DASS Tech saleaf DSP-3315i-ODS Instruction manual

DASSTECH Solar Photovoltaic
DSP-3315i-ODS
Version 1.1
www.dasstech.com
Customer Ser vice Center
Main Phone of Headquarter
(FAX)
E-mail
The specifications of the product are subject to change without notice due to quality improvement, etc.
Headquarter: 109, Yangcheongsongdae-gil, Ochang-eup, Cheongwon-gu, Cheongju-si, Chungcheongbuk-do,
28118, Republic of Korea (in Science Park of Ochgang)
http://www.dasstech.com
Ver 1.1
Manual for Use and Installation
DASS Tech Co., Ltd.
1588-7468
043-218-5670
043-218-5671
webmaster@dasstech.com

DSP 3315i-ODS
Danger indicates a hazardous situation which, if not avoided, willresult
in death or serious injury.
Warning indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
Caution indicates a hazardous situation, if not avoided, could result in
minor or moderate injury.
Attention indicates there are potential risks. If fail to prevent, may lead
to equipment cannot run normally or property damage.
It also can be some tips to use this product, it can help you to solve some
problems and save you time.
Danger
Warning
Caution
Attention
Note
Notice
The product , service and features that you purchased are bound by DASS TECH's commercial
contract and terms,The product, service and features(or part of them) described in this
document may not be in your purchase or usage range. DASS TECH does not declare or
guarantee any content in this document except there are other contractual stipulation.
Save these instructions!
This manual must be considered as an integral part of the equipment, and must be available
at all times to everyone who interacts with the equipment. The manual must always
accompany the equipment, even when it is transferred to another user or field.
Copyright Declaration
The copyright of this manual belongs to DASS Tech Co., Ltd Any corporation or
individual should not plagiarize, partially copy or fully copy it (including software, etc.),
and no reproduction or distribution of it in any form or by any means. All rights
reserved. DASS TECH reserves the right of final interpretation. This manual is subject to
change according to user’s or customer’s feedback.
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

DASS TECH inverter
6
7
8
7
10
13
14
14
15
17
21
24
26
27
27
27
28
28
29
31
43
43
47
48
48
48
48
48
49
49
50
50
51
52
10.1 Standard warranty period
10.2 Extended warranty period
10.3 Invalid warranty clause
52
52
52
DRMs Functions
Symbols
Safety instructions and warnings 2
Protection units
Interface and Dimensions
3
4
3
Packing Materials
Intended grid types
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

1.1 Symbols
DASS TECH inverter has some safety related symbol, please make sure you have read and
understand these symbol content before you install this equipotent.
IP65
there is residual voltage
danger in inverter.
Symbol Symbol name Meaning
After turning off inverter DC switch , there is
voltage in the inverter capacitor within some
time, we suggest you start to open the inverter
for maintenance 5 minutes later after you
turning off DC switch.
High voltage , electric
shock hazard.
There is high voltage during inverter
running , all the operations should be done
by quantifie d professional e lectrical
person.
H i g h t e m p e r a t e o n
inverter enclosure
Burn Hazard.
High temperature in inverter enclosure
when it is running,do not touch.
C E c e r t i f i c a t e : t h i s
inve r ter i s comp i l abl e
w i t h C E c e r t i f i c a t e
standard.
This inverter is compilable with CE
certificate standard.
PE connection symbol. Connect inverter with earth terminal for
protection.
Temperature sysbol. Inverter working temperature range.
Ingress protection symbol. This product has IP65.
Elect rical posit ive an d
negative.
Be care of electrical polarity.
1.2 Safety instructions and warnings
Operator must follow bellowing safety instructions when he installs DASS TECH inverter
,incorrect operation may cause property loss, equipments damage or personal injury.
1. Inverter can be installed only by professional electrician or electrical engineer according to
local standard and regulations. Only after getting permission from local power department,
inverter can be connected on grid.
2. DC and AC switch must be turned off when installing and maintaining inverter. Can not
touch inverter metal part with 5 minutes after inverter turning off.
3. Some part of inverter may be higher than 60 degree when it is running, please do not
touch its metal part to avoid burn injury.
4. It is forbidden to plug off DC or AC connector when inverter is in generation.
5. Please do not open the inverter upper case, touch or remove inside components ,it may
cause inverter damage or personal injury.
6. DASS TECH inverter are transformer-less no-isolated inverter , the PV modules connected
with DASS TECH inverter should be compatible with IEC 61730 Class A.
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

