Delta DVPEN01-SL User manual

DVPEN01-SL
Ethernet Communication Module
Operation Manual
DVP-0204320-02


Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 1
Warning
3
Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages
on the device or injuries to staff.
3
Switch off the power before wiring.
3
RTU-DNET is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric
shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools
are required for operating the enclosure) in case danger and damage on the device may occur.
3
RTU-DNET is to be used for controlling the operating machine and equipment. In order not to damage it, only qualified
professional staff familiar with the structure and operation of RTU-DNET can install, operate, wire and maintain it.
3
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the
wirings again before switching on the power and DO NOT touch any terminal when the power is switched on. Make sure the
ground terminal is correctly grounded in order to prevent electromagnetic interference.
Table of Contents
1INTRODUCTION...................................................................................................................................3
1.1 Functions.....................................................................................................................................3
1.2 Specifications ..............................................................................................................................3
2PRODUCT PROFILE & OUTLINE .......................................................................................................4
2.1 Dimension ...................................................................................................................................4
2.2 Product Profiles...........................................................................................................................4
2.3 LED Indicators.............................................................................................................................5
2.4 RJ-45 PIN Definition....................................................................................................................5
3INSTALLATION & WIRING ..................................................................................................................5
3.1 Installation ...................................................................................................................................5
4CONTROL REGISTER (CR) ................................................................................................................6
4.1 Control Registers in DVPEN01-SL..............................................................................................6
4.2 Explanations on CR ....................................................................................................................8
4.3 Numbering of Left-Side Modules...............................................................................................13
5SETTING UP SOFTWARE.................................................................................................................14
5.1 Setting up Communication & Searching for Modules................................................................14
5.2 Basic Settings ...........................................................................................................................20
5.3 Network Settings .......................................................................................................................21
5.4 Setting up E-Mails .....................................................................................................................24
5.5 Data Exchange..........................................................................................................................25
5.6 RTU ...........................................................................................................................................26
5.7 IP Filter......................................................................................................................................27
5.8 Static ARP Table........................................................................................................................27
5.9 Setting up Password .................................................................................................................28

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
2
5.10 Returning to Default Setting ..................................................................................................... 29
6APPLICATION EXAMPLES............................................................................................................... 30
6.1 Setting up IP and Communicating through WPLSoft................................................................ 30
6.2 Connecting the PC with DVPEN01-SL through LAN ................................................................ 33
6.3 Setting up Password and Clearing Password .......................................................................... 37
6.4 When the Password is Lost (Returning to Default Setting by RS-232)..................................... 39
6.5 IP Filter Protection .................................................................................................................... 40
6.6 Setting up Static ARP Table ...................................................................................................... 42
6.7 Application of E-Mail................................................................................................................. 44
6.8 Application of Data Exchange (1) ............................................................................................. 45
6.9 Application of Data Exchange (2) ............................................................................................. 48
6.10 Application of Data Exchange (3) ............................................................................................. 49
6.11 Application of Data Exchange (4) ............................................................................................. 50
6.12 Application of Data Exchange (5) ............................................................................................. 52
6.13 Application of Modbus TCP Master .......................................................................................... 53
6.14 RTU Mapping............................................................................................................................ 54

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 3
1 Introduction
Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read
the manual carefully before using the module.
DVPEN01-SL is an Ethernet communication module for remote setting and communication through
WPLSoft. DVPEN01-SL is able to send E-mails, automatically correct the RTC in DVP28SV11R/T and
exchange data. It supports Modbus TCP communication protocol and can conduct remote monitoring by using
SCADA (Supervisor Control and Data Acquisition) software or HMI (Human Machine Interfaces). DVPEN01-SL
can be the master of Modbus TCP, sending out Modbus TCP instructions and controlling the peripheral
equipment. In addition, under MDI/MDI-X auto-detection, it does not need to use a crossing cable. See the
contents below for more detailed instructions on DVPEN01-SL module.
1.1 Functions
zAuto-detects 10/100Mbps transmission speed
zMDI/MDI-X auto-detection
zSupports Modbus TCP protocol (at the same time supports Master and Slave mode)
zAble to send out E-mails
zAuto-corrects the RTC in PLC through the Internet time correction function
zSupports point-to-point data exchange (Max. data exchange length: 200 bytes)
1.2 Specifications
Internet interface
Item Specification
Interface RJ-45 with Auto MDI/MDIX
Number of ports 1 Port
Transmission method IEEE802.3, IEEE802.3u
Transmission cable Category 5e
Transmission speed 10/100 Mbps Auto-Detect
Network protocol ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, Modbus TCP
Serial communication interface
Item Specification
Interface RS-232
Number of ports 1 Port
Transmission cable DVPACAB230, DVPACAB215, DVPACAB2A30, DVPACAB2B10
Environment
Item Specification
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Environment Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
4
Item Specification
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Vibration/ Shock Resistance Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Electrical specifications
Item Specification
Power supply voltage 24VDC (-15% ~ 20%) (Power is supplied by the internal bus of MPU.)
Power consumption 1.5W
Insulation voltage 500V
Weight (g) 92 (g)
2 Product Profile & Outline
2.1 Dimension
LAN
RS-232
LINK
DVPEN01
RS-232
POWER
100M
60 [2.362]
90 [3.543]
3 [0.118]
Unit: mm [inches]
2.2 Product Profiles
LAN
RS-232
LINK
DVPEN01
RS-232
POWER
100M
1
4
3
7
5
6
9
8
2
1. Model name 6. Fixing tenon for I/O module
2. Extension port to connect device 7. Fixing clip for I/O module
3. Extension port to connect I/O module 8. RS-232 connection port
4. POWER, LINK, RS-232, 100M indicators 9. Ethernet RJ-485 connection port
5. DIN rail clip

