
InsTallaTIon
www.DaikinApplied.com 11 IM 1137-4 • TEMPLIFIER®MODEL TGZ
The strainer is sized per Table 2. Connection sizes are given in
Dimensions beginning on Figure 17 on page 19.
2. A eld-supplied strainer that meets specication and
installation requirements of this manual on www.DaikinApplied.
com.
Table 2: Evaporator Characteristics
Inlet and outlet connections are clearly marked on the unit and
also appear on the dimension drawings, beginning with Figure
17 on page 19. Drain connections should be provided at all
low points in the system to permit complete drainage. Air vents
should be located at the high points in the system to purge out
air. A vent connection, located on top of the evaporator vessel,
permits the purging of air out of the evaporator. Air purged from
the water system prior to unit start-up provides adequate ow
through the vessel and prevents safety cutouts on the freeze
protection. System pressure should be maintained by using a
properly sized expansion tank.
Pressure gauges should be installed in the inlet and outlet
water lines to the evaporator. Pressure drop through the
evaporator should be measured to calculate proper gpm (L/s)
as specied in the Pressure Drop tables starting with Figure 14
on page 16.
Source water piping may have to be insulated (depending on
its temperature) to reduce heat loss and prevent condensation
if cold water is used. If cooling tower water is used, insulation
may not be necessary. Complete unit and system leak tests
should be performed prior to insulating the water piping.
Insulation with a vapor barrier is recommended. If the vessel is
insulated, the vent and drain connections must extend beyond
the proposed insulation thickness for accessibility. If the unit
operates year-round, or if the system is not drained for the
winter, the chilled water piping exposed to outdoor ambient
should be protected against freezing by wrapping the lines with
a heater cable.
Source/Hot Water Thermostat
The source water temperature sensor is factory installed in the
leaving water connection on the evaporator. The controlling hot
water sensor is in the leaving condenser connection. A sensor
is also located in the entering water connection in order to
measure the condenser Delta-T. Care should be taken not to
damage the sensor cable or lead wires when working around
the unit. It is also advisable to check the lead wire before
running the unit to be sure that it is rmly anchored and not
rubbing on the frame or any other component.
If the sensor is ever removed from the well for servicing,
care must be taken as not to wipe off the heat conducting
compound supplied in the well.
The units can be switched from heating to cooling. In the
cooling mode they are controlled by a thermistor in the leaving
evaporator connection, in the heating mode by the leaving
condenser thermistor.
Flow Switch
A water ow switch must be mounted in the evaporator and
condenser leaving water lines to prove adequate water ow
to the vessels before the unit can start. This will safeguard
against slugging the compressors on startup. It also serves to
shut down the unit in the event that water ow is interrupted to
guard against evaporator freeze-up.
A ow switch is available from Daikin Applied (part #
01750330). It is a “paddle” type switch and adaptable to any
pipe size from 1” (25mm) to 6” (152mm) nominal. Certain
minimum ow rates are required to close the switch and are
listed in Table 3. Installation should be as shown on Figure
9. See Figure 28 on page 31 for terminal locations. The
normally open contacts of the ow switch should be wired
between these two terminals. There is also a set of normally
closed contacts on the switch that could be used for an
indicator light or an alarm to indicate when a “no ow” condition
exists.
NOTE: Install per the vendor instructions and calibrate to a
safe setting based on the application design ow.
1. The ow arrow must be pointed in the correct direction.
2. Provide a straight length of pipe before and after the ow
switch of at least ve times the pipe diameter.
3. Trim ow switch paddle if needed to t the pipe diameter.
Make sure paddle does not hang up in pipe.
CAUTION
Make sure the arrow on the side of the switch is pointed in
the direction of ow. Install per manufacturer’s instructions.
Incorrect installation will cause improper operation and
possible evaporator damage.
Table 3: Flow Switch Minimum Flow Rates
Unit Size 040B-120B 150B-190B
Evaporator Brazed Plate Shell-and tube
Materials Stainless Steel, Copper Carbon Steel, Copper
Max Perf. Size No larger than 0.062” dia. No larger than 0.125” dia.
Cleaning Chemical Chemical
Nominal Pipe Size Inches
(mm)
Minium Req’d Flow to Acve Switch
- GPM (l/s)
2 (50.8) 18.8 (1.2)
2 1/2 (63.5) 24.3 (1.5)
3 (76.2) 30.0 (1.9)
4 (101.6) 39.7 (2.5)
5 (127.0) 58.7 (3.7)
6 (152.4) 79.2 (5.0)