2.1 Intended grid types
DASS TECH inverter
DASS TECH inverter DASS TECH inverter DASS TECH inverter DASS TECH inverter
DASS TECH inverter
1, DC Switch
2, Vent valve
3-6, DC connector (DCV C)
7, WIFI/GPRS (DCV A)
8, DRM0 (DCV A)
9, DRM5~8 & External digital inputs (DCV A)
10-11, RS485 (DCV A)
12, AC output connector (DCV C)
2.2 Interface and Dimensions
34
1 2 3 4 5 6 7 8 9 10 11 12
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

1, Inverter front 2, Inverer side 3, Inverter back 4, Installation rack
2.3 Protection units
A. RCMU
When inverter'e leakage current exceeds safety requirement, inverter will stop generation
B. Grid abnormal protection
When inverter detects the grid or voltage is out of range , inverter will stop generation.
Inverter will restart to generation automatically when the grid is normal again
C. Ground fault detecting
When ground fault happen , inverter will stop generation automatically and the GFI red LED
will be on to inform customer.
D. Over temperature de-rating
When temperature is higher than internal setting ,inverter will derate the power
automatically
E. Over voltage de-rating
WHen MPPT point is higher then 850V , inverter will derate the power automatically
F. Over current protection
When inverter is abnormal, overter current protection can protect inverter from damange
G. Reverse connection protection
56
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

DASS TECH inverter
3PCS
3PCS
3PCS
3PCS
3PCS
6PCS
78
M6
DASS TECH inverter.
DASS TECH inverter
3-2
3.1 Packing Materials
3.2 Tools
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

2.0
5.0
Diameter 2.0mm
Diameter 5.0mm
DASS TECH inverter
DASS TECH inverter.
Installation position requirements
1.It should be easy to cut off the power supply
2.The wall should have enough strength to
support inverter
3.Can not be touched by child
3.3
910
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

Figure 3-3 Many DASS TECH inverter installation
11 12
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

Figure 3-4
13 14
3.4 Installing the DASS TECH inverter
1, Mart and drilling hole 2, Insert expansion blots 3, install rack 4, put on inverter
5, Install fix screw 6, Lock the inverter(if nessary)
1. Make sure the inverter DC switch is in OFF status
2.Check if the grid voltage and frequency are in correct range
3.If the PV panel is thin-film panel , a transformer(1.25 times as inverter capacity) should be
added at AC side
4.PE cable should be thicker than 4mm and reliable,
M6 Screws
OT Terminal (Screw diameter : 6mm)
M6 Threaded hole
4.1
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

15 16
30~50mm
3~5mm
DSP 3315i-ODS
4-6
32A
Cable and breaker selection
Model
For safety requirement, please use the quantified cable , or it may cause
cavle over heat even fire
The leakage current of breaker should be higher than 100mA and lower
than 300mA
Note
DSP 3315i-ODS
34
Cross area
( )
Maximum cable length (m)
6
420
DASS TECH inverter is three phase output inverter, it complies with related on-grid standard
and safety requirements.
AC cable installation steps
A. part cable length 30-50mm
B. part cable length 3-5mm
Isolation cover and terminals
can not be exposed
water-proff cover A
Crimp each core cable to OT terminal(KST, RNBL5-4 is recommended), after fixing , use
isolation tape to cover exposed part of OT(except O part).
Connect OT terminal to AC connector according to the painting then fix the water-proof cover.
4.2
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

DASS TECH inverter
DASS TECH inverter
DASS TECH inverter.
4-6
4-7
4-8
4-9
17 18
4.3
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

TERMINAL
TERMINAL
DASS TECH inverter
DASS TECH inverter
TERMINAL
DASS TECH inverter
DASS TECH inverter
DASS TECH inverter
TERMINAL
TERMINAL
DASS TECH inverter
DASS TECH inverter
4-10
4-11
4-12
19 20
The distance between WIFI and Ethernet router should be less than 100m.
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

TECH inverter
4-3
4-13
4-13 4-15
4-14
4-15
4-16
21 22
4.4
DASS
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

