Deekax TALTERI DIVK-C 60 CD User manual

TALTERI
DEEKAX Air Oy
Patruunapolku 4 Puh. 0207 912550
79100 LEPPÄVIRTA www.deekaxair.fi
R
AIR EXCHANGE EQUIPMENT
INSTALLATION AND USER
MANUAL
THE QUALITY GOALS OF AIR CONDITIONING COME TRUE
WITH THE RECOVERY SYSTEM
TALTERI removes used air from interior and brings in fresh air.
Humidity and impurities are exhausted through thermal recovery
unit that heats the filtered ambient air cost-effectively. The fresh
warm air is channelled draught-free and noise-free into the
premises in necessary quantities.
ENSURE THE QUALITY OF AIR EXCHANGE!
DIVK-C 60 CD
QUALITY TESTED

SYSTEM COMPONENTS
Picture 1
1 Air exchange unit......DIVK-C60 CD
2 Control hood.....e.g. .DX-ULTRA- PG EC
3 Exhaust air outlets..
4 Channel noise deductor...... Ø 125
5 Exhaust air for the system....... Ø 125
6 Outdoor air for the system...... Ø 125
7 Interior air supplies............
Ø
125
pictured right handed (R)
Picture 1
****
utility room
washroom
clothing
room
bed room
living
room
OUTDOOR AIREXTRACT AIR
kitchen
SUPPLY AIR
1
2
3
56
7
4
DIVK
EQUIPMENT DETAILS AND TECHNICAL DATA
1 Exhaust air out.............. 125 mm
2 Outdoor air for the system ..... 125 mm
3 Exhaust air for the system...... 125 mm
4 Interior air supply........ 125 mm
6 Door switch
7 Supply fan, adjustable.. 118W
8 Exhaust fan, adjustable.... .118W
9 Heat exchanger
10 Afterheater,adjustable, 500w
11 Preheater, adjustable, 500w
12 Extract air filter (G4) ISO Coarse>75%
13 Suply air filter (F7) ISO ePM1
14 Exhaust of condensing water
16 Manual overheat protection of the preheater
17 Manual overheat protection of the afterheater
1
8
Summer bypass appliance
2
In the picture is shown right handed (R) unit
Talteri heat recovery system
1 EXHAUST AIR
2 OUTDOOR AIR
3 EXTRACT AIR
4 SUPPLY AIR
DUCT OUTLETS
HANDEDNESS RIGHT
4 EXHAUST AIR
3 OUTDOOR AIR FOR
2 EXTRACT AIR
1 SUPPLY AIR
5 ELECTRIC WIRING
DUCT OUTLETS
HANDEDNESS LEFT
l/s
Pa
200
100
40 60
Extract air
Supply
20
Air flow
External ductwork pressure
100%
80 %
60 %
40 %
Fan speed % 40 50 60 70 80 90 100
Fan power W 16 21 34 52 77 116 152
Sound pressure level LpA
in the room 10m2 absortion dB(A)
20 24 28 33 36 40 43
Hz E S E S E S E S E S E S E S
63 35 46 42 53 47 57 51 59 55 65 57 67 59 68
125 32 42 37 49 43 53 47 56 50 61 53 64 56 66
250 35 39 41 47 46 52 51 57 54 61 57 64 60 67
500 22 42 31 47 32 54 35 60 39 65 43 68 46 71
1000 28 40 34 47 39 52 41 58 44 62 46 64 49 66
2000 6 35 14 43 20 51 24 58 28 62 31 65 33 68
4000 * 25 5 36 12 45 17 52 22 57 25 61 29 65
8000 * 10 * 23 4 35 9 45 14 52 18 56 21 60
Total power level L
wa
29 42
35 49
40 56
43 63
46 67
49 70
51 73
weighted
sound
pressure
levels for
exhaust(E)
and supply(S)
channels at
different
octave levels
EXHAUST AIR
OVEN
DIMENSIONS: height 645 mm, widht 598 mm,
depth 335 mm, weight 52 Kg
78
9
6
10
17
11
12
13
14
16
18

