA-YE
+ 2x
JT335DA-YE
2x
JT300DA-YE
+ 4x
JT335DA-YE
6x
JT335DA-YE
Speed
(rpm)
2900 2900 2900
Oil type FVC 68D FVC 68D FVC 68D
Oil charge volume
(l)
2x 2.7 4x 2.7 6x 2.7
Evaporator
Type brased plate heat exchanger
Qty 12 3
Nominal water flow
(l/min)
123 161 186 247 284 321 347 373 407 444 482 507 533 559
Water flow range
(l/min)
62 -247 80 - 321 93 - 373 123 - 493 142 - 568 161 - 642 173 -694 186 - 745
204 - 814 222 - 889 241 -963 254-1015 267-1066 280-1118
Condenser
Type brased plate heat exchanger
Qty 12 3
Nominal water flow
(l/min)
157 205 237 314 362 410 442 474 519 567 614 647 679 711
Water flow range
(l/min)
79 - 314 102 - 410 118 - 474 157 - 629 181 -724 205 - 819 221 - 883 237 - 948
260-1038 283-1133 307-1229 323-1293 339-1357 355-1422
(a) The nominal cooling capacity is based on:
-entering water temperature of 12°C
-chilled water temperature of 7°C
-condenser in/out water temperature of 30/35°C
(b) The nominal input includes total input of the unit: compressor, control circuit and water pumps.

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
2
Electrical specifications
(1)
D
ESCRIPTION
Figure -
Main components
Required space around the unit for service
(1) Refer to the engineering data book for the complete list of specifications.
General
Hp 16 20 24 32 36 40 44 48 52 56 60 64 68 72
Power supply
• Phase
3N~ 3N~ 3N~
•Frequency (Hz)
50 50 50
•Voltage (V)
400 400 400
•Voltage tolerance (%)
±10 ±10 ±10
Unit
• Nominal running
current (A)
20.8 26.6 30.0 41.6 47.0 52.4 56.2 60.0 67.8 73.2 78.6 82.4 86.2 90.0
• Maximum running
current (A)
28 36 40 56 64 72 76 80 92 100 108 112 116 120
• Recommended fuses
according to IEC 269-2 (A)
3x 35 3x 40 3x 50 3x 63 3x 63 3x 80 3x 80 3x 80 3x 100 3x 100 3x 125 3x 125 3x 125 3x 125
Compressor
• Phase
3~ 3~ 3~
•Frequency (Hz)
50 50 50
•Voltage (V)
400 400 400
• Nominal running
current (A)
10.4 13.1 15.0 10.4 10.4/13.1 13.1 13.1/15 15
10.4/13.1 10.4/13.1
13.1 13.1/15 13.1/15 15
27 11
23
26
500 500
500
2
3
1
4
20
17
12
13
24
21
18
25 16
22
19
28
28
28 8
5
6
9
7
10
15
14
1
52~72Hp
32~48Hp
16~24Hp
1
Compressor
15
Condenser water in 2
2
Evaporator
16
Condenser water in 3
3
Condenser
17
Evaporator entering water temperature sensor 1
4
Switchbox
18
Evaporator entering water temperature sensor 2
5
Chilled water in 1
19
Evaporator entering water temperature sensor 3
6
Chilled water in 2
20
Freeze up sensor 1
7
Chilled water in 3
21
Freeze up sensor 2
8
Chilled water out 1
22
Freeze up sensor 3
9
Chilled water out 2
23
Condenser entering water temperature sensor 1
10
Chilled water out 3
24
Condenser entering water temperature sensor 2
11
Condenser water out 1
25
Condenser entering water temperature sensor 3
12
Condenser water out 2
26
Digital display controller 16~24Hp
13
Condenser water out 3
27
Digital display controller 32~72Hp
14
Condenser water in 1
28
Power supply intake

Operation manual
3
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Function of the main components
Figure -
Functional diagram
As the refrigerant circulates through the unit, changes in its state or
condition occur. These changes are caused by the following main
components:
■
Compressor
The compressor (M*C) acts as a pump and circulates the
refrigerant in the refrigeration circuit. It compresses the refri-
gerant vapour coming from the evaporator to a pressure at
which it can easily be liquified in the condenser.
■
Condenser
The function of the condenser is to change the state of the
refrigerant from gaseous to liquid. The heat gained by the gas in
the evaporator is discharged through the condenser and the
vapour condenses to liquid.
■
Filter
The filter installed behind the condenser removes small particles
from the refrigerant to prevent blockage of the tubes.
■
Expansion valve
The liquid refrigerant coming from the condenser enters the
evaporator via an expansion valve. The expansion valve brings
the liquid refrigerant to a pressure at which it can easily be
evaporated in the evaporator.
■
Evaporator
The main function of the evaporator is to take heat from the
water that flows through it. This is done by turning the liquid
refrigerant, coming from the condenser, into gaseous
refrigerant.
■
Water inlet/outlet connection
The water inlet and outlet connections allow an easy connection
of the unit to the water circuit of the air handling unit or industrial
equipment.
S4LP
S1HP
S5LP
S2HP
R3T
R4TR5T
Q2D
Q1D
HP
LP
HP
LP
M2C
M1C
S4LP
S1HP
S5LP
S2HP
R3T
R4TR5T
Q2D
Q1D
HP
LP
HP
LP
M2C
M1C
S4LP
S1HP
S5LP
S2HP
R3T
R4TR5T
Q2D
Q1D
HP
LP
HP
LP
M2C
M1C
52~72Hp
32~48Hp
16~24Hp
Condenser
Filter
Water
inlet
Water
outlet
Water
inlet
Water
outlet
Evaporator
Filter
Compressor
Compressor

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
4
Safety devices
■
Overcurrent relay
The overcurrent relay (K*S) is located in the switch box of the
unit and protects the compressor motor in case of overload,
phase failure or too low voltage.The relay is factory-set and may
not be adjusted. When activated, the overcurrent relay has to be
reset in the switch box and the controller needs to be reset
manually.
■
High-pressure switch
The high-pressure switch (S*HP) is installed on the discharge
pipe of the unit and measures the condenser pressure (pressure
at the outlet of the compressor). When the pressure is too high,
the pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs
to be reset manually.
■
Low pressure switch
The low-pressure switch (S*LP) is installed on the suction pipe
of the unit and measures the evaporator pressure (pressure at
the inlet of the compressor). When the pressure is too low, the
pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs
to be reset manually.
■
Reverse phase protector
The reverse phase protector (R1P) is installed in the switch box
of the unit. It prevents the compressor from running in the wrong
direction. If the unit does not start, two phases of the power
supply must be inverted.
■
Discharge thermal protector
The discharge thermal protector (Q*D) is activated when the
temperature of the refrigerant leaving the compressor becomes
too high. When the temperature returns to normal, the protector
resets automatically, but the controller needs to be reset
manually.
■
Freeze-up protection
The freeze-up protection prevents the water in the evaporator
from freezing during operation. When the outlet water
temperature is too low, the controller disables the circuit. When
the outlet water temperature returns to normal, the circuit can
start up again.
When freeze-up protection occurs several times in a certain
period, the freeze-up alarm will be activated and the circuit will
be shut down. The cause of freezing up should be investigated
and after outlet water temperature has risen enough, the alarm
indicator on the controller needs to be reset manually.
■
Additional interlock contact
To avoid that the unit could be started or run without water
circulating through the water heat exchanger, an interlock
contact (S11L) of e.g. a flow switch must be installed in the start-
up circuit of the unit.
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:
A1P........................ PCB terminal unit
A2P.................**.... PCB address card
F1,2,3U...........# .... Main fuses for the unit
F5B,F6B ................ Automatic fuse for the control circuit/secondary
of TR1
F8U........................ Surge-proof fuse
F9U.................## .. Surge-proof fuse
H1P.................* ..... Indication lamp alarm
H3P.................* ..... Indication lamp operation compressor (M1C)
H4P........................ Indication lamp operation compressor (M2C)
K1A........................ auxiliary contactor for alarm (for 16~24Hp only)
K1A........................ auxiliary contactor for high pressure
(for 32~72Hp only)
K1M ....................... Compressor contactor (M1C)
K1P ................ * .....Pumpcontactor
K2M........................Compressor contactor (M2C)
K4S ........................Overcurrent relay (M1C)
K5S ........................Overcurrent relay (M2C)
K19T ......................Timer, time delay for M2C
M1C,M2C...............Compressor motor
PE ..........................Main earth terminal
Q1D........................Discharge thermal protector (M1C)
Q2D........................Discharge thermal protector (M2C)
R1P........................Reverse phase protector
R3T ........................Evaporator inlet water temperature sensor
R4T ........................Evaporator outlet water temperature sensor
(Freeze up sensor)
R5T ........................Condenser inlet temperature sensor
S1HP,S2HP............High pressure switch
S4LP,S5LP.............Low pressure switch
S7S ........................Switch for remote cooling/heating selection
(for 16~24Hp only)
S7S ........................Changeable digital input 1(for 32~72Hp only)
S9S ................ * .....Switch for remote start/stop (for 16~24Hp only)
S9S ................ * .....Changeable digital input 2 (for 32~72Hp only)
S10L............... #.....Flowswitch
S11L............... #.....Contact that closes if the pump is working
S12S .............. #.....Main isolator switch
TR1 ........................Transfo 230 V
➞
24 V for power supply of
controllers
Y1R........................Reversing valve
Y1S ........................Solenoid valve for injection line
X1
...........................Connector for digital inputs, analog inputs, analog
outputs and for power supply controller (A1P)
X2...........................Connector for digital outputs (A1P)
X3...........................Connector for (A1P)
X4,X5,X6................Interconnection connector Main
↔
Control
switchbox
Terminal unit: Digital Inputs
X1 (ID1-GND) ........flowswitch
X1 (ID2-GND) ........remote cooling/heating selection
X1 (ID3-GND) ........high pressure switch + discharge protector +
overcurrent
X1 (ID4-GND) ........low pressure switch
X1 (ID5-GND) ........remote On/Off
Terminal unit: Digital outputs (relays)
X2 (C1/2-NO1).......compressor M1C on
X2 (C1/2-NO2).......compressor M2C on
X2 (C3/4-NO3).......voltage free contact for pump
X2 (C3/4-NO4).......voltage free contact for reversing valve
X2 (C5-NO5)..........alarm voltage free contact
Terminal unit: Analog inputs
X1 (B1-GND)..........evaporator inlet water temperature
X1 (B2-GND)..........evaporator outlet water temperature (Freeze up
sensor)
X1 (B3-GND)..........condenser inlet water temperature
Not included with standard unit
Not possible as option Possible as option
Obligatory # ##
Not obligatory * **