DASS TECH inverter
DASS TECH inverter
4-16
4-17
4-17
4-17 4-18
4-18
23 24
4.5 DRMs Functions
4.5.1 DASS TECH inverter have five TTL input and one 5V Power output witch provided the
DRMs function. The Ports are RG/0,CL/0, DRM1/5, DRM2/6, DRM3/7, DRM4/8, and GND
,5V,as shown below :
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

25 26
1. Check the string polarity
2. Make sure the DC switch is OFF,connect the sting to inverter DC side accordingly
3.The string voltage can not be higher than 1000V
4. Check if the connector is fixed well and correctly
5. Check if the PE connection cable and screw is fixed well , check if the communication is
connected well(if needed)
6. Check string connection type , if one string is connected to inverter two MPPT, set inverter
mode as parallel mode(default is independent mode)
7. Switch on DC switch first ,check if the LCD turned on normally , then turn ON AC switch ,
inverter should generate power normally, if any abnormal sound, turn off the AC and DC
switch. If there is alarm on the inverter , check the manual for trouble shooting.
4.5.2 PINs Physical Function Discription:
The DRMs function allocation is shown in below Table:
4.5.3 Enable the DRMs function.
1. Connected the cables as shown below ;
2. Provided the DC Power through the PV Pannel until the LCD is working;
3. Set inverter country code as 02(Australia) in Enter Setting>Set Country Code(password 0001);
4. Enable DRMs function in Enter Setting>DRMs Control(password 0001);
5. Only DRM0, DRM5, DRM6, DRM7, DRM8 has been defined. Inverter will works as DRM0,
DRM5, DRM6, DRM7, DRM8 when Corresponding switch closure. Their priority is
DRM0>DRM5>DRM6>DRM7>DRM8.
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

27 28
Step 1 Turn on DC switch.
Step 2 Turn on AC switch.
When the solar arrays generate adequate power, the inverter will startup automatically.
Display showing “normal” indicates correct operation.
Step 3: Choose the correct country code. (refer to section 6.3 of this manual)
Notice: Different distribution network operators in different countries have
different requirements regarding grid connections of PV grid connected
inverters.
Therefore, it's very important to make sure that you have selected the correct
country code according to requirements of local authority.
Please consult qualified electrical engineer or personnel from electrical safety
authorities about this.
DASS Tech Co., Ltd is not responsible for any consequences arising out of
incorrect country code selection.
If the inverter indicates any other fault, please refer to part 7——error messages for help.
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

160V
180V
29 30
remote off
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

Clear Energy
Enset Country
Set Energy
Set Address
Set Inputmode
Set Language
Set StartPara
Set SafetyVolt
Set SafetyFreq
Set Insulation
Set Reactive
Set PowerDerat
17. PE Linecontrol
18. Set RefluxP
19. DRMS0 Control
31 32
20. Set PowerRatio
21. Autotest Fast
On-Off Control
22. Autotest STD
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual

Clear Energy
Clear Energy
Enset Country
7 . Set Energy
6. Enset Country
Set Energy
8
In
9
DASS TECH inverter
6 . Enset Country
33 34
and rekey in the correct passwords.It will enter into ''Power on&Power off'' interface if the
passwords is correct,then you can select ''Power on'' or ''Power off'' by pressing ''Up''
button or ''Down'' button and press ''OK'' button to finish the setting successfully.If you
select ''Power off'',need to set how many days you want the inverter to power off,increase
or decrease value though pressing ''Up'' button or ''Down'' button.After you set ''Power off''
successfully,you need to contact manufacturer to supply passwords to re-power on this
inverter.
On-Off Control
Users press ''Back'' button to enter ''1.Enter Setting'' interface,Press ''OK'' button to enter
main setting interface.Enter ''5.On-Off Control'' by pressing ''UP'' button or ''Down'' button.
Press ''OK'' button and enter On-Off Control interface,press ''OK'' button and enter ''Input
Password'' Setting interface.Press ''OK'' button to set passwords (default:0001),increase or
decrease value though pressing ''Up'' button or ''Dwon'' button,press ''OK'' button to next
value setting.''Error! Try again'' will be displayed for wrong passwords.Press ''back'' button
User can check current country code in SystemInfo>>5. Country.
Note: Country code changing will take effect after inverter reboot.
(default:0001)
33 Ukraine
34-49
DSP 3315i-ODS
User manual
DSP 3315i-ODS
User manual