TALTERI DIVK-C 60 INSTALLATION
The air exchange unit is meant for warm inner facilities. Suitable installation spots are,
among others, office, dressing or household facilities and technical or warm storages. In case
the temperature of the installation location is lower than ro om temperature, the factory settings
of the appliance must be changed to obtain faultless functioning. The unit can not be installed
into cold outer premises or garages.
UPPER BASE DUCT
The channelling is usually mounted to the upper base thermal insulation.
The steam barrier puncture must be carefully sealed.
CONDENSATE
Condensate drain is connected to the machine condensate connector (3/8 "external thread).
Condensate can be made at a least 10 mm in the bore copper pipe or Relatively stiff hose.
The water pipe Making about 10 cm in the water trap and the tube is connected
to a floor drain. The water line shouldnt be connected directly to the sewer.
WALL MOUNTING
The wall mounting kit includes a ceiling mounting plate, a wall mounting
plate and 15mm thick insulation pieces. The roof mounting plate is
attached to the machine and the insulation pieces are glued to the rear wall
and bottom of the machine.
The wall mounting plate is installed about 25 mm below the ceiling
surface.The wall mounting plate will be fixed to the wall and then the unit
lifted upto the mounting plate and the horizontal plane of the machine is
checked.
Ceiling
moldings can be put around the machine.
3
170
170
43 200 200 43
20
90
130
485
6kpl D=6,5mm
TALTERI
DOOR
120
135
WALL BRACKET
Condensate connector
left (L)
Condensate connector
right (R)

WASHER
BOLT M8X40
SERVICE HATCH
4
The ceiling-mounting plate is attached
to the roof with M8, thread bars (not included in the
delivery).
RUBBER SILENCER
WASHER
NUT
5mm
40-50
mm
The head of the threaded bar can not
reach below the bottom of the plate.
The unit will be pushed to the mounting plate and
tightened with four M8 bolts against the mounting plate
so that the cover seal of the unit is evenly sealed against
the m
ounti
ng plate
, not tighter.
MOUNTING PLATE BINDING
UPPER SURFACE IS
INSTALLED 5 mm
BELOW THE ROOF SURFACE
LEAVE A 40-50MM GAP
BETWEEN THE CEILING AND
THE FRONT EDGE OF THE
MOUNTING PLATE
SERVICE HATCH
M8 THREADED BAR
BACKUP NUT
THE UNIT IS PULLED
INTO THE MOUNTING
PLATE “RAILS”
MEASURES OF THE MOUNTING PLATE
SERVICE HATCH
THE UNIT IS ATTACHED
TO THE MOUNTING
PLATE FROM THE INSIDE
BY FOUR M8 BOLTS
1 EXHAUST AIR
2 OUTDOOR AIR
3 EXTRACT AIR
4 SUPPLY AIR
DUCT OUTLETS
HANDEDNESS RIGHT
4 EXHAUST AIR
3 OUTDOOR AIR FOR
2 EXTRACT AIR
1 SUPPLY AIR
5 ELECTRICAL WIRING
DUCT OUTLETS
HANDEDNESS LEFT
Front edge
DIVK
-
C
60
INSTALLATION TO A SUSPENDED CEILING