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 5
2.3 LED Indicators
Indicator Color Indication
POWER Green Power indication
RS-232 Red Communication status of the series port
100M Orange Network connection status
LINK Green Network communication speed
2.4 RJ-45 PIN Definition
RJ-45 sketch Terminal No. Definition Explanation
1 Tx+ Positive pole for data transmission
2 Tx- Negative pole for data transmission
3 Rx+ Positive pole for data receiving
6 Rx- Negative pole for data receiving
4, 5, 7, 8 - N/C
3 Installation & Wiring
This section gives instructions on how to connect DVPEN01-SL with PLC MPU and how to connect
DVPEN01-SL to the network.
3.1 Installation
Connect PLC MPU to DVPEN01-SL
zAdjust the I/O module clip on the left side of the MPU.
zMeet the I/O module port of the MPU with DVPEN01-SL as shown in the figure below.
zFasten the I/O module clip on the left side of the MPU.
DVP28SV
LAN
RS-232
RS-232
LINK
100M
DVPEN01
POWER
Connect DVPEN01-SL to other I/O modules
zTo connect DVPEN01-SL with the other I/O module, lift the extension clip of the I/O module by a
screwdriver and open the side cover.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
6
Connect DVPEN01-SL to the Network:
Connect DVPEN01-SL to the Ethernet Hub by twisted pair cable CAT-5e. DVPEN01-SL has Auto MDI/MDIX
function; therefore, DVPEN01-SL does not need to use a crossing cable between the PC and DVPEN01-SL.
Network connections between the PC and DVPEN01-SL:
4 Control Register (CR)
4.1 Control Registers in DVPEN01-SL
CR#
HW LW Attribute Content Explanation
#0 R Model name Set up by the system; read only. Model code of DVPEN01-SL
= H’4050
#1 R Firmware version Displaying the current firmware version in hex.
#2 R Communication mode b0: Modbus TCP mode; b1: data exchange mode
#3 W E-Mail Event 1 trigger Set up whether to send E-Mail 1
#4 W E-Mail Event 2 trigger Set up whether to send E-Mail 2
#5 W E-Mail Event 3 trigger Set up whether to send E-Mail 3
#6 W E-Mail Event 4 trigger Set up whether to send E-Mail 4
Ethernet
PC Maste
r
DVP28SV
LAN
RS-232
RS-232
LINK
100M
DVPEN01
POWER
DVP28SV
DVPEN01
DVP28SV
LAN
RS-232
RS-232
LINK
100M
DVPEN01
POWER
DVP28SV
DVPEN01

