Det-Tronics Eagle Quantum Premier EQ3750ASH User manual

5.1 Rev: 4/17 95-8654
Instructions
Eagle Quantum Premier ®
Addressable Smoke & Heat (ASH) Module
Model EQ3750ASH

5.1
95-8654
2
INSTRUCTIONS
Eagle Quantum Premier®
(EQP)
Addressable Smoke & Heat (ASH) Module
EQ3750ASH
5.1 ©2020 Detector Electronics Corporation Rev: 4/17 95-8654
DESCRIPTION
The Eagle Quantum Premier®(EQP) Addressable
Smoke and Heat (ASH) Module is designed to expand
the input and output capability of Detector Electronics
Corporation’s (Det-Tronics®) EQP system.
The ASH is an interface device designed to provide
continuous and automated fire protection. It ensures
system operation through supervision of system inputs/
outputs and Local Operating Network/Signaling Line
Circuit (LON/SLC) monitoring in the Controller.
The ASH is located directly on the LON of the EQP system,
with a loop of up to 64 addressable devices tied into the
ASH. This allows the EQP Controller to annunciate a fire
alarm from either its own LON based I/O or from the ASH
connected addressable detection loops.
System status can be determined using the Eagle
Quantum Safety System Software (S3), and the status
indicators on the module.
FEATURES AND BENEFITS
• Expands the capabilities of Det-Tronics’ Eagle
Quantum Premier system
• EQP Controller can support up to 10 ASH Modules
on a loop
NOTE
This support is dependant on system conguration
and logic within S3.
• Provides power and communications to 64
addressable devices
• Utilizes Apollo Discovery devices
• ASH Module alarm and fault conditions are logged in
the EQP Controller
• LEDs for easy annunciation of power, faults and
active devices on the loop
• Monitors single addressable devices
• Provides remote I/O capabilities via LON/SLC.
• DIN Rail or Panel mounting
• Plug-in wiring connectors
• RFI and EMI hardened
• Approved for use in Marine applications (Panel
mount only)

5.1
95-8654
3
THEORY OF OPERATION
During normal operation, the ASH Module continuously
checks the loop for alarm and fault conditions and
executes user defined programmed logic that coordinates
the control of the field devices. The ASH Module reports
any device based fault and alarm conditions to the EQP
Controller.
The ASH Module can support different Apollo Discovery
and XP95 devices (see Table 3). The supported devices
include smoke detectors, heat detectors, manual calls,
sounders, beacons and I/O modules. The addressable
devices are configured individually via the ASH Apollo
Editor in the S3software.
To ensure reliable system operation, the ASH Module can
continuously monitor its input and output circuits for open
and short circuit conditions. The EQP Controller also
continuously monitors the status of the ASH Module as
well as the status of each device connected to the ASH
Module.
The controller communicates with the ASH Module by
continuously broadcasting a heartbeat signal over the
LON (Figure 1). This heartbeat is used for verifying the
integrity of the LON and for keeping the addressed
field devices from going into a fault isolation mode.
The heartbeat also contains the current date and time,
which is used by the field devices to log status events
and calibrations. For detailed information on the EQP
Controller, refer to instruction manual 95-8533.
ISOLATORS
Isolators are used to disconnect a shorted section
of the ASH Module Apollo loop so that the remaining
sections can continue to operate. In accordance
with the NFPA 72 standard for SLCs, the ASH Module
supports Class A, Class B, and Class X SLC wiring
styles.
NOTE
A maximum of sixty-ve isolators may be used on
the Apollo loop.
For the Class A wiring style, isolators are optional on the
ASH Module Apollo loop where only a single zone is
monitored. During a single open, a single ground fault,
or the combination of a single open and a single ground
fault, the Class A pathway shall maintain alarm receipt
capabilities. See Figure 2 for Class A pathway.
Class B requires that a spur configuration be used, with
the single spur connected to the “Loop Out” terminals
on the ASH Module. The Class B pathway is intended for
use in a single zone system. When a single ground fault
is present, alarm receipt capabilities shall be maintained.
Devices beyond a single open will lose connection, but
all devices will lose connection for a short. See Figure 3
for Class B pathway.
C2532
NODE 1 NODE 8
HARDWIRED LON CONNECTION
NODE 3 NODE 6
NODE 2 NODE 7
ASH MODULE
NODE 5
NODE 4
EQP
CONTROLLER
EAGLE QUANTUM PREMIER
Safety System Controller
FireAlarm Inhibit Pow er
SuprHighGas
Trouble
CntrlFlt
LonFaultLowGas Ack Silence
OutInhibit
EagleQuantum Premier
Time& Date
Cancel Enter Next Previous Reset Acknowledge Silence
DET-TRONICS®
NODE 64
NODE 1
...NODE 63
NODE 3...
NODE 2
.............
.......
........
ASH MODULE APOLLO LOOP
2-WAY COMMUNICATION
...................
................. .................
...................
A2589
ASH MODULE
NODE 64
NODE 1
...NODE 63
NODE 3...
NODE 2
SINGLE
ZONE
.............
.................
.......
........
ASH MODULE APOLLO LOOP
2-WAY COMMUNICATION
.....................
.................
.....................
ISOLATOR
(Optional)
ISOLATOR
(Optional)
ISOLATOR
(Optional)
ISOLATOR
(Optional)
ENCLOSURE
Figure 1—EQP LON with ASH Module Communication
Figure 2—Class A Pathway (isolators are optional)
A2590
ASH MODULE
NODE 64
NODE 2...
...NODE 63
NODE 1
SINGLE
ZONE
.............
.............
ASH MODULE APOLLO LOOP
2-WAY COMMUNICATION
........ ........ ........
ENCLOSURE
Figure 3—Class B Pathway (without isolators)