ELECTRICAL CONNECTIONS
Electrical connections must be done following the installation manual
and wiring diagram.
ELECTRICAL CONNECTIONS CAN BE DONE ONLY BY
AN ENTREPRENEUR WITH RESPECTIVE INSTALLATION RIGHTS.
5
VAK
Alarm and operation
indication
max 24 V
as contact tip information
from the unit
0-10V
GND
24V
CO2
trans-
mitter
VAK
0
0-10V
KITCHEN HOOD
0-10v control
0
0-10V
PC EC
PG EC
DS EC
DSA EC
Input
-power cord
230V,
50 Hz
10 A
NO
NC
0-10V
GND
24V
RH
trans-
mitter
-
+
MODBUS
GND
D+/ A
D- / B
Out-of-home
switch
Pulse
switch
switch
Under pressure
compensation
set value 0 as
contact tip infor-
mation
Fireplace
Overpressure
KITCHEN HOOD
boosting with
contact tip information
NO
COM
NC
open
closed
Pulse
switch
Boost
switch
switch
set value 0
as contact tip
information
Boost
switch
Extended time
Cooling
radiator
actuator
DC 24 V
0-10v
set value 0
as contact tip
information
Internal connection of the HRV unit
Input,
-power cord
230V,
50 Hz
10 A
RJ12 2,5 m AHU
To control panel
Input
230V,
50 Hz
10 A
-power
cord
(plug)
(
Pulse
switch
Input
-power
cord 2 m
(plug)
connection box
cable 1 m
External connections of the HRV unit are connected to the connection
box located on the top the unit.
The unit is equipped with a power plug.
The unit is set up and the setvalue changes are made via a separate AHU
control panel. The control panel is connected to the cable above the unit
with the RJ12 connector.
The following can be connected as
accessories:
- Carbon dioxide transmitter;
- Humidity transmitter;
- Separate Overpressure or Extended
time
switch (pulse switch);
- Separate Boost switch (pulse switch);
or setting off as pre-data (for instance,
sauna oven, stove hood);
- Remote control or out-of-home switches
(pre-data);
- Differential pressure switches for filters;
- External speed control 0-10V.
- Modbus.
The functions can be operated through
maintenance and setup menus of the
operating panel
.

6
C 60 CD
KS KS
T1 T2 T3 T4 T5 T6
230VAC
L N PE
+24 0 0-10
CO2/%RH1
+24 00-10
CO2/%RH2
0-10
+24 0 0-10 +24 0+24 0
YHT
NC
YHT
NO
R
0-10 0-100 0
N NU U
N3 21
K
S
N3 2 1
KS
N3 2 1
K
S
N3 2 1
K
S
N
4
L
1
L
2
N
3
L
N
E
J
MODBUS
A/D+
B/D-
0
O O O
O O O
O O O
ON OFF BIAS B
ON OFF Term
ON OFF BIAS A
1
-
2
+
3
+
Belimo CH 24 L
50c 90c
500W
50c 90c
500W
1 N
1N
LN
RJ12 3 m to AHU control panel
Black
Violet
Gr-Pi
R-bl
Wh-gr
Grey
Yellow
Green
Brown
White
Br-gr
Ye-br
Wh-ye
Red
Blue
Pink
0-10
0
+24
Input
230V,
50 Hz
10 A
-power
cord
(plug)
( IU )
POST-
HEATTER
PRE-
HEATER
Coupler
female 1934516
white.
Coupler
male 1934512
white.
Supply air
fan
Extract air
fan
TRIAC
PreH.
TRIAC
PostH.
FUSE
SUPP LY / E XTRA CT
EXTR ACT SU PPLY
CIRCUIT BOARD
ECU_M
CONTROLL
PANEL
POST-
HEATER
PRE-
HEATER
ALARM
HEAT EXHANGER
BYPASS
SUMMER
WINTER
TEMPERATURE SENSORS
OUTD OOR SU PPLY E XTRACT EXHAU ST WAT ER
OVERPRESSURE
/EXTENDED TIME
BOOSTING
OUT-OF-HOUSE/
REMOTE
FIL TER
COOLING WATER
RADIATOR
SUMMER BYPASS
DOOR SWITCH
Humidity trans-
mitter
Optional