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 7
CR#
HW LW Attribute Content Explanation
#7 R Status of E-Mail 1, 2 b0 ~ b7: Current status of E-Mail 2
b8 ~ b15: Current status of E-Mail 1
#8 R Status of E-Mail 3, 4 b0 ~ b7: Current status of E-Mail 4
b8 ~ b15: Current status of E-Mail 3
#9 R/W
E-Mail 1 additional
message Filled in by the user, and it will be send by E-mail.
#10 R/W
E-Mail 2 additional
message Filled in by the user, and it will be send by E-mail.
#11 R/W
E-Mail 3 additional
message Filled in by the user, and it will be send by E-mail.
#12 R/W
E-Mail 4 additional
message Filled in by the user, and it will be send by E-mail.
#13 R/W Data exchange trigger Set up whether to send out data in data exchange mode
#14 R Status of data exchange Displaying current status of data exchange.
#15 RW
Enabling flag for RTU
mapping 1: Enable; 0: Disable. Default = 0
#16 RW
Connection status of
RTU mapping slave
b0: Status of RTU slave 1
b1: Status of RTU slave 2
b2: Status of RTU slave 3
b3: Status of RTU slave 4
#24 ~ #17 - Reserved
#26 #25 R/W Destination IP Destination IP address for data exchange
#27 - Reserved
#28 R/W Destination Slave ID Destination Slave ID for data exchange
#48 ~ #29 R/W Data transmission buffer Buffer for transmitted data in data exchange
#68 ~ #49 R Data receiving buffer Buffer for received data in data exchange
#80 ~ #69 - Reserved
#81 R/W
Read address for data
exchange Slave transmission buffer address for data exchange
#82 R/W
Read length for data
exchange Number of registers for read data
#83 R/W
Received address for
data exchange Buffer address for the receiving Master in data exchange
#84 R/W
Written-in address for
data exchange Buffer address for the receiving Slave in data exchange
#85 R/W
Written-in length for data
exchange Number of registers for data transmission
#86 R/W
Transmission address
for data exchange Master transmission buffer address for data exchange
#110 ~ #87 - Reserved
#111 R/W 8-bit processing mode Setting up Modbus TCP Master control as 8-bit mode
#112 R/W
Modbus TCP Keep-Alive
Time-out Modbus TCP Keep-Alive Time-out (s)
#113 - Reserved
#114 R/W Modbus TCP time-out Setting up Modbus TCP time-out (in ms)