Operation manual
5
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
B
EFORE
OPERATION
Checks before initial start-up
After the installation of the unit, check the following before switching
on the circuit breaker:
1
Field wiring
Make sure that the field wiring between the local supply panel
and the unit has been carried out according to the instructions
described in the installation manual, according to the wiring
diagrams and according to European and national regulations.
2
Additional interlock contact
An additional interlock contact S11L should be provided (e.g.
flow switch, contact of pump motor contactor). Make sure that it
has been installed between the appropriate terminals (refer to
the wiring diagram supplied with the unit). S11L should be a
normal open contact.
3
Fuses or protection devices
Check that the fuses or the locally installed protection devices
are of the size and type specified in the installation manual.
Make sure that neither a fuse nor a protection device has been
bypassed.
4
Earth wiring
Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.
5
Internal wiring
Visually check the switch box on loose connections or damaged
electrical components.
6
Fixation
Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.
7
Damaged equipment
Check the inside of the unit on damaged components or
squeezed pipes.
8
Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.
9
Oil leak
Check the compressor on oil leakage. If there is an oil leak, call
your local dealer.
10
Power supply voltage
Check the power supply voltage on the local supply panel. The
voltage should correspond to the voltage on the identification
label of the unit.
Water supply
Fill the water piping, taking into account the minimum water volume
required by the unit. Refer to the "installation manual".
Make sure that the water is of the quality as mentioned in the
installation manual.
Purge the air at the high points of the system and check the operation
of the circulation pump and the flow switch.
General recommendations
Before switching on the unit, read following recommendations:
1
When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.
2The service panels of the switch boxes may only be opened by a
licensed electrician for maintenance purposes.
OPERATION 16~24HP
The 16~24Hp units are equipped with a digital controller offering a
user-friendly way to set up, use and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apart
from the first section, which gives a brief description of the controller
itself, each section or subsection deals with a specific task you can
perform with the unit.
Digital controller
User interface
The digital controller consists of a numeric display, four labelled keys
which you can press and four LEDs providing extra user information.
Figure : Digital controller
Keys provided on the controller:
Each key, except for the lower left key, combines two functions: E/
O, A/ Yand I/ Z. The function carried out when the user
presses one of these keys depends on the status of the controller
and the unit at that specific moment.
LEDs provided on the controller:
Make sure that the circuit breaker on the power supply
panel of the unit is switched off.
Ekey, to enter the scroll list of user parameters, to confirm a
parameter modification and to return to normal operation.
Okey, to de-activate the buzzer in the case of an alarm.
Akey, to scroll through the list of direct or user parameters or to
raise a setting.
Ykey, to start the unit in heating mode or to switch the unit off when
heating mode is active.
Rkey, to enter the scroll list of direct parameters or to switch
between a parameter's code and its value.
Ikey, to start the unit in cooling mode or to switch the unit off when
cooling mode is active.
Zkey, to scroll through the list of direct or user parameters or to
lower a setting.
T
LEDs, indicates the status of the compressor 1 (left LED) and
compressor 2 (right LED). The TLEDs do not light up when the
compressor is not active, blinks when the compressor cannot start
up although extra load is requested (e.g. timer active) and lights
up permanently when the compressor is active.
YLED, indicates that heating mode is active.
ILED, indicates that cooling mode is active.
ULED, indicates that the value on the numeric display should be
multiplied by 100.
comp
x
100
clear
PRG
mute
SEL

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
6
Direct and user parameters
The digital controller provides direct and user parameters. The direct
parameters are important for the everyday usage of the unit, e.g. to
adjust the temperature setpoint or to consult actual operational
information. The user parameters on the contrary provide advanced
features such as adjusting time delays or disabling the buzzer.
Each parameter is defined by a code and a value. For example, the
parameter used to select local or remote on/off control has code h7
and value 1or 0.
Working with the 16~24Hp units
This chapter deals with the everyday usage of the unit. Here, you will
learn how to perform routine tasks, such as:
■"Switching the unit on" on page 6 and "Switching the unit off" on
page 6,
■"Adjusting the cooling temperature setpoint" on page 6 and
"Adjusting the heating temperature setpoint" on page 7,
■"Consulting actual operational information" on page 7,
■"Resetting alarms" on page 7,
■"Resetting warnings" on page 8.
Switching the unit on
To switch the unit on, proceed as follows:
1When the on/off digital input user parameter h7 is set to 0(=No),
press the Ikey for approximately 5 seconds to switch the unit
on in cooling mode (inlet water temperature control of
evaporator) or press the Ykey for approximately 5 seconds to
switch the unit on in heating mode (inlet water temperature
control of condenser).
When the on/off digital input user parameter h7 is set to
1(=Yes), you can also switch the unit on using the remote on/off
switch (installed by the customer).
In both cases an initialization cycle is started and the TLED
starts blinking. The ILED or the YLED lights up, indicating
whether cooling or heating mode is selected. Once all the timers
have reached zero, the unit starts up and the TLED lights up
permanently. The numeric display shows the actual inlet water
temperature of the evaporator in cooling mode or the actual inlet
water temperature of the condenser in heating mode.
2When the unit is started up for the first time, or when the unit has
been out of operation for a longer period, it is recommended to
go through the following checklist.
Abnormal noise and vibrations
Make sure the unit does not produce any abnormal noises or
vibrations: check the fixations and piping. If the compressor
makes any abnormal noises, this may also be caused by an
overcharge of refrigerant.
Working pressure
It is important to check the high and low pressure of the
refrigerant circuit to ensure the proper operation of the unit and
to guarantee that the rated output will be obtained.
3If the unit does not start after a few minutes, consult the actual
operational information available in the list of direct parameters.
Also refer to the chapter "Troubleshooting" on page 19.
Switching the unit off
To switch the unit off, proceed as follows:
1When the on/off digital input user parameter h7 is set to 0(=No)
and the unit is on, press the Ikey for approximately 5 seconds
to switch the unit off.
The ILED and the TLED are extinguished.
2When the on/off digital input user parameter h7 is set to 0(=No)
and heating mode is active, press the Ykey for approximately 5
seconds to switch the unit off.
The YLED and the TLED are extinguished.
3When the on/off digital input user parameter h7 is set to
1(=Yes), switch the unit off using the remote on/off switch.
The ILED or the YLED (depending on the active mode) and
the TLED are extinguished.
Adjusting the cooling temperature setpoint
The units enable definition and modification of the cooling
temperature setpoint. The default, limit and step values for the
cooling setpoint are:
■Default value 12.0°C
■Limit values 7.0to 25.0°C
■Step value 0.1°C
To adjust the cooling temperature setpoint, proceed as follows:
1Press the Rkey for approximately 5 seconds to enter the list of
direct parameters.
The direct parameter code r1 defining the cooling temperature
setpoint appears on the display.
2Press the Rkey.
The actual cooling temperature setpoint appears on the display.
3Press the Aor Zkey to raise, respectively lower the
temperature setting.
4Press the Rkey to return to parameter code r1.
5To save the adjusted temperature setpoint, press the Ekey. To
cancel the modification wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of direct parameters and returns to its normal operation,
displaying the inlet water temperature.
In the second case the display starts flashing. Approximately
40 seconds later, the controller leaves the list of direct
parameters without saving the modified parameter. The inlet
water temperature reappears on the display.
NOTE Temperature readout tolerance: ±1°C.
Legibility of the numeric display may decrease in direct
sunlight.
The pressures measured will vary between a maximum
and minimum value, depending on the water and outdoor
temperatures (at the moment of measurement).
NOTE In case of remote on/off control (h7=1), it is recom-
mended to install an on/off switch near the unit in
series with the remote switch. The unit can then be
switched off from either place.
The selection of cooling mode or heating mode can only
be carried out at startup.
Selecting an opposite mode without switching the unit off is
impossible.
NOTE By pressing any button while the display is flashing
and cancelling of all changes is in progress, the can-
celling process is stopped, the display stops flashing
and the user can continue to change the settings.