INTRODUCTION OF THE AIR EXCHANGE
SYSTEM
BEFORE OPERATING YOUR AIR EXCHANGE SYSTEM,
MAKE SURE THAT:
- There are no loose objects within the unit or the air impeller;
- The coverings of construction-time are removed from
the outlet- and exhaust air holes;
- All isolations and steam barriers are in order;
- The heat transfer and fans are in their places;
- The condensing water outlet is installed and the water
is drained out;
- The air impellers and their adjusters are in working order;
- Afterheating is regulated and working.
USAGE DURING INSTALLING
The air exchange unit should be started as soon as
installation permits.
Efficient air exchange promotes drying of the constructions
and prevents damage.
In case channelling has not been completed, fans and adjustments
are missing,filter paper must be used in place of fans to keep
the channels clean andprovide sufficient counterpressure for
preventing overload. The unit must be used with full power and
check the drainage of the condensing water.
The appliance, filters and heat exchangers must be cleaned
and the systemadjusted after the construction works are
completed.
BASIC ADJUSTMENT OF AIRFLOW
The unit alone can not produce good interior ear in case
the channels and fans are installed carelessly and main
adjustments are not made.
Regulate the inlet and outlet fans to the planned positions
and start the unit
at design power speed. Measure the airflow in outside- and
exhaust air channels.
The outlet must be 5-10% higher than inlet. Check the
pressure level of thechannels by checking from the fans and
adjust it accordingly to obtain the pressure level of 20-30 Pa
for fans; adjust and lock the pattern.Draw measuring- and
adjustment records!
USAGE AND CORRECT LEVEL OF AIR EXCHANGE
The air exchange level is regulated by changing the
working speed of the air impeller from the operating panel.
Airflow of different adjustable positions can be seen
from table 2.
Adjustable position 1 is for basic air exchange for an empty house.
Adjustable position 2 and 3 are normal working positions.
Adjustable position 4 and 5 are efficiency positions (i.e. for
saunas).
The correct usage positions will be found by experience;
observing the purity of the air or sultriness when coming in
from outside, observing moisture on the windows or drying
of the sauna.
AFTERHEATING AND SUMMER BYPASS OF INLET AIR
The unit is equipped with 500W electrical heater operated
by the means of triac controller for afterheating of the heat
recovered inlet air.
The temperature of inlet air is usually regulated to +16C.
The temperature may be adjusted to higher during winter so there
would be no draught like feeling. In ca
se of severe frost and
efficiency mode the heating power might turn out insufficient –
in such circumstances, the air exchange should be reduced.
The overheating protection launched during malfunctioning
must be annulled manually.
During summertime, the bypass plate will be opened so the
exhaust air will not warm up the inlet air.
CONDENSING WATER AND FREEZING PREVENTION
When outlet air freezes, the humidity in the heat exchanger cell
turns into water, flows down to the condensing basin and from
there, through the hose and water-lock, into the open drain.
In the frosty weather the freezing of water is prevented by a dual-
acting antifreeze function which first turns on the preheater and
switches it off when the temperature rises above the set value. If the
power of the preheater is insufficient and the waste air temperature
drops below the "waste air cold" limit, the supply fan power is dropped
by increments until the limit value is reached.
THE SUMMER BYPASS OF THE HEAT RECOVERY UNIT MUST BE IN THE WINTER POSITION WHEN THE
AIRFLOWS ARE BEING ADJUSTED.
7
SERVICE MENU
INTRODUCTION OF THE AHU CONTROL PANEL
Settings are applied via the service menu
SETTINGS
NOTE! SWIPE RIGHT AT THE TOP OF THE SCREEN
Touch screen buttons:
Boosting
Fireplace switch
(pressure compensation)
Out-of-house mode
Fan speed adjustment 1....5
The button can be used to browse
the menu upwards and change settings.
The button can be used to browse
the menu downwards and change setting value.
Return to the previous or main menu.