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
8
CR#
HW LW Attribute Content Explanation
#115 R/W Modbus TCP trigger Setting up whether to send out data in Modbus TCP mode
#116 R/W Modbus TCP status Displaying current status of Modbus TCP mode
#118 #117 R/W Modbus TCP
destination IP Setting up destination IP address for Modbus TCP transaction
#119 R/W Modbus TCP data length Setting up the data length for Modbus TCP transaction
#219 ~ #120 R/W Modbus TCP data buffer Data buffer of Modbus TCP for storing sending/receiving data
#248 ~ #220 - Reserved
#251 R Error code Displaying the errors. See table of error codes in the following
section for more information.
#255 ~ #252 - Reserved
Symbols “R” refers to “able to read data by FROM instrcution”; “W” refers to “able to write data by TO
instrcution”.
4.2 Explanations on CR
CR#0:Model Name
Explanations:
1. Model code of DVPEN01-SL = H’4050.
2. You can read the model code in the program to see if the I/O module exists.
CR#1: Firmware Version
Explanations:
The firmware version of DVPEN01-SL is displayed in hex, e.g. H’0100 indicates version V1.00.
CR#2: Communication Mode
Explanations:
Bit No. Mode “0” “1”
b0 Modbus TCP Disable Enable
b1 Data exchange Disable Enable
E-mail Functions
CR#3 ~ 6: E-Mail Event 1 ~ 4 Trigger
Explanations:
When the CR is set as “1”, E-mail sending will be enabled. After the sending is completed, the
CR will automatically be reset as “0”. Note: Please trigger by differential instructions.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 9
CR#7 ~ 8: Status of E-Mail 1 ~ 4
Explanations:
1. CR#7_b0 ~ b7: current status of E-Mail 2; CR#7_b8 ~ b15: current status of E-Mail 1.
2. CR#8_b0 ~ b7: current status of E-Mail 4; CR#8_b8 ~ b15: current status of E-Mail 3.
3. Table of E-Mail status
CR value E-Mail status
0 Not been sent
1 Being processed
2 E-Mail sending is successful
10 Fail to connect to SMTP-Server
11 Incorrect recipient E-Mail address
12 SMTP-Server communication error
13 Exceeding the max. number of TCP connection
3 ~ 9, 14 ~ 255 Reserved
CR#9 ~ 12: E-Mail 1 ~ 4 Additional Message
Explanations:
The user fills in the code, and the code will be stored in the title of the E-Mail and sent out with the
E-Mail.
Data Exchange
CR#13: Data Exchange Trigger
Explanations:
When the CR is set as “0”, the data in data exchange area will not be transmitted. When the CR is
set as “1”, the data in data exchange area will be transmitted.
fWhen the Execute Mode in the software is set to “Program Control” (See 5.5), set CR#13 to 2,
and the data exchange will continue to execute. Set CR#13 to 0 to stop the data exchange.
fWhen the Execute Mode in the software is set to “Always Enable”, the data exchange will
continue to execute whatever the setting in CR#13 is.
(Firmware V2.0 and later versions support continuous execution of data exchange.)
CR#14: Data Exchange Status
Explanations:
When the CR is set as “0”, the data have not yet been received. When the CR is set as “1”, the
data exchange is in progress. When the CR is set as “2”, the data exchange is successful. When
the CR is set as “3”, the data exchange fails.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
10
CR value Status
0 Data have not yet been received.
1 Data exchange is in progress.
2 Data exchange is successful.
3 Data exchange fails.
CR#25, 26: Destination IP
Explanations:
To set up the Slave IP address for data exchange manually, write “0” into CR#28 first before
setting up the destination IP. For example, if the user wants to set the destination IP address to
192.168.0.2, write H’0002 to CR#25 and H’C0A8 to CR#26. (K192 = H’C0, K168 = H’A8, K0 =
H’00, K2 = H’02).
CR#28: Destination Slave ID
Explanations:
When you set up the Salve ID (i.e. K1 ~ K255) for data exchange, DVPEN01-SL will
automatically search for the corresponding IP address from the Slave IP list. For example, if the
ID is set as “0”, the value in CR#25 and #26 will be regarded as the destination IP.
CR#29 ~ 48: Data Transmission Buffer
Explanations:
Storing the data to be transmitted to the remote MPU.
CR#49 ~ 68: Data Receiving Buffer
Explanations:
Storing the data received from the remote MPU.
CR#81: Read Address for Data Exchange
Explanations:
Setting up manually the Modbus address of the register for Slave data exchange. Only register
address is allowed (e.g. D0 = H’1000).
CR#82: Read Length for Data Exchange
Explanations:
The number of receiving registers (K1 ~ K100) in data exchange.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 11
CR#83: Read Length for Data Exchange
Explanations:
Setting up the Modbus address of the register for Master data exchange.
CR#84: Written-in Address for Data Exchange
Explanations:
Setting up manually the Modbus address of the register for Slave data exchange.
CR#85: Written-in Address for Data Exchange
Explanations:
The number of transmission registers (K1 ~ K100) in data exchange.
CR#86: Transmission Address for Data Exchange
Explanations:
1. Setting up the Modbus address of the register for Master data exchange.
2. Example: Write H’1000 (D0) into CR#81, K1 into CR#82, and H’1064 (D100) into CR#83. If
the data exchange is successful, the value in D0 of the Slave will be written into D100 of the
MPU. Or write H’1002 (D2) into CR#84, K4 into CR#85, and H’1008 (D8) into CR#86. If the
data exchange is successful, the value in D8 ~ D11 of the Master will be written into D2 ~ D5
of the Slave. Both sending and receiving can be executed at the same time. When the values
in CR#82 and #85 are both “0”, DVPEN01-SL will use the default registers (CR#29 ~ CR#68)
and number of registers (K20).
Sending Modbus TCP Instruction
CR#111: 8-bit Processing Mode
Explanations:
Setting up the Modbus TCP transmission mode. When the CR value is set as “0” Æ16-bit mode;
when the CR value is set as “1” Æ8-bit mode.
CR#112: Modbus Client Keep-Alive Time-out
Explanations:
CR#112 is the TCP Keep-Alive time-out for Modbus TCP connection (s). Default: 30s. If the
connection idle time becomes longer than the keep-alive time-out, DVPEN01-SL will cut off the
idle connection.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
12
CR#114: Modbus TCP Time-Out
Explanations:
Setting up the communication time-out (in ms) for Modbus TCP mode.
CR#115: Modbus TCP Trigger
Explanations:
When the CR value is set as “1”, Modbus TCP will be triggered. After the data transmission is
completed in Modbus TCP mode, the CR value will automatically be reset to “0”. Please trigger
by differential instructions.
CR#116: Modbus TCP Status
Explanations:
Displaying the current communication status of Modbus TCP mode. When the CR value is set
as”0” Æthe data have not yet been received; when the CR value is set as “1” Æthe data
exchange is in progress; when the CR value is set as “2” Æthe data exchange is successful;
when the CR value is set as “3” Æthe data exchange fails.
CR value Data exchange status
0 The data have not been received.
1 The data exchange is in progress.
2 The data exchange is successful.
3 The data exchange fails.
CR#117, 118: Modbus TCP Destination IP
Explanations:
Setting up the destination IP address in Modbus TCP mode. See explanations on CR#70 and
#71 for how to set.
CR#119: Modbus TCP Data Length
Explanations:
Setting up the length of communication data in Modbus TCP mode. Length for 8-bit mode: K1
~K100; length for 16-bit mode: K1 ~ K200.
CR#120 ~ 219: Modbus TCP Data Buffer
Explanations:
Buffer for transmitted/received data in Modbus TCP mode.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 13
CR#251: Error Code
Explanations:
Table of error code:
Bit No. Error
b0 The network is not yet connected.
b1 Incorrect IP setting
b2 CR#13 is set as “transmitting data”, but the data exchange
is forbidden.
b3 CR#13 is set as “transmitting data”, but the data exchange
mode has not yet been enabled.
b4 NTP-Server connection fails.
b7 SMTP-Server connection fails.
b8 DHCP has not obtained the correct network parameter.
RTU Mapping
CR#15:Enabling Flag for RTU Mapping
Explanations:
1: Enable; 0: Disable. Default = 0
Firmware V2.0 and later versions support RTU mapping.
CR#16: Connection Status of RTU Mapping Slave
Explanations:
b3 ~ b0 display the connection status of RTU slave. The connection may encounter some
problems when any of the bits becomes 0. Firmware V2.0 and later versions support RTU
mapping.
b0: Status of RTU slave 1
b1: Status of RTU slave 2
b2: Status of RTU slave 3
b3: Status of RTU slave 4
4.3 Numbering of Left-Side Modules
After DVPEN01-SL is installed properly, you need to compile the PLC program to control the special I/O
module. PLC offers FROM instruction (for reading) and TO instruction (for writing) to control the control registers
(CR) in the special I/O module.
Numbering of the modules: Every special I/O module connected to PLC MPU has a No. to allow you to know
which module is which when compiling the PLC program. The first special I/O module attached at the left hand
side of the PLC MPU is numbered as K100, the second as K101, the third K102, and so on.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
14
5 Setting up Software
This section gives instructions on how to set up DVPEN01-SL by DCISoft and explanations on each setup
page. Before you start a setup page, you have to select “Ethernet” in the communication setting. Next, you can
search by IP address or use Auto-Search. You also can open the setup page for DVPEN01-SL by RS-232.
DVPEN01-SL is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the
firewall.
5.1 Setting up Communication & Searching for Modules
Communication settings
1. Open DCISoft in your PC and click on “Communication Setting”.
2. Select “Ethernet” as the transmission type.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 15
Broadcast search
1. Click broadcast icon in DCISoft to search for all Delta Ethernet products on the network. The
window on the left hand side shows the models found, and the window on the right hand side
displays the device list of all models.
2. Click a model on the left hand side, and you will see the device list of the model selected on the
right hand side. Click the device to be set up to enter the setup page.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
16
3. You will see the basic setup page as follow.
Designating model to search
1. Right click “Ethernet” on the left hand side window and select “Configure” to designate a model to
search for.