5.1
95-8654
4
Class X is intended for use in a multi-zone system and
requires that the first isolator on each leg be installed
next to the ASH Module, within the same enclosure. In
addition, an isolator is needed between each zone as
illustrated in Figure 4. Alarm receipt capabilities in the
other zones shall be maintained during a single open,
single ground, wire-to-wire short, or open and ground.
NOTE
The isolator has an operating temperature range
of +32°F to +100°F (0°C to +38°C). This means
that, for Class X installations, the enclosure
temperature will be rated to +100°F (+38°C) max.
Reference Table 1 for further details on the performance
requirements for SCLs as defined by NFPA 72.
LED INDICATORS
LEDs on the front of the ASH Module are provided for
indicating device status conditions. There are 6 LED
status indicators (Power, ASH Module Fault, Loop Fault,
Loop Device Fault, Ground Fault, and Alarm) located
on the front panel (Figure 5). Refer to Table 2 for a
description of the LED indicators.
MOUNTING
The ASH Module can be DIN Rail or Panel mounted.
ADDRESSABLE LOOP DEVICES
See Table 3 for a list of all supported Apollo loop devices.
NOTE
The input and/or output circuits for the Mini
Monitor Module and Priority Mini Switch
Monitor (P/N 55000-765*), Priority Switch
Monitor (P/N 55000-806), Input / Output
Module (P/N 55000-820) and Sound Control
Module (P/N 55000-825) must be no longer
than 20 ft (6 m) and must be installed in conduit
or equivalently protected against mechanical
injury.
For additional information and documentation regarding
all Apollo devices, visit www.apollo-fire.co.uk.
A2591
ASH MODULE
NODE 64
NODE 1
...NODE 63
NODE 3...
NODE 2
ZONE 2
ZONE 1 ZONE 3
.............
.................
.......
........
ASH MODULE APOLLO LOOP
2-WAY COMMUNICATION
.....................
.................
.....................
ISOLATOR ISOLATOR
ISOLATORISOLATOR
ENCLOSURE
Figure 4—Class X Pathway (multi-zone with isolators)
Figure 5—Location of LED Indicators
STATUS
INDICATOR
LEDs
LED Label ASH Module Status*
Green PWR On when power is present
Yellow ASH MOD Fault in the ASH Module
Yellow LOOP Loop Fault
Yellow LOOP DEV Fault with a device on the loop
Yellow GND FLT Ground fault on the Apollo loop
Red ALARM An alarm is present
*Reference to “loop” refers to the ASH Module or Apollo device loops.
Table 2—ASH Module Device Status Indicators
Table 1—Performance of Signal Line Circuits (SLCs)
NFPA 72-2013 Class
Class B Class A Class X
Alarm Trouble ARC Alarm Trouble ARC Alarm Trouble ARC
Condition 1 2 3 4 5 6 7 8 9
Single open – X – – X R – X R
Single ground – X R – X R – X R
Wire-to-wire short – X – – X – – X R
Open and ground – X – – X R – X R
ARC = Alarm Receipt Capability
R = Required capability
X = Indication required at protected premises