8
THE CHANGES OF THE SERVICE MENU SETTINGS ALWAYS HAVE TO BE SAVED
.
Factory setting
10 min
3
Factory setting
17
o
C
MODBUS MENU
Check the separate Modbus manual
SEPARATE FIREPLACE SWITCH OR PRESSURE COMPENSATION
Factory setting
10 min
1
INTRODUCTION OF THE AHU CONTROL PANEL
0-10V external control (0-10V hood,remote monitoring) select the deployment
SENSOR 1 "EXT" or SENSOR 2 "EXT"
External control controls the basic speed , replaces the fan speed set in the menu.
Out-of-home, overpressure and boost are in use normally.
The main screen shows the fan speed at REMOTE CONTROL and
below of it is the speed of the supply fan.
External control fan speeds
0-2V fan 0
2-5V fan 2
5-7V fan 3
7-9V fan 4
9-10V fan 5
DEFAULT SETTINGS
1. 30 %
2. 40 %
3. 60 %
4. 80 %
5. 100 %
FAN SPEED PRIORITY
Fan speed preselection is performed from the control panel service menu.
Inlet and outlet fans can be individually adjusted for five different speeds with fan speeds of 20-100%
BOOSTING FROM THE COOKER HOOD WITH CONTACT TIP INFORMATION.
Boosting time settings 0 and 5...120 min. In 0 position with different pre-data
Boosting level settings 1...4 (the air impellers higher than basic speed), can be
adjused also from the settings menu.
Overpressure duration specification 0 and 5...20 min. In 0 position with different
pre-data
Overpressure limit regulation 1...4 (inlet air impeller higher than outlet air impeller)
REGULATION of the INLET AIR TEMPERATURE
Inlet air temperature range 5...30 oC,
can be adjusted via SETTINGS menu
CO2 AND/or RH SENSORS ACTIVATION
CO2 AND HUMIDY PERCENTAGE SETTING
Note: set the sensor on in the settings menu
SPEED CONTROL WITH A COOKER HOOD (0-10V)

Factory setting
IN USE
Factory setting
5
o
C
Factory setting
0
o
C
THRESHOLDS FOR FREEZING PROTECTION
The preheater is switched onfrom the service menu.
The limit value of the preheater can be changed from
the service menu if necessary. The adjustment range is 0 - +10
o
C.
The limit value of the preheater must be approx. 5
o
C higher than
the WASTE AIR COLD limit.
Temperature measurements of the preheater and
WASTE AIR COLD are measured from the waste air temperature
It is recommended to use value a minimum of 5 oC for the
WASTER AIR COLD limit ,if the preheater is not in use. When
the preheater is in use, the set value is about 5 o
C lower than the
limit value of the preheater. The adjustment range is -10 ... + 10
oC
The preheater and freezing protection are enabled,
changes are only if needed.
CHANGES OF THE SERVICE MENU SETTINGS ALWAYS HAVE TO BE SAVED
9
The summer bypass plate control. The user of the unit can set the bypass
plate manually to SUMMER/WINTER or AUTOMATIC mode.
In summer mode the bypass plate is activated
In the automatic mode, the plate works according to outside temperature.
Set value 15...20 oC
The automatic mode has adjustment amplitude of approx 2 hours
CO
2
transmitter ON/OFF switching. Setting of CO
2
upper limit.
Set value 250...1500ppm, 50ppm steps
%RH transmitter ON/OFF switching.
Setting of RH upper limit. Set value 30...80%, 5% steps
Regulating amplitude 5...20min
Regulation of inlet air afterheating set value 5...30 oC
SETTINGS ARE APPLIED VIA THE SETTINGS MENU OF THE CONTROL PANEL
Set value of boosting duration 0 and 5…120 min.
In 0 position with different pre
-
data
.
Set value of overpressure duration time (fireplace switch) 0 and 5…30
min. In 0 position with different pre-data.