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual 17
2. After configure a model, select “DVPEN01-SL” and click “OK” to auto-search for DVPEN01-SL
modules on the network.
3. List of the current DVPEN01-SL modules

Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
18
Searching by IP address
1. Set the communication type to “Ethernet” and enter the IP address. Click “OK”.
2. Click “IP Search” icon to start searching for the designated IP.
3. The DVPEN01-SL module found will be displayed in the right hand side window. Double click it
to enter the setup page.
Other manuals for DVPEN01-SL
1
Table of contents
Other Delta Network Hardware manuals

Delta
Delta DX-2100 Series User manual

Delta
Delta R2-EC 004 Series User manual

Delta
Delta CMC-EC01 User manual

Delta
Delta MNVR1104-GCW User manual

Delta
Delta VIVOTEK ND9442P User manual

Delta
Delta Vivotek ND9213P User manual

Delta
Delta AHCPU560-EN2 Series User manual

Delta
Delta PD-01 User manual

Delta
Delta AS Series Owner's manual

Delta
Delta DVP series User manual
Popular Network Hardware manuals by other brands

D-Link
D-Link DNS-1560-04 Quick installation guide

Extron electronics
Extron electronics PoleVault System PVT RGB CV MK installation guide

D-Link
D-Link ShareCenter Pulse DNS-320 user manual

FieldServer
FieldServer FS-8704-06 instruction manual

Digitus
Digitus Unique Series manual

Omron
Omron DeviceNet DRT2-ID16 brochure