5.1
95-8654
5
POWER-UP SEQUENCE
Set the ASH Module network address prior to applying
power. Make sure all the necessary connections are made
between the ASH Module and the Controller. At power-up
the “PWR” (Power) LED will illuminate and remain steady.
FAULTS
When a fault condition occurs, a yellow LED on the front
panel of the ASH Module will become active. There are 4
yellow LEDs for different categories of faults.
Module faults
A module fault occurs when a fault is detected within the
ASH Module, such as:
• Low voltage fault
• Memory fault
• Crystal oscillator fault
• Battery fault
Loop faults
A loop fault is related to the Apollo device’s loop
communication and configuration, such as:
• Open loop
• Shorted loop
• Device missing
• Extra device
• Wrong device
• Multiple devices
Loop device faults
A loop device fault is related to an individual device on the
loop, and is typically fixed by replacing the faulty device.
Any of the following faults can be categorized as a loop
device fault:
• Integrity check fault
• Device open
• Device short
• Device hardware faults
• Drift warning
• Earth fault
Ground faults
Ground faults occur when a short or partial short exists
between the loop wiring and earth on the Apollo loop. There
is a local dedicated LED indicator that activates when there
is either a positive or negative ground fault.
Table 3—List of Supported Devices
DET-TRONICS
PART NUMBER
APOLLO
PART NUMBER DEVICE NAME
000515-501 58000-500 Apollo Ionization Smoke, EU
000515-502 58000-600 Apollo Optical Smoke Detector, EU
000515-503 58000-400 Apollo Heat Detector, EU
000515-504 58000-700 Apollo Multisensor, EU
000515-505 58000-300 Apollo Carbon Monoxide Detector, EU
000515-507 45681-284 Apollo Isolating Base, FM
000515-508 55000-720 Apollo Isolator, EU
000515-509 55000-847 Apollo Input / Output Unit, with Isolator
000515-510 55000-852 Apollo Sounder Control Unit
000515-511 55000-841 Apollo Switch Monitor Plus
000515-512 58100-908 Apollo Manual Call, with Isolator
000515-513 58100-951 Apollo Manual Call, with Isolator, IP66
000515-514 26729-152 Apollo Manual Call Cover, EU
000515-515 55000-278 Apollo Sounder, 100dB, Red
000515-516 55000-274 Apollo Sounder, 100dB, Red, IP66
000515-517 55000-877 Apollo Beacon, Red
000515-518 55000-293 Apollo Sounder / Beacon, with Isolator
000515-521 38531-771 Apollo Blank Address Card
000515-551 58000-550 Apollo Ionization Smoke, FM
000515-552 58000-650 Apollo Optical Smoke Detector, FM
000515-553 58000-450 Apollo Heat Detector, FM
000515-554 58000-750 Apollo Multisensor, FM
000515-555 45681-210 Apollo Mounting Base, 4”, FM
000515-556 45681-225 Apollo Deep Base, 6”, FM
000515-557 55000-750 Apollo Isolator, FM
000515-559 55000-806 Apollo Priority Switch Monitor, FM
000515-558 45681-211 Apollo Isolator Base, FM, EU
000515-560 55000-825 Apollo Sounder Control Module, FM
000515-561 55000-765* Apollo Input / Output Module, FM
000515-563 45681-209 Apollo Deep Base, EU
000515-605 56000-005USA Pull Station, Dual Action, Non-Isolated,
Non-Waterpoof, UL Listed
000515-620 55000-863 Apollo Relay Output, Standard, FM
* The device type depends on the priority switch setting on the device.
FM = FM Approved
EU = European Approvals

