Daintree WWD2-4SM User manual

LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
INSTALLATION INSTRUCTIONS
Page 1 of 7
Rev 03/14/23
DT_WWD2-4SM_InstallSheet
currentlighting.com
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
WWD2-4SM
Installation Guide
Product Overview
.
Prepare Electrical Wiring
¥ When replacing a line voltage switch, the
power must be off at the branch circuit
breaker. Bypass the line voltage switch to
provide uninterrupted power to the fixtures
and make sure the connection is properly
insulated before installing the wireless switch.
The WWD2-4SM wireless dimmer is
a batery powered surace mount wall
switch for use in zonal room control. The
WWD2-4SM device installs onto an ex-
isting junction box to replace an existing
switch or directly on the wall providing a
wireless solution that enables dimming
and ON/OFF commands to be delivered
to luminaires in its commissioned space.
The communication with the luminaires
or wireless controllers utilizes a secure
and reliable wireless connection which
helps minimize installion cost and
complexity.
Electrical Requirements

Page 2 of 7
Rev 03/14/23
DT_WWD2-4SM_InstallSheet
currentlighting.com
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
INSTALLATION INSTRUCTIONS
WWD2-4SM
Installation Guide
�
�
Installation
To reset the network of the device,
remove the faceplate from the device.
Then press and hold the reset button for
5 seconds. Install the faceplate back onto
the device. Press either dimming up or
down button to enter the pairing mode
to join the device to a network.
Network Reset
123
4
Use a standard screwdriver
to open the faceplate. Pull
the plastic insulation strip
out of the battery
compartment.
Install the faceplate onto
the device. Note: Device
supports the use of other
standard faceplates on the
market.
If you
want to install on the
junction box, use the screw
in the package and a cross
screwdriver to lock the
device on the junction box
If you
want to install the device on
the wall, use the 3M tape in
the package to stick the
device firmly on the wall.
You can also use the device
handheld in the signal coverage
area of the commissioned system.
5

Installation Guide
�
Personality Change
12
Button Change
12
Squeeze the clips on the side
of the button module to
remove the button module
from the device.
Press the replacement button
module with the desired
printing onto the device.
3Please contact if you would
like to purchase customized
buttons.
Hold the reset button and
2nd button for 5 seconds to
change the personality to
dual zone mode.
Hold the reset button and 4th
button for 5 seconds to change
the personality to scene mode.
Page 3 of 7
Rev 03/14/23
DT_WWD2-4SM_InstallSheet
currentlighting.com
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
�
LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
INSTALLATION INSTRUCTIONS
WWD2-4SM
Installation Guide
�
�

Page 4 of 7
Rev 03/14/23
DT_WWD2-4SM_InstallSheet
currentlighting.com
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
INSTALLATION INSTRUCTIONS
NXC-WWD2-4SM
Installation Guide
�
Battery Replacement
�
Product Dimensions
123
4
70.00
114.20
32.80
66.50
The device's LED flashing
on for 2 seconds every 30
seconds indicates that the
batteries need to be replaced.
Use a standard screwdriver
to open the faceplate.
Install the faceplate onto
the device.
Separate the battery cover
from the device. Replace
the batteries with AAA
batteries. All batteries need
to be replaced at the same
time.
15.00
15.30

Page 5 of 7
Rev 03/14/23
DT_WWD2-4SM_InstallSheet
currentlighting.com
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
�
LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
INSTALLATION INSTRUCTIONS
WWD2-4SM
Installation Guide
�
LED Indicator
Rapid flash (12 times per second)
for up to 30 seconds
Solid ON for 10 seconds
Flashes once (100ms duration)
Flashes ON 2 seconds every
30 seconds
Device is trying to join a network
Device successfully joined a network
Device has been activated while in the network
Batteries need to be replaced
Forth Button
Short press
First Button
Short press
Second Button
Short press
Third Button
Short press
Four Scene Personality
SCENE 1 turns ON
SCENE 2 turns ON
SCENE 3 turns ON
SCENE 4 turns ON
Product Operation
Button Functionality
Forth Button
Short press
Double short press
Hold
First Button
Short press
Double short press
Hold
Second Button
Short press
Double short press
Hold
Third Button
Short press
Double short press
Hold
Dual Zone Personality Four Scene Personality
Zone 1 lights ON at previous level
Zone 1 lights ON at 100% output
Turn Zone 1 ON and dim up
Zone 2 lights ON at previous level
Zone 2 lights ON at 100% output
Turn Zone 2 ON and dim up
Zone 1 lights OFF
Zone 1 lights ON at minimum dimming level
Turn Zone 1 ON and dim down or dim down
if lights are already ON
Zone 2 lights OFF
Zone 2 lights ON at minimum dimming level
Turn Zone 2 ON and dim down or dim down
if lights are already ON
SCENE 1 turns ON
SCENE 2 turns ON
SCENE 3 turns ON
SCENE 4 turns ON