Operation manual
7EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Adjusting the heating temperature setpoint
In addition to the cooling setpoint, the 16~24Hp units enable
definition of a temperature setpoints for heating operation. The
default, limit and step values for the heating setpoint are:
■Default value 30°C
■Limit values 15 to 50 °C
■Step value from 15.0to 19.9°C 0.1°C
from 20 to 50°C 1°C
To adjust the heating temperature setpoint, proceed as follows:
1Press the Rkey for approximately 5 seconds to enter the list of
direct parameters.
The direct parameter code r1 defining the cooling temperature
setpoint appears on the display.
2Press the Akey twice.
The direct parameter code r3 defining the heating temperature
setpoint appears on the display.
3Press the Rkey.
The actual heating temperature setpoint appears on the display.
4Press the Aor Zkey to raise, respectively lower the
temperature setting.
5Press the Rkey to return to parameter code r3.
6To save the adjusted temperature setpoint, press the Ekey. To
cancel the modification wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of direct parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of direct
parameters without saving the modified parameter. The inlet
water temperature reappears on the display.
Consulting actual operational information
The actual operational information that can be consulted in the list of
direct parameters consists of:
■r6 : outlet water temperature evaporator,
■r8 : when cooling mode is active: inlet water temperature of the
condenser,
when heating mode is active: inlet water temperature of the
evaporator,
■c9 : total running hours of the compressor1,
■ca : total running hours of the compressor2,
■cv : total running hours of the pump.
To consult the actual operational information, proceed as follows:
1Press the Rkey for approximately 5 seconds to enter the list of
direct parameters.
The direct parameter code r1 defining the cooling temperature
setpoint appears on the display.
2Depending on the information to be consulted, select parameter
code r6, r8, c9, ca or cv using the Aand/or Zkey.
3Press the Rkey to consult the actual value of the selected
parameter.
4Press the Rkey to return to the parameter codes.
5To consult other actual operational information, repeat from
instruction 2 onwards.
6To return to normal operation, press the Ekey or wait
approximately 40 seconds.
In the first case, the controller immediately leaves the list of
direct parameters and returns to normal operation displaying the
inlet water temperature.
In the second case, the display will start flashing. Approximately
40 seconds later, the controller leaves the list of direct para-
meters. The inlet water temperature reappears on the display.
Resetting alarms
When an alarm is detected, the following happens:
■the buzzer is activated (if enabled by means of user parameter p4),
■the alarm relay is energized,
■the display starts flashing, alternately showing the alarm code
and the inlet water temperature.
The following alarm codes may appear on the screen:
■a1: indicates an anti-freeze alarm,
■e1:indicates that the NTC probe used to measure the
evaporator inlet water temperature is defective,
■e2:indicates that the NTC probe used to measure the outlet
water temperature is defective,
■e3:indicates that the NTC probe used to measure the
condenser inlet water temperature is defective,
■ee,ep:indicates that the EEPROM on the controller PCB inside the
unit is defective,
■ei,e0:indicates that the supply voltage is exceedingly low (ei) or
exceedingly high (e0). In these cases contact a licensed
electrician,
■el:indicates that the power supply has a "remarkable noise". In
this case contact a licensed electrician,
■fl:indicates that there was no water flow either during the
period of 15 seconds after the pump was started or for 5
seconds while the compressor is active,
■h1:indicates that a high pressure switch, the discharge thermal
protection or the overcurrent protection of the compressor
motor is activated,
■l1: indicates that the low pressure switch is activated.
To reset an alarm, proceed as follows:
1Press the Okey to acknowledge the alarm.
The buzzer is de-activated.
2Find the cause of shutdown and correct.
Refer to the chapter "Troubleshooting" on page 19.
3If the alarm codes a1, fl, h1 or l1 appear on the display, reset
the alarm manually by pressing the Aand Zkey
simultaneously for approximately 5 seconds.
In all other cases the alarm is reset automatically.
Once the alarm is reset, the error code no longer appears on the
display. The controller continues its normal operation, displaying
the inlet water temperature.
NOTE To reset the timers c9, ca and cv, refer to chapter
"Resetting warnings" on page 8.
NOTE If the alarm codes fl and h1 are flashing alternately,
the alarm is most probably caused by the reverse
phase protector.

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
8
Resetting warnings
During normal operation, the display of the controller may start
flashing, alternately showing the inlet water temperature and the
following warning code:
■n1:indicates that the compressor1 requires maintenance: the
total running hours of the compressor1 (direct parameter c9)
has exceeded the setting of the timer threshold for
maintenance warning (user parameter cb).
■n2:indicates that the compressor2 requires maintenance: the
total running hours of the compressor2 (direct parameter ca)
has exceeded the setting of the timer threshold for
maintenance warning (user parameter cb).
To reset the maintenance warning n1 or n2, proceed as follows:
1Enter the list of direct parameters by pressing the Rkey for
approximately 5 seconds.
The parameter code r1 appears on the display.
2Select parameter code c9 or ca using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Press the Aand Zkeys simultaneously for approximately
5 seconds.
The timer's value becomes 0.
5Press the Rkey to return to parameter code c9 or ca.
6Press the Ekey to return to normal operation.
Advanced features of the digital controller
This chapter gives an overview of the direct parameters and user
parameters provided by the controller. In the following chapter, you
will learn how you can set up and configure the unit using these
parameters.
Overview of the direct parameters
The list of direct parameters is accessible by pressing the Rkey for
approximately 5 seconds.
When scrolling through the list of direct parameters using the Aand/
or Zkey, the parameters appear in the following order:
■r1: to define the cooling temperature setpoint,
■r2: to define the cooling temperature difference,
■r3: to define the heating temperature setpoint,
■r4: to define the heating temperature difference,
■r6: to check the evaporator outlet water temperature,
■r8:when cooling mode is active: inlet water temperature of the
condenser,
when heating mode is active: inlet water temperature of the
evaporator,
■c9: to check the total running hours of the compressor1,
■ca: to check the total running hours of the compressor2,
■cv: to check the total running hours of the pump.
Overview of the user parameters
The list of user parameters is only accessible by means of the user
password. When scrolling through the list of parameters using the A
and/or Zkey, you see the direct parameters and user parameters.
The user parameters appear in the following order:
■:d: to define the measurement unit (°C or °F),
■c7:to define the time delay between the pump startup and the
compressor startup,
■c8:to define the time delay between the unit shutdown and the
pump shutdown,
■cb: to define the time threshold for maintenance warning,
■p4:to disable the buzzer or to define the activation period of the
buzzer in case of an alarm,
■h6: to activate or to deactivate the remote cool/heat control,
■h7: to activate or de-activate the remote on/off control,
■h9: to lock or unlock the controller keyboard,
■ha: to define the unit's serial address,
■h8,hb,c6: not used.
Tasks carried out using direct parameters
Entering the list of direct parameters
1Press the Rkey for approximately 5 seconds.
The controller enters the list of direct parameters, displaying
parameter code r1.
Defining the cooling temperature difference
To control the cooling load, the unit is equipped with a two-step
thermostat. The thermostat's "cooling temperature difference" can
be modified by means of direct parameter r2.
The default, limit and step values are:
■Default value 3.0°C
■Limit values 0.3to 19.9°C
■Step value 0.1°C
To define the cooling temperature difference, proceed as follows:
1Enter the list of direct parameters.
2Press the Akey once.
Direct parameter code r2 appears on the display.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to switch to the list of parameter codes.
6To adjust or to consult other direct parameters before saving the
modifications, select another direct parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
NOTE Do not forget to carry out the required maintenance
activities after resetting the timers.
Besides resetting timer c9 (running hours of the
compressor 1) and ca (running hours of the
compressor 2), it is also possible to reset timer cv
which defines the total running hours of the pump. To
do this, consult the timer's value (refer to paragraph
"Consulting actual operational information" on page 7)
and press the Aand Zkeys simultaneously for
approximately 5 seconds while the timer's value is
displayed. The timer's value becomes 0. Then
successively press the Rkey and the Ekey to return
to normal operation.
12 15
°C
13.5
compressor
inlet water temperature
of evaporator
ON
ON
OFF
OFF
compressor2
compressor1

