8 | AQ450740142615en-000201 © Danfoss | Climate Solutions | 2023.07
3|Areas of application
ATTENTION Compressor operation is possible within the operating limits.
These can be found in Bock compressor selection tool (VAP)
under vap.bock.de. Observe the information given there.
- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature 140°C.
-Max.permissibleswitchingfrequency12x/h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with supplementary cooling:
- Use only oils with high thermal stability.
- Avoid continuous operation near the threshold.
- Additional fans (accessories) can be used for additional cooling.
For operation with capacity regulator:
-
Continuous operation, when the capacity regulator is activated,
is not permissible and can cause damage to the compressor.
- The suction gas superheat temperature may need to be reduced
or set individually when operating near to the threshold.
- When the capacity regulator is activated, the gas velocity in the
systemcannotundercertaincircumstancesensurethatsuf-
cient oil is transported back to the compressor.
Foroperationwithfrequencyconverter:
- The maximum current and power consumption must not be
exceeded.Inthecaseofoperationabovethemainsfrequency,
the application limit can therefore be limited. Max. 60 Hz.
(Formoreonthefrequencyconverter,seechapter5.10,p.24)
When operating in the vacuum range, there is a danger of air
entering on the suction side. This can cause chemical reactions,
a pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!
3.3 Limits of application
3.1 Refrigerants
• HFKW / HFC: R134a, R404A/R507, R407C, R407F • (H)FCKW / (H)CFC: R22
3.2 Oil charge
INFO For refilling, we recommend the above oil types.
Alternatives: see lubricants table, Chapter 7.4
ATTENTION The oil level must be in the
visible part of the sight glass;
damage to the compressor is
possible if overfilled or under-
filled!
Max.
Min.
1,9 Ltr.
Oil level
Fig. 3
~
~
Thecompressorsarelledatthefactorywiththefollowingoiltype:
- for R134a, R404A/R507, R407C BOCK lub E55
- for R22 BOCK lub A46
Compressors with ester oil charge (BOCK lub E55) are marked with an X in the type designation
(e.g. HGX66e/2070-4).