Page 6 of 7
Rev 03/14/23
DT_WWD2-4SM_InstallSheet
currentlighting.com
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
INSTALLATION INSTRUCTIONS
WWD2-4SM
Installation Guide
�
Technical Data
Product Specifications
DESCRIPTIONA RTICLE NO
WWD2-4SM
Product Availablity
Wireless Wall Switch, Surface Mount, 4 Button, Battery
The alkaline batteries supplied with your wireless switch are prone to leak over their lifetime, particularly when the battery
is mostly depleted. In the event that your battery leaks alkaline into the battery compartment, the chemicals can damage
the metal terminals.The chances of this happening can be reduced by changing the batteries in the switch promptly when
the batteries are nearing their end of their useful life. If a battery leak should occur, however, it should be cleaned up to
prevent damage to the wireless switch.
WARNING: THE CHEMICALS LEAKED FROM ALKALINE BATTERIES ARE CORROSIVE. WHEN HANDLING LEAKING BATTERIES,
PROPER PERSONAL SAFETY EQUIPMENT SHOULD BE USED, INCLUDING RUBBER GLOVES AND EYE PROTECTION.
If it is discovered that the batteries have leaked, wearing rubber gloves and using eye protection, remove all of the batteries
from the battery compartment and seal them in a plastic bag. The bag should be discarded in a manner in accordance with
local laws and regulations. Then, using a small cloth lightly moistened with vinegar or other mild acid, carefully wipe all of
the leaked battery chemicals from inside the battery compartment and allow it to dry. Once dry, the batteries may be
replaced and the switch may be reinstalled.
SIMPLIFIED EU DECLARATION OF CONFORMITY:
Hereby, Current Lighting Solutions, LLC declares that the radio equipment type WWD2-4SM is in compliance with Directive
2014/53/EU.
The full text of the EU declaration of conformity is available at the following internet address: www.gecurrent.com
114mm H x 70mm W x 15mm D
130g
(4) AAA1.5V battery
5yr(normal operation)
-10¡C to 40¡C (Indoor Use Only)
Network joined/Button triggered
Surface mount with either screw hole in backplate or with included 3M tape
5 years
Operating Control
Independently Mounted
Dimensions
Weight
Power Supply
Battery Life
Operating Environment
Status Indicator
Mounting
Warranty
Purpose of Control
Construction of Control
Type 1 Action
Pollution Degree 2
Product Certifications and Regulatory Marks
FCC ID: 2AS3F-WWD4SM
IC : 25008-WWD4SM
Operating Control
E486320
Frequency band of radio operation: 2405-2480 MHz
Maximum radio transmit power: 8 dBm
A

72-00187, Rev. D
LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
INSTALLATION INSTRUCTIONS
Page 7 of 7
Rev 03/14/23
DT_WWD2-4SM_InstallSheet
currentlighting.com
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
LightOWL®Dual Technology Passive Infrared
and Acoustic Sensors (LODIA)
WWD2-4SM
Installation Guide
Product Name: Wireless Wall Dimmer
Supplier's Declaration of Conformity
47 CFR ¤ 2.1077 Compliance Information
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2)t his device must accept any interference received, including interference that may cause undesired operation.
This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic
Development CanadaÕs license-exempt RSS(s). Operation is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference including interference that may cause undesired operation of the device.
FCC RF Radiation Exposure Statement: Specific Absorption Rate (SAR) is a measure of the rate of RF (radiofrequency)
energy absorption by the body from the source being measured. This equipment has been subject to the FCC RF Exposure
SAR Evaluation and this equipment complies with the FCC RF exposure limits set forth for the general population with
uncontrolled exposure. These requirements set a SAR limit of 1.6W/kg averaged over one gram of tissue.
Caution: The user is cautioned that changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part
residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference
to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
ÑReorient or relocate the receiving antenna.
ÑIncrease the separation between the equipment and receiver.
ÑConnect the equipment into an outlet on a circuit different from that to which the receiver is connected.
ÑConsult the dealer or an experienced radio/ TV technician for help
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
-
-
-
-
Model No: WWD2-4SM
Supplier’s Name: Current Lighting Solutions, LLC
Supplier’s Website: http://www.gecurrent.com
Supplier’s Address (USA): 25825 Science Park, STE 400, Beachwood, OH 44122
Supplier’s Phone: 1-866-855-8629
L’émetteur/récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d’Innovation, Sciences et
Développement économique Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux
deux conditions suivantes:
(1) L’appareil ne doit pas produire de brouillage;
(2) L’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le
fonctionnement.
Table of contents
Other Daintree Control System manuals
Popular Control System manuals by other brands

BWO
BWO CONTROL SYSTEM 900 Hardware installation

Zonex
Zonex GEN II -VVT Installation and application manual

heat-timer
heat-timer DHW Energy Saver Installation and operation manual

Unique Automation
Unique Automation Bathomatic Basic MK3 user guide

Altronics
Altronics PowerQuest quick start guide

Security Brands
Security Brands SECUREPASS CR1 40-100 install guide