Operation manual
9EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
7To save the modifications, press the Ekey. To cancel the
modifications, wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of direct parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of direct
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Defining the heating temperature difference
To control the heating load, the unit is equipped with a two-step
thermostat. The thermostat's "heating temperature difference" can be
modified by means of direct parameter r4.
The default, limit and step values are:
■Default value 3.0°C
■Limit values 0.3to 19.9°C
■Step value 0.1°C
To define the heating temperature difference, proceed as follows:
1Enter the list of direct parameters.
2Press the Akey three times.
Direct parameter code r4 appears on the display.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other direct parameters before saving the
modifications, select another direct parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of direct parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of direct
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Tasks carried out using user parameters
Entering the list of user parameters
Access to the list of user parameters is protected by the user
password (a 3-digit number between 0and 199).
To enter the list of user parameters, proceed as follows:
1Press the Ekey for approximately 5 seconds.
The number 00 starts flashing on the display.
2Enter the correct password using the Aand/or Zkey.
The password's value is 22.
3Press the Rkey to confirm the password and to enter the list of
user parameters.
The controller displays parameter code :d (which is the first user
parameter).
Defining the measurement unit
Depending on the setting of user parameter :d, all temperature
values are displayed in °C or in °F. The conversion formulas from °C
to °F and vice versa are:
■T°C = (T°F – 32) / 1.8
■T°F = (T°C x 1.8) + 32
If user parameter dis set to 0, all temperatures appearing on the
display will be expressed in °C. If user parameter :d is set to 1all
temperatures will be expressed in °F.
To define the measurement unit, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Press the Rkey to switch to the parameter value.
3Select the appropriate setting using the Aand/or Zkey.
4Press the Rkey to return to the list of parameter codes.
5To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 2 onwards.
6To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Defining the time delay between pump and compressor
startup
User parameter c7 allows you to define the time delay between the
pump startup and the compressor startup. The default, limit and step
values for the time delay are:
■Default value 15 sec
■Limit values 0to 150 sec
■Step value 1sec
To define the time delay, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code c7 using the Aand/or Zkey.
Parameter code c7 appears on the display.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
27 30
°C
28.5
compressor
inlet water temperature
of condenser
ON
ON
OFF
OFF
compressor2
compressor1

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
10
Defining the time delay between unit and pump shutdown
User parameter c8 allows you to define the time delay between the
unit shutdown and the pump shutdown, more specifically the period
during which the pump will still be active after the unit has been shut
down. The default, limit and step values for the time delay are:
■Default value 0min
■Limit values 0to 150 min
■Step value 1min
To define the time delay, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code c8 using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Defining the timer threshold for maintenance warning
User parameter cb allows you to define a timer threshold (running
hours of the compressor) after which the controller will generate a
maintenance warning or request. The default, limit and step values
for the timer threshold are:
■Default value 0hours
■Limit values 0to 10,000 hours
■Step value 100 hours
To define the timer threshold, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code cb using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Enabling or disabling the buzzer
When an alarm is detected, the buzzer is activated for the period
defined by user parameter p4. The default, limit and step values for
the activation period are:
■Default value 1min
■Limit values 0to 15 min
0buzzer disabled
15 buzzer active until muted by the user
■Step value 1min
To enable the buzzer for a certain period or to disable the buzzer,
proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code p4 using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Selecting local or remote cool/heat control
User parameter h6 in combination with the remote cool/heat selection
switch (installed by the customer) allows the user to select cooling or
heating mode without using the Ior Ykey on the controller.
■When user parameter h6 is set to 0(= No), cooling or heating
mode is determined by means of the controller.
■When user parameter h6 is set to 1(= Yes), cooling or heating
mode is determined by means of the remote switch.
To select local or remote cool/heat control, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code h6 using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
NOTE If the unit is always working in normal conditions, no
specific maintenance is requested. In this case the
warning function can be disabled by setting parameter
cb to 0.

Operation manual
11 EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Selecting local or remote on/off control
User parameter h7 in combination with the remote on/off switch
(installed by the customer) allows the user to switch the unit on
without using the Ior Ykey on the controller.
■When user parameter h7 is set to 0(= No), the unit can only be
switched on by means of the Ior Ykey on the controller.
■When user parameter h7 is set to 1(= Yes), the unit can be
switched on by means of the remote on/off switch and the Ior
Ykey on the controller.
To select local or remote on/off control, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code h7 using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Locking the controller keyboard
Once user parameter h9 is set to 0, the following advanced features
can no longer be carried out by means of the controller:
■modifying direct and user parameters (parameters can be
displayed but not modified),
■selecting cooling or heating mode,
■resetting the timers.
When user parameter h9 is set to 1, the above-described advanced
features can be carried out using the controller.
To lock or unlock the controller keyboard, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code h9 using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Defining the unit's serial address
To control the unit from a supervisory system, an address card
(optional module) should be installed in the unit. The unit's serial
address required for communication with the supervisory system is
defined by parameter ha. The default, limit and step values for the
serial address are:
■Default value 1
■Limit values 1to 16
■Step value 1
To define the unit's serial address, proceed as follows:
1Enter the list of user parameters.
Parameter code :d appears on the display.
2Select parameter code ha using the Aand/or Zkey.
3Press the Rkey to switch to the parameter value.
4Select the appropriate setting using the Aand/or Zkey.
5Press the Rkey to return to the list of parameter codes.
6To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the Aand/
or Zkey and then repeat from instruction 3 onwards.
7To save the modifications, press the Ekey. To cancel the
modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
8In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.
Key on the controller Remote On/off switch UNIT RESULT
ON ON ON
ON OFF OFF
OFF ON OFF
OFF OFF OFF

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
12
OPERATION 32~72HP
The 32~72Hp units are equipped with a built-in digital controller
offering a user-friendly way to set up, use and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apart
from the first section, which gives a brief description of the controller
itself, each section or subsection deals with a specific task you can
perform with the unit.
Depending on the model there are two or three modules in the
system. The models 32~48Hp only have two modules, whereas the
models 52~72Hp consist of three modules. These modules are
generally named M1, M2 and M3 in the following descriptions. All
information about module 3 (M3) is not applicable for 32~48Hp
models.
Digital controller
User interface
The digital controller consists of an alphanumeric display, labelled
keys which you can press and a number of LEDs.
Figure - Digital controller
Working with the 32~72Hp units
This chapter deals with the everyday usage of the unit. Here, you will
find how to perform routine tasks, such as:
■"Setting the language" on page 12
■"Switching the unit on" on page 12 and "Switching the unit off"
on page 12
■"Consulting actual operational information" on page 12
■"Selecting cooling or heating operation" on page 13
■"Adjusting the temperature setpoint" on page 13
■"Resetting the unit" on page 13
Setting the language
If desired, the operating language can be changed to any of the
following languages: English, German, French, Spanish or Italian.
1Enter the usersettings menu. Refer to chapter "Main menu" on
page 14
2Go to the appropriate screen of the usersettings menu using the
g and h keys.
3Select the appropriate field (LANGUAGE) using the qkey.
4Press the gand hkeys to adjust the language setting.
5Press qto confirm the adjusted language setting.
When the setting has been confirmed, the cursor switches to the next
setting.
Switching the unit on
1Press the Jkey on the controller.
Depending on whether or not the remote ON/OFF switch is
configured (refer to the service manual), the following conditions
may occur.
When no remote ON/OFF switch is configured, the LED inside
the Jkey lights up and an initialization cycle is started. Once all
the timers have reached zero, the unit starts up.
When a remote ON/OFF switch is configured, the following table
applies:
2When the unit is started up for the first time, or when the unit has
been out of operation for a longer period, it is recommended to
check the following.
Abnormal noise and vibrations
Make sure that the unit does not produce abnormal noises or
vibrations: check the fixation, stop valves and piping. If the
compressor makes abnormal noises, this may also be caused by
an overcharge of refrigerant.
3If the water chiller does not start after a few minutes, refer to
"Troubleshooting" on page 19.
Switching the unit off
If the remote on/off control parameter is set to NO:
Press the okey on the controller.
The LED inside the okey goes out.
If the remote on/off control parameter is set to YES:
Press the okey on the controller or switch the unit off using the
remote on/off switch.
The LED inside the okey goes out in the first case and starts
blinking in the second case.
Consulting actual operational information
1Enter the readout menu through the main menu. (Refer to the
chapter "Main menu" on page 14.)
The controller automatically shows the first screen of the
readout menu which provides the following information:
•MANUAL MODE or INLSETP1/2: manual/automatic control mode
operation. If the automatic control mode is selected, the
controller will indicate the active temperature setpoint.
Depending on the status of the remote contact, setpoint one
or setpoint two is active.
•INL WATER E/C: actual inlet water temperature.
•THERMOSTAT STEP: actual thermostat step. The maximum
number of thermostat steps are as listed:
fkey, to enter the main menu
okey, to start up or to shut down the unit.
pkey, to enter the safeties menu or to reset an alarm.
g
h
keys, to scroll up or down through the screens of a menu
(only in case W, Xor Cappears) or to raise, respectively
lower a setting.
qkey, to confirm a selection or a setting.
NOTE Temperature readout tolerance: ±1°C.
Legibility of the alphanumeric display may decrease in
direct sunlight.
Local key Remote switch Unit oLED
ON ON ON ON
ON OFF OFF Flashing
OFF ON OFF OFF
OFF OFF OFF OFF
In case of emergency, switch off the unit by pushing the
emergency stopbutton.
NOTE Also consult "Defining the schedule timer" on page 17.
32Hp 448Hp 464Hp 6
36Hp 452Hp 668Hp 6
40Hp 456Hp 672Hp 6
44Hp 460Hp 6