10
The fastening screws of the preheater
REMOVING THE FAN
The fans can be removed for cleaning or replacement.
Before removing the fans ,the heat recovery ventilation unit must be
disconnected from the power supply
When removing the extract air fan ,remove first the pre-heater housing by
unscrewing the upper fastening screw and removing the lower lower fastening screw(see the picture).
When removing the supply airfan, move first the reset button of the overheat protection
aside by removing the metal plate.
Unplug the fan plug connector.
Remove the fastening screws of the fan and
pull the fan out of the machine.
REMOVING OF THE ELECTRICAL HOUSING
The screws of the
bypass damper.
The screws of the
electrical housing.
The electrical housing can be removed for the necessary maintenance, the external controls
or the
modbus termination by removing the bypass damper and then unscrewing the electrical
housing screws.

DEEKAX Air Oy
Patruunapolku 4 Puh. 0207 912550
79100 LEPPÄVIRTA www.deekaxair.fi
PURE JOY FROM INDOOR AIR !
MAINTENANCE OF TALTERI
For producing good indoor climate continuously, the air exchange systems require regular maintenance.
The metallic grease filter of stove hood must always be kept clean for fire safety reasons. Cleansing with hot
water dishwasher once a month is
necessary. Substances suitable for machine washing may darken the
aluminium parts of the filter.
The inlet and outlet filters of Talteri must be cleansed at least twice a year.
In summertime the summer cassette plate will be set to summer mode
when the external air should come in fresh and clean.
The heat recovery cell will be pulled out of the unit and washed thoroughly in autumn just before the heating
season begins –the heat recovery will then be at its best. Check the condition of sealing and push the heat
recovery cell back to its place.
The inner painted walls of the unit are easy to clean. Check the condition of sealing, clean the outlet hose of
condensing water and make sure the water flows freely and without any obstructions.
The impellers, air exchange adjusters and thermostats are components that do not require regular
maintenance. Electrical works can be carried out only by a qualified electrician.
During the frosty period the heat recovery cell is defrozen by using the preheater. The power of the
preheater is mainly adequate to keep the heat recovery cell defrozen. In extreme conditions, if the power of
the preheater is not sufficient, the supply fan power will be reduced or stopped by the freezing protection
thermostat when the exhaust air temperature drops below the set value (0°C). The supply fan starts when
the exhaust air temperature rises above the set value.
Under extreme conditions (humidity /harsh cold) the Ito-element may freeze over and the anti-freeze
protection series are not able to defrost it. If such a case occurs, the machine has to be stopped, opened and
the cold flow stopped and the ice given the necessary time to melt. Check the drainage of condensing water!
In case the water-lock dries out and makes pulping noise, you can pour a drop or two of cooking oil.
In really cold weather, the head recovery unit heats the preheated inlet air with afterheating. The functionality
can be proved by comparing the temperature of inlet air to the set value of the inlet air afterheating.
The overheat protection has been activated in case the temperature has risen +90 °C (for instance, in case
of power failure). Reset the overheat temperature by pressing the switch under the threaded contact
protection.
The channels must be checked if the impeller works but the air exchange is inadequate or the temperature
changes in the channels between the interior and the machine. Temperature changes and humidity
concentration in channels must be prevented by improving the isolation.
Table of contents
Other Deekax Air Handler manuals
Popular Air Handler manuals by other brands

Salda
Salda RIS 400 PE 0 MOUNTING AND INSTALLATION INSTRUCTION

Carrier
Carrier 40MBAA installation instructions

RDZ
RDZ RNW 404-CS Technical installation manual

MrCool
MrCool PRODIRECT Series Installation & owner's manual

Daikin
Daikin Altherma 3 R F Installer's reference guide

Vents
Vents MICRA 100 user manual

Lennox
Lennox SL280DFNV Series Unit information

Trane
Trane Performance Climate Changer Installation, operation and maintenance

Carrier
Carrier 42DW Series Installation instruction

Allstyle
Allstyle SL Series installation guide

Multicalor
Multicalor MC-10 installation instructions

Weather-Rite
Weather-Rite XT112 Installation, operation & service manual