Error list
If any failure happens at the cooling mode an error code will show in the display. The error - Exx and the
corresponding corrective action can be found in the table below.
Display error No. Error description What to do
E01
The supply voltage is higher than the pre-set
60VDC, and the Controller stop the unit.
Check the rectier and adjust the supply
voltage to below VDC and the unit start up
automatically.
E02
The supply voltage is lower than the pre-set
40VDC, and the Controller stop the unit.
Check the batteries and rectier and rose the
supply voltage to over VDC and the unit start
up automatically.
E03
The actual Amps are higher than the pre-set
30A and the Controller stops the unit.
The cooling unit is out of normally operation
conditions, the unit will starts up again
automatically when compressor restart time
out has expired. (90 sec)
E04
The actual amps are lower than the pre-set 1A. The cooling unit is out of normal operation
conditions. An alarm can be given if
congured.
E05
The room temperature is higher than the
preset 40°C or lower than the preset 0°C.
The unit will continue running.
This is a temperature warning that tells the
room temperature is far away from the cooling
setpoint.
E06 Internal Fans have failure and have stopped or
they are not working properly.
Check the internal fans, and replace them if
necessary.
E07 The Condenser Fan has failure and has
stopped or it is not working properly.
Check the Condenser fan, and replace if
necessary.
E08 The compressor motor has failure and is
stopped or not working properly.
Check the electric circuit, check the
compressor connections.
E09
The room temperature sensor mounted at
the indoor unit has fail and are not working
properly.
At the indoor unit, check the room
temperature sensor, either shortcut or a
missing connection.
E13
The temperature sensor mounted at the
condenser coil has failed and is not working
properly.
At the outdoor unit, check the temperature
sensor at the Condenser coil, either shortcut or
a missing connection.
E14 Digital input 1 active. Depending of what the Customer have
connected to digital input 1.
E15 Digital input 2 active. Depending of what the Customer have
connected to digital input 2.
E16
The cooling system have high pressure more
than 28barg the unit short down in order to
protect the unit. If more than 6 times,HP failure
within 1 hour, compressor will be locked.
Needs restart of unit.
Lack of air ow due to clogged condenser/oil
or airways at outdoor unit. Check the airways
and the condenser Coil, and clean them. The
cooling unit start up automatically when
pressure is equalized.
E17
The electronic located at the top of the
outdoor unit is hot, and the Cooling unit close
down to protect the unit.
Lack of air ow due to clogged condenser/coil
or airways at outdoor unit. Check the airways
and the condenser Coil, and clean them. The
unit will start up again automatically when the
electronics is cooled down.
E18
The compressor is too warm and the thermal
cut o stop the compressor.
This happens only in extreme conditions
where the outdoor temperature is above 55°C.
The unit will start up again automatically when
the compressor is cooled down and restart
time out has expired.
E19
The low pressure switch stops the cooling unit
in order to protect the compressor.
Can happen in low outdoor temperature
below -15°C and or lack of refrigerant in the
cooling system, rechargeR134a to the cooling
system, The cooling unit start up automatically
when pressure is equalized.