Operation manual
13 EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
2Press the hkey to enter the next screen of the readout menu.
This screen of the readout menu provides the following
information on the evaporator:
•M1: OUTLWATER: actual outlet water temperature of module 1.
•M2: OUTLWATER: actual outlet water temperature of module 2.
•M3: OUTLWATER: actual outlet water temperature of module 3.
3Press the hkey to enter the next screen of the readout menu.
The COMPRESSOR STATUS screen of the readout menu provides
information concerning the status of the different compressors.
•C11: actual status of compressor 1 of module 1.
•C12: actual status of compressor 2 of module 1.
•C21: actual status of compressor 1 of module 2.
•C22: actual status of compressor 2 of module 2.
•C31: actual status of compressor 1 of module 3.
•C32: actual status of compressor 2 of module 3.
When a circuit is OFF, the following status information may
appear.
•SAFETY ACTIVE: one of the circuit safety devices is activated
(refer to the chapter "Troubleshooting" on page 19).
•(LIMIT): the circuit is limited by a remote contact.
•TIMERS BUSY: the actual value of one of the software timers is
not zero (refer to the "Timers menu" on page 15).
•CAN STARTUP: the circuit is ready to start up when extra
cooling load is needed.
The preceding OFF messages are written down in order of priority. If
one of the timers is busy and one of the safeties is active, the status
information says SAFETY ACTIVE.
4Press the hkey to enter the next screen of the readout menu.
To consult actual operational information about the total running
hours of the compressors.
Selecting cooling or heating operation
The "cooling/heating" menu allows the user to set the unit in cooling
or heating operation.
The COOL/HEAT menu provides information concerning the selected
operation mode.
■COOLING (EVAP): cooling mode. The two setpoints for inlet
water temperature control of the evaporator can be used.
■HEATING (COND): heating mode. The two setpoints for inlet
water temperature control of the condenser can be used.
To define cooling/heating operation, proceed as follows:
1Enter the cooling/heating menu through the main menu. (Refer
to the chapter "Main menu" on page 14.)
2Position the cursor behind MODE using the qkey.
3Select the appropriate setting using the g and h keys.
4Press qto confirm.
The cursor returns to the upper left corner of the screen.
Adjusting the temperature setpoint
The unit provides definition and selection of four or two independent
temperature setpoints.
In cooling operation, two setpoints are reserved for inlet control of the
evaporator.
■INLSETP 1 E: inlet water temperature of evaporator, setpoint 1,
■INLSETP2 E: inlet water temperature of evaporator, setpoint 2.
In heating operation, two setpoints are reserved for inlet control of the
condenser.
■INLSETP 1 C: inlet water temperature of condenser, setpoint 1,
■INLSETP 2 C: inlet water temperature of condenser, setpoint 2.
In double thermostat operation, two setpoints are reserved for inlet
control of the evaporator and two others are reserved for inlet control
of the condenser.
■INLSETP 1 E: inlet water temperature of evaporator, setpoint 1,
■INLSETP2 E: inlet water temperature of evaporator, setpoint 2.
■INLSETP 1 C: inlet water temperature of condenser, setpoint 1,
■INLSETP 2 C: inlet water temperature of condenser, setpoint 2.
The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.
If the manual control mode is selected (refer to "User settings menu"
on page 14), none of the above-mentioned setpoints will be active.
To adjust a setpoint, proceed as follows:
1Enter the setpoints menu through the main menu. (Refer to the
chapter "Main menu" on page 14).
If the user password is disabled for setpoint modifications (refer
to the "User settings menu" on page 14), the controller will
immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the g and h keys. (Refer to the "User
password menu" on page 16). Press qto confirm the password
and to enter the setpoints menu.
2Select the setpoint to be adjusted using the qkey.
A setpoint is selected when the cursor is blinking behind the
setpoint's name.
The ">" sign indicates the actual active temperature setpoint.
3Press the gand hkeys to adjust the temperature setting.
The default, limit and step values for the cooling (evaporator)
and heating (condenser) temperature setpoints are:
4Press qto save the adjusted temperature setpoint.
When the setting has been confirmed, the cursor switches to the
next setpoint.
5To adjust other setpoints, repeat from instruction 2 onwards.
Resetting the unit
The units are equipped with three kinds of safety devices: unit
safeties, module safeties and network safeties.
When a unit safety occurs, all compressors are shut down. The
safeties menu will indicate which safety is activated. The COMPRESSOR
STATUS screen of the readout menu will indicate OFF - SAFETY ACTIVE
for all circuits. The red LED inside the pkey lights up and the buzzer
inside the controller is activated.
When a module safety occurs, the compressors of the corresponding
module are shut down. The COMPRESSOR STATUS screen of the
readout menu will indicate OFF - SAFETY ACTIVE for the module
concerned. The red LED inside the pkey lights up and the buzzer
inside the controller is activated.
If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.
IIIINN
NNLL
LLSS
SSEE
EETT
TTPP
PP IIIINN
NN EE
EE IIIINN
NNLL
LLSS
SSEE
EETT
TTPP
PP IIIINN
NN CC
CC
default value 12°C 30°C
limit values(a)
(a) For glycol units the lower limit of the cooling temperature setpoint can be
adapted in the factory. The following values apply:
INLSETP IN E/C: 5°C, 3°C, –2°C, –7°C
8--> 23°C 15--> 50°C
step value 0.1°C 0.1°C
NOTE Also consult "Defining the schedule timer" on page 17.