5.1
95-8654
6
CONTROL MESSAGE
The control message manages loop device specific
commands, such as integrity check, LED, relay and sound
control. The control message is transmitted from the
controller every 20 seconds, or immediately when there is
a change in the state of an output channel. A fault will be
annunciated if the control message is not received at the
controller within 2 minutes.
INTEGRITY CHECK
Integrity checks are internal tests that are performed on loop
devices that support the integrity check feature. All Apollo
Discovery detectors and manual call points are equipped with
the integrity check feature. The integrity check may be initiated
and monitored via the ASH Module point display in S3.
Passive and Active Integrity Checks
During a passive integrity check no alerts will be sent to
the ASH Module or EQP Controller. All indications will be
handled by the local LEDs on the loop devices.
An active integrity check will be indicated on the ASH
Module, the controller, and the loop devices as an active
alarm. A fault indication will be generated if the integrity
check fails.
Automatic Integrity Check (AIC)
When enabled, an automatic integrity check is performed
every 24 hours for all the loop devices. The ASH Module
controls the initiating of the integrity check for each loop
device, one at a time. The AIC is disabled by default and
the start time is configurable within the ASH Apollo editor
in S3. If a device is currently in the middle of an AIC,
and the AIC becomes disabled, that particular device
will conclude its test, but no new test will begin. Manual
integrity check requests are ignored during an AIC, and
if a manual integrity check is in progress when an AIC is
scheduled, the AIC will be delayed.
Manual Integrity Check (MIC)
The manual integrity check can be performed individually
for a single loop device, or globally for all devices on a
single ASH Module.
NOTE
If a manual integrity check is already in progress,
a new request of either an AIC or MIC will be
ignored.
Integrity Check Faults
When an integrity check fails, the loop device fault LED
will be activated. The fault indication will remain until an
ASH Module reset is performed, or until another integrity
check is done, and passes.
NOTE
If there is an active alarm, any new integrity
check request is ignored. If an integrity check is
in progress and an alarm condition occurs, the
integrity check will be interrupted and the alarm
will be annunciated.
WALK TEST
The walk test is intended to verify the operation of the loop
devices. A walk test is activated by physically walking up
to each device, one at a time, and setting them into an
alarm condition. Alternatively, a walk test can be activated
from the ASH Module’s point display within S3. The test
verifies that each device does indeed go into an alarm.
The alarm condition is logged into the EQP Controller, but
the controller takes no further action.
SPECIFICATIONS
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc.
INPUT CURRENT (Maximum)—
690 mA.
LOOP CURRENT (Maximum)—
225 mA.
POWER CONSUMPTION (Maximum)—
11 Watts.
WIRING (Maximum)—
12 AWG 14 AWG 16 AWG 18 AWG
4 mm22.5 mm21.5 mm20.75 mm2
Feet 15500 9800 6200 3900
Meters 4700 3000 1900 1200
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –67°F to +185°F (–55°C to +85°C).
A2536
6.31
(16.0)
4.31
(10.9)
4.56
(11.5)
2.0
(5.08)
Figure 6—Dimensions of the ASH Module in Inches (Centimeters)

5.1
95-8654
7
HUMIDITY RANGE—
5 to 95% RH, non-condensing
DIMENSIONS—
See Figure 6
SHIPPING WEIGHT—
2.7 pounds (1.22 kilograms)
CERTIFICATION —
FM / CSA: Class
I
, Div. 2, Groups A, B, C, D (T4).
Class
I
, Zone 2, Group