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
14
To reset the unit, proceed as follows:
1Press the pkey to acknowledge the alarm.
The buzzer is deactivated.
The controller automatically switches to the corresponding
screen of the safeties menu: unit safety or module safety.
2Find the cause of shutdown and correct.
Refer to "Listing activated safeties and checking the unit status"
on page 17 and the chapter "Troubleshooting" on page 19.
When a safety can be reset, the LED under the pkey starts
blinking.
3Press the pkey to reset the safeties that are no longer active.
Once all safety devices are disactivated and reset, the LED
under the pkey goes out. If one of the safeties is still active, the
LED under the pkey goes on again. In this case, return to
instruction 2.
4If a unit safety occurred or if all modules were shut down due to
module safeties, switch on the unit using the okey.
Advanced features of the digital controller
This chapter gives an overview and a brief functional description of
the screens provided by the different menus. In the following chapter,
you will find how you can set up and configure the unit using the
various menu functions.
The down arrow X on the display indicates that you can go to the next
screen of the current menu using the hkey. The up arrow Won the
display indicates that you can go to the previous screen of the current
menu using the g key. If Cis displayed, this indicates that you can
either return to the previous screen or can go to the next screen by
using the g and h keys.
Main menu
Scroll through the main menu using the g and h keys to move the >
mark in front of the menu of your choice. Push the qkey to enter the
selected menu.
Readout menu
Setpoints menu
Depending upon the settings in the user settings menu and on the
selected cooling/heating operation mode, the "setpoints" menu can
either be entered directly or by means of the user password.
User settings menu
The "user settings" menu, protected by the user password, allows a
full customization of the units.
If the user shuts down the power supply in order to repair a
safety, the safety will automatically be reset after power-up.
NOTE The history information, i.e. the number of times a unit
safety or a circuit safety occurred and the unit status at
the moment of shutdown, can be checked by means of
the history menu.
To consult actual operational infor-
mation about the control mode, the
inlet water temperature of the
evaporator/condenser and the
thermostat step.
To consult information about the
outlet water temperature of the
modules 1, 2 and 3 (only for
52~72Hp).
To consult information about the
compressor status (first screen).
>READOUT MENU
SETPOINTS MENU
USERSETTINGS MENU
TIMERS MENU
HISTORY MENU
INFO MENU
I/O STATUS MENU
USERPASSWORD MENU
COOL/HEAT MENU
BX MANUAL MODE
INL WATER E: 12.0°C
INL WATER C: 30.0 °C
THERMOSTAT STEP :2/6
BC EVAPORATOR
M1 : OUTLWATER: 07.0 °C
M2: OUTLWATER: 07.0 °C
M3: OUTLWATER:-03.0 °C
BC COMPRESSOR STATUS
C11 : OFF-CAN STARTUP
C12: OFF-CAN STARTUP
C21: OFF-CAN STARTUP
To consult information about the
compressor status (second screen).
To consult actual operational
information about the total running
hours of the compressors.
To define the temperature setpoints.
To define the manual settings and to
select the control mode.
To define the thermostat settings.
To define the lead-lag mode of the
modules.
To define capacity limitation.
(first screen)
To define capacity limitation.
(second screen)
To define the pump control settings.
To define the schedule timer.
To define the dual evaporator pump.
To define the display settings.
To define whether or not a password
is needed to enter the setpoints
menu.
BC COMPRESSOR STATUS
C22: OFF-CAN STARTUP
C31 : OFF- SAFETY ACT.
C32: OFF- LIMIT
BW RUNNING HOURS
C11 : 00010h 12 ; 00010h
C21 : 00010h 22 ; 00010h
C31 : 00010h 32 ; 00010h
B>INLSETP1 E : 12.0°C
INLSETP2 E : 12.0°C
INLSETP1 C : 30.0°C
INLSETP2 C : 30.0°C
BC CONTROL SETTINGS
MODE :MANUAL CONTROL
C11 : OFF 12 ; OFF
C21 : OFF 22 ; OFF
BC THERMOST.SETTINGS
STEPS : 6 STPL.: 1.5°C
STEPDIFFERENCE: 0.5°C
LOADUP: 180s-DWN: 30s
CLEAD-LAG SETTINGS
LEAD-LAG MODE : AUTO
LEAD-LAG HOURS: 1000h
BC CAP. LIM. SETTINGS
MODE : REMOTE DIG INP.
L1M1 : OFF 2: OFF 3: OFF
L2M1 : OFF 2: OFF 3: OFF
BC CAP. LIM. SETTINGS
L3M1 : OFF 2: OFF 3: OFF
L4M1 : OFF 2: OFF 3: OFF
BC PUMPCONTROL
PUMPLEADTIME : 020s
PUMPLAGTIME : 000s
DAILY ON : Y AT : 00h00
BC SCHEDULE TIMER
ENABLE TIMER : N
ENABLE HOLIDAY PER : N
BC HOLIDAY : 01 TO 03
1 : 00h00 -
2: 00h00 -
3: 00h00 -
BC DUAL EVAP. PUMP
MODE : AUTOM. ROTATION
OFFSET ON RH : 0048h
BC DISPLAY SETTINGS
LANGUAGE : ENGLISH
TIME : 00h00
DATE : 00/01/2001
BC SETPOINT PASSWORD
PASSWORD NEEDED TO
CHANGE SETPOINTS : Y

Operation manual
15 EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Timers menu
Safeties menu
The "safeties" menu provides useful information for trouble shooting
purposes. The following screens contain basic information.
Along with the basic information, more detailed information screens
can be consulted while the safety menu is active. Press the qkey.
Screens similar to the following will appear.
History menu
The "history" menu contains all the information concerning the latest
shutdowns. The structure of those menus is identical to the structure
of the safeties menu. Whenever a failure is solved and the operator
performs a reset, the concerning data from the safeties menu is
copied into the history menu. Warnings are also recorded.
Additionally the number of safeties that already occurred, can be
consulted on the first line of the history screens.
Info menu
Input/output menu
The "input/output" menu gives the status of all the digital inputs and
the relay outputs of the unit.
To enter the service menu. (Only a
qualified installer is allowed to
access this menu.)
To check the actual value of the
general software timers (first screen).
To check the actual value of the
general software timers (second
screen).
To check the actual value of the
compressor timers (first screen).
To check the actual value of the
compressor timers (second screen).
To consult which unit safety caused
the shutdown.
To consult which module 1 safety
caused the shutdown.
To consult which module 2 safety
caused the shutdown.
To consult which module 3 safety
caused the shutdown.
To check the time and control mode
at the moment of the unit shutdown.
To check which were the common
evaporator and condenser inlet water
temperature.
To check which were the evaporator
outlet water temperature of all
modules at the moment of shutdown.
To check which was the status of the
compressors at the moment of
shutdown (first screen).
To check which was the status of the
compressors at the moment of
shutdown (second screen).
BC ENTER SERVICE
PASSWORD : 0000
BX GENERAL TIMERS
LOADUP : 000s - DWN : 000s
PUMPLEAD : 000s
FLOWSTOP : 00s
BC COMPRESSOR TIMERS
COMPR. STARTED : 00s
BC COMPRESSOR TIMERS
C11 GRD : 000s AR : 000s
C12 GRD : 000s AR : 000s
C21 GRD : 000s AR : 000s
BW COMPRESSOR TIMERS
C22 GRD : 000s AR : 000s
C31 GRD : 000s AR : 000s
C32 GRD : 000s AR : 000s
BX UNIT SAFETY
0C9 : INL E SENSOR ERR
BX MODULE 1 SAFETY
1CA : OUT E SENSOR ERR
BX MODULE 2 SAFETY
2CA : OUT E SENSOR ERR
BX MODULE 3 SAFETY
3CA : OUT E SENSOR ERR
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
00h00 - 12/01/2001
MANUAL MODE
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
INL.E : 12.0°C STEP:
INL.C : 30.0°C 0
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
OUTE1 : 07.0°C OUTE3 :
OUTE2 : 07.0°C 07.0°C
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
C11 : ON C21 :
C12 : ON ON
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
C22 : ON
To check which were the total
amount of running hours of the com-
pressors at the moment of shutdown
(first screen).
To check which were the total
amount of running hours of the com-
pressors at the moment of shutdown
(second screen).
To consult time and date information.
To consult additional information
about the unit such as the unit type,
the refrigerant used and the manu-
facturing number.
To consult information about the con-
troller's software version.
To consult information about the
PCB.
To check whether any module
safeties are active.
To check the reverse phase protector
and if there's any waterflow to the
evaporator.
To check the status of the change-
able digital inputs.
To check the status of the compres-
sor relay outputs.
To check the status of the modules
low pressure bypass.
To check the status of the alarm
voltage free contact and the pump/
general operation contact.
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
RH11 : 00000h RH21:
RH12 : 00000h 00000h
BC UNIT HISTORY : 004
0C9 : INL E SENSOR ERR
RH22 : 00000h
BX TIME INFORMATION
TIME : 00h00
DATE : 00/01/2001
BC UNIT INFORMATION
UNITTYPE : WW-HP-32
MANUFACT. NR.: 0000000
REFRIGERANT : R134a
BC UNIT INFORMATION
SW : V1.0M6 (01/11/01)
SW CODE : FLDKNMCH0A
BW PCB INFORMATION
BOOT : V2.02-02/08/00
BIOS : V2.32-31/07/01
BX DIGITAL INPUTS
M1 SAFETY OK
M2 SAFETY OK
M3 SAFETY NOK
BC DIGITAL INPUTS
FLOWSWITCH : FLOW OK
REV.PHASE PR. : OK
BC CHANG. DIG. INPUTS
DI1 DUAL SETP : SETP.1
DI2 REM. ON/OFF : OFF
DI3 REM. C/H : COOL
BC RELAY OUTPUTS
C11 : ON C12 : ON
C21 : ON C22 : ON
C31 : ON C32 : OFF
BC RELAY OUTPUTS
LPBYPASS1 : CLOSED
LPBYPASS2 : CLOSED
LPBYPASS3 : OPEN
BC RELAY OUTPUTS
GEN. ALARM : CLOSED
PUMP/GEN OPER : CLOSED

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
16
User password menu
Cooling/heating menu
Tasks of the user settings menu
Entering the user settings menu
The user settings menu is protected by the user password, a 4-digit
number between 0000 and 9999.
1Enter the USERSETTINGS MENU through the main menu.(Refer to
the chapter "Main menu" on page 14).
The controller will request the password.
2Enter the correct password using the g and h keys.
3Press qto confirm the password and to enter the user settings
menu.
The controller automatically enters the first screen of the user
settings menu.
To define settings of a certain function:
1Go to the appropriate screen of the usersettings menu using the
g and h keys.
2Position the cursor behind the parameter to be modified using
the qkey.
3Select the appropriate setting using the g and h keys.
4Press qto confirm the selection.
When the selection has been confirmed, the cursor switches to
the next parameter which can now be modified.
5Repeat from instruction 2 onwards to modify the other
parameters.
Defining and activating the control mode
The unit is equipped with a thermostat which controls the cooling
capacity of the unit. Two different control modes exist:
■manual control mode: the operator controls the capacity himself
- MANUAL CONTROL
■inlet control mode: uses the evaporator and/or condenser
entering water temperature to control the capacity of the unit -
INLET WATER
When the operator wants to control the capacity himself, he can
activate manual control mode using the CONTROL SETTINGS screen of
the user settings menu. In this case, he has to define the following
parameters:
■MODE (present mode): manual control.
■C11, C12, C21, C22, C31, C32 (compressor status of module 1, 2
and 3 in manual mode or capacity limitation value in case the
"capacity limitation remote contact" is enabled): ON or OFF.
Defining the thermostat settings
When automatic control mode is selected, the unit uses a thermostat
to control the cooling or heating capacity. The maximum number of
thermostat steps are as listed:
However, the thermostat parameters are not fixed and can be
modified via the THERMOST. SETTINGS screen of the user settings menu.
The default, limit and step values for the thermostat parameters are:
Defining the lead-lag mode
The lead/lag mode determines which module starts up first in case of
a capacity demand.
The lead-lag parameters are:
■LEAD-LAG MODE
Automatic: the controller decides whether module 1, module 2,
or module 3 starts up first.
The modules follow the entered order of starting up (see table
below).
■LEAD-LAG HOURS: In the automatic mode, the number of hours
indicated on the display is the maximum difference between the
running hours of the modules. This value is important for main-
tenance purposes. It should be set high enough so that the
modules do not require maintenance at the same time and that
at least one module can remain constantly active.
The lower and upper limits are 100 and 1000 hours respectively.
The default value is 1000 hours.
Defining the pump control settings
The PUMPCONTROL screen of the user settings menu allows the user to
define the pump-leadtime and pump-lagtime.
■PUMPLEADTIME: used to define the time that the pump must run
before the unit can start up.
■PUMPLAGTIME: used to define the time that the pump keeps
running after the unit has been stopped.
Defining the display settings
The DISPLAY SETTINGS screen of the user settings menu allows the
user to define the choice of language, time and date.
■LANGUAGE: used to define the language of the displayed
information of the controller.
■TIME: used to define the present time.
■DATE: used to define the present date.
To check the status of the change-
able relay output.
To change the user password.
To select cooling or heating mode.
NOTE To activate manual control mode, select MANUAL as
present mode. To deactivate the manual control mode,
select INLET WATER as present mode.
BW CHANG. REL OUTPUTS
DO1 REV.VALVE(C/H) : O
BCHANGE PASSWORD
NEW PASSWORD : 0000
CONFIRM : 0000
BCOOLING/HEATING
MODE : COOLING (EVAP)
32Hp 448Hp 464Hp 6
36Hp 452Hp 668Hp 6
40Hp 456Hp 672Hp 6
44Hp 460Hp 6
Lower limit Upper limit Step Default
STPL (°C) 0.4 2.0 0.1 1.5
STEPDIFFERENCE (°C) 0.2 0.8 0.1 0.5
LOADUP (sec) 15 300 1 180
LOADDOWN (sec) 15 300 1 20
NOTE A functional diagram showing the thermostat parame-
ters can be found in "Annex I" on page 21.
3 modules 2 modules
first >next >last first >last
123 12
231 21
312
NOTE If a module is de-activated due to a failure, the next
module will start up instead.

Operation manual
17 EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Defining dual evaporator pump control
The DUAL EVAP. PUMP screen of the user settings menu allows the
user to define the steering of two evaporator pumps (for this to be
possible a changeable digital output has to be configured for a
second evaporator pump in the service menu).
■MODE: used to define which kind of control will be used for the
two evaporator pumps. When automatic rotation is chosen the
offset on running hours also has to be entered.
■OFFSET ON RH: used to define the offset in running hours between
the two pumps. Used to switch over between pumps when they
work in automatic rotation mode.
Defining the schedule timer
The SCHEDULE TIMER screen of the user settings menu allows the user
to define the schedule timer settings.
■MON, TUE, WED, THU, FRI, SAT and SUN: used to define to which
group each day of the week belongs (-/G1/G2/G3/G4).
■For each of the four groups up to nine actions can be set, each
with their respective timing. Actions include: putting the unit on/
off, setting a setpoint, setting cooling/heating and setting
capacity limitation.
■Beside these four groups there is also a holiday period group
which is set the same way as the other groups. Up to 12 holiday
periods can be entered in the HD PERIOD screen. During these
periods the schedule timer will follow the settings of the holiday
period group.
Activating or deactivating the setpoints password
The SETPOINT PASSWORD screen of the user settings menu allows the
user to activate or deactivate the user password needed to change
the temperature setpoint. When deactivated, the user does not have
to enter the password each time he wants to change the setpoint.
Installing BMS address card
The BMSCARD INSTALLED parameter allows the user to control the unit
from a supervisory system.
If the BMSCARD INSTALLED parameter is set to Y(yes), communication
with a supervisory system is possible. The BMSSETTINGS screen and
BMSBOARDSETTINGS screen of the user settings menu are available.
These screens are used to set BMS parameters.
The selection "BMS address card installed" or "not installed", is done
in the service menu (refer to the service manual):
Tasks of the timers menu
Checking the actual value of the software timers
As a protective measure and to ensure correct operation, the
controller's software features several countdown timers:
■LOADUP (LOADUP – refer to the thermostat parameters): starts
counting when a thermostat step change has occurred. During
the countdown, the unit is not able to enter a higher thermostat
step.
■LOADDOWN (DWN – refer to the thermostat parameters): starts
counting when a thermostat step change has occurred. During
the countdown, the unit will not be able to enter a lower thermo-
stat step.
■FLOWSTOP (FLOWSTOP – 5 sec): starts counting when the water
flow through the evaporator stops after the flowstart timer has
reached zero. If the water flow has not restarted during the
countdown, the unit will shut down.
■PUMPLEAD (PUMPLEAD – refer to the pump control settings):
starts counting whenever the unit is switched on. During the
countdown, the unit cannot start up.
■PUMPLAG (PUMPLAG – refer to the pump control settings): starts
counting whenever the unit is switched off. During the count-
down, the pump keeps running.
To check the actual value of the software timers, proceed as follows:
1Enter the TIMERS MENU through the main menu. (Refer to the
chapter "Main menu" on page 14.)
The controller displays the actual value of the GENERAL TIMERS:
the loadup timer, the loaddown timer, the flowstart timer, the
flowstop timer (when the unit is on and the flowstart timer has
reached zero), the pumplead timer and the pumplag timer.
2Press the hkey to check the compressor timers (first screen).
The controller shows the actual value of the COMPRESSOR TIMERS:
the guard timers (one per compressor) and the antirecycling
timers (one per compressor).
3Press the hkey to check the compressor timers (second
screen).
The controller shows the actual value of the COMPRESSOR TIMERS:
the guard timers (one per compressor) and the antirecycling
timers (one per compressor).
Tasks of the safeties menu
Listing activated safeties and checking the unit status
If the alarm buzzer is activated and the user presses the pkey, the
controller automatically enters the safeties menu.
■The controller will enter the UNIT SAFETY screen of the safeties
menu when a unit safety was the cause of shutdown. This
screen provides the following information:
•the activated safety: emergency stop, flow switch, sensor
error or reverse phase
• the unit status at the moment of shutdown
inlet water temperature setpoint of the evaporator,
inlet water temperature setpoint of the condenser,
time and date at the moment of shutdown.
■The controller will enter the MODULE 1, MODULE 2 or MODULE 3
SAFETY screen of the safeties menu when a safety of module 1,
respectively module 2 or module 3 was activated. These
screens provide information about the module status at the
moment of shutdown.
• the activated safety: freeze-up, general safety or sensor error
• the unit status at the moment of shutdown
inlet water temperature setpoint of the evaporator,
inlet water temperature setpoint of the condenser,
time and date at the moment of shutdown.
1Press the pkey when the alarm buzzer is activated.
The appropriate safety screen with the basic information
appears. Press the qkey to see the detailed information.
2If more than one kind of safety is active (indicated by means of
W, Xor C), use the g and h keys to consult them.
NOTE A functional diagram showing the schedule timer
working can be found in "Annex II" on page 22.
NOTE The unit always works with “last command”. This
means that the last command given, whether manually
by the user or by the schedule timer, is always
executed.
Examples of command that can be given are switching
the unit on/off or changing a setpoint.

EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
Operation manual
18
Tasks of the history menu
Checking the safety info and the unit status after a reset
The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the module.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest 10 shutdowns.
To check the safety info and the unit status, proceed as follows:
1Enter the HISTORY MENU through the main menu. (Refer to the
chapter "Main menu" on page 14.)
The controller enters the UNIT HISTORY screen which contains the
following information: the number of shutdowns, the unit safety
which caused the most recent shutdown and the basic
information at the moment of this shutdown.
2Press the g and h keys to consult the M1,M2 or M3 HISTORY
screens.
3Press the qkey to see the detailed information.
Tasks of the info menu
Consulting additional unit information
1Enter the INFO MENU through the main menu. (Refer to the
chapter "Main menu" on page 14).
The controller enters the UNIT INFORMATION screen which contains
the following information: the unit name, the refrigerant used and
the manufacturing (serial) number.
2Press hto consult the next UNIT INFORMATION screen.
This screen contains information about the controller's software
version.
Tasks of the input/output menu
Checking the status of the inputs and outputs
The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.
The locked digital inputs are:
■M1,M2 or M3 SAFETY: indicates the status of the general module
safeties.
■FLOWSWITCH: indicates the status of the flowswitch, activated or
deactivated.
■REVERSE PHASE PROTECTOR: indicates the status of this safety.
The changeable digital inputs are:
■REM. C/H: indicates the status of the remote cooling/heating
switch.
■DUAL SETPOINT: indicates the status of the remote dual setpoint
switch, setpoint 1 or setpoint 2.
■REM. ON/OFF: indicates the status of the remote on/off switch.
■CAP LIM1/2/3: indicates the status of the enable/disable capacity
limitation switch(es).
The locked relay outputs are:
■LPBYPASS 1/2/3: indicates whether the low pressure of the
module is in bypass mode or not.
■C11, C12, C21, C22, C31, C32: indicates whether the compressor is
running or not.
■PUMP/GEN OPER: indicates the status of this voltage free contact.
It is activated if the pump should be ON, which also indicates
general operation.
The changeable relay outputs are:
■REV. VALVE (C/H): indicates whether the unit is running in cooling
or in heating.
■2ND EVAP PUMP: indicates the status of the second evaporator
pump.
■CONDENSER PUMP: indicates the status of the condenser pump.
■100% CAPACITY: indicates when the unit is working at 100%.
To check the inputs and outputs, proceed as follows:
1Enter the I/O STATUS MENU through the main menu. (Refer to the
chapter "Main menu" on page 14.)
The controller enters the first DIGITAL INPUTS screen.
2Consult the other screens of the input/ouput menu using the g
and h keys.
Tasks of the user password menu
Changing the user password
Access to the user settings menu and the setpoints menu is
protected by the user password (a 4-digit number between 0000 and
9999).
To change the user password, proceed as follows:
1Enter the USERPASSWORD MENU through the main menu.(Refer to
the chapter "Main menu" on page 14).
The controller will request the password.
2Enter the correct password using the g and h keys.
3Press qto confirm the password and to enter the password
menu.
The controller requests the new password.
4Press qto start the modification.
The cursor is positioned behind NEW PASSWORD.
5Enter the new password using the g and h keys.
6Press qto confirm the new password.
When the new password has been confirmed, the controller will
ask to enter the new password a second time (for safety
reasons). The cursor is positioned behind CONFIRM.
7Enter the new password again using the g and h keys.
8Press qto confirm the new password.
NOTE The actual password will only be changed when the
new password and the confirmed password have the
same value.

Operation manual
19 EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
TROUBLESHOOTING
This section provides useful information for diagnosing and correct-
ing certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will
save you time and money.
When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no circum-
stances safety devices may be bridged or changed to a value other
than the factory setting. If the cause of the problem cannot be found,
call your local dealer.
Symptom 1:The unit does not start, but the ON LED lights up
Symptom 2:The unit does not start, but the ON LED is flashing
Symptom 3:The unit does not start and the ON LED does not light up
Symptom 4: One of the circuits does not start up
Symptom 5: One of the following safety devices is activated
When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not
correct. Check the controller setpoint.
The flowstart timer is still running. The unit will start after approx. 15
seconds. Make sure that water is
flowing through the evaporator.
Neither one of the circuits can start
up. Refer to Symptom 4: One of the
circuits does not start up.
Unit is in manual mode (all
compressors at 0%). Check on the controller.
Power supply failure. Check the voltage on the supply
panel.
Blown fuse or interrupted protection
device. Inspect fuses and protection
devices. Replace by fuses of the
same size and type (refer to
"Electrical specifications" on
page 2).
Loose connections. Inspect connections of the field
wiring and the internal wiring of the
unit. Tighten all loose connections.
Shorted or broken wires. Test circuits using a tester and repair
if necessary.
POSSIBLE CAUSES CORRECTIVE ACTION
The remote ON/OFF input is
enabled and the remote switch is off. Put the remote switch on or disable
the remote ON/OFF input.
POSSIBLE CAUSES CORRECTIVE ACTION
All circuits are in failure mode. Refer to Symptom 5: One of the
following safety devices is activated.
One of the following safety devices is
activated:
• Flow switch (S8L,S9L)
• Emergency stop
Refer to Symptom 5: One of the
following safety devices is activated.
The ON LED is broken. Contact your local dealer.
The unit is in bypass mode. Check the bypass remote contact.
POSSIBLE CAUSES CORRECTIVE ACTION
One of the following safety devices is
activated:
• Compressor thermal protector (Q*M)
•Overcurrent relay (K*S)
• Discharge thermal protector (S*T)
•Low pressure switch
• High pressure switch (S*HP)
•Reverse phase protector (R*P)
•Freeze-up
Check on the controller and refer to
Symptom 5: One of the following
safety devices is activated.
The anti-recycling timer is still active. The circuit can only start up after
approximately 10 minutes.
The guard timer is still active. The circuit can only start up after
approximately 1 minute.
The circuit is limited to 0%. Check the "enable/disable capacity
limitation" remote contact.
Symptom 5.1: Overcurrent relay of compressor
POSSIBLE CAUSES CORRECTIVE ACTION
Failure of one of the phases. Check fuses on the supply panel or
measure the supply voltage.
Voltage too low. Measure the supply voltage.
Overload of motor. Reset. If the failure persists, call your
local dealer.
RESET
Push the blue button on the over-
current relay inside the switch box
and reset the controller.
Symptom 5.2: Low pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to water heat exchanger
too low. Increase the water flow.
Shortage of refrigerant. Check for leaks and refill refrigerant,
if necessary.
Unit is working out of its operation
range. Check the operation conditions of
the unit.
Inlet temperature to the water heat
exchanger is too low. Increase the inlet water temperature.
Flow switch is not working or no
water flow. Check the flow switch and the water
pump.
RESET
After pressure rise, this safety resets
automatically, but the controller still
needs to be reset.
Symptom 5.3: High-pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to condenser is too low. Increase the water flow and/or check
the strainer for clogging.
RESET
After finding the cause, push the
button on the high-pressure switch
housing and reset the controller.
Symptom 5.4: Reverse phase protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Two phases of the power supply are
connected in the wrong phase
position.
Invert two phases of the power
supply (by licensed electrician).
One phase is not connected
properly. Check the connection of all phases.
RESET
After inverting two phases or fixing
the power supply cables properly,
the protector is reset automatically,
but the controller still needs to be
reset.
Symptom 5.5: Discharge thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Unit is working outside the operation
range. Check the operation condition of the
unit.
RESET
After temperature decrease, the
thermal protector resets
automatically but the controller still
needs to be reset.
Other manuals for EWWP045KAW1M
2
This manual suits for next models
5
Table of contents
Popular Water Dispenser manuals by other brands

Elkay
Elkay 2G Installation, care & use manual

H2oEliteLabs
H2oEliteLabs EWC-MAX-i Operation manual

Rheem
Rheem RHW42 Installation and operation manual

DE VECCHI
DE VECCHI DVA ISI Series instruction manual

Zip
Zip Classic HydroTap G4 range installation instructions

Hague
Hague MAXIMIZER 7180 Owner's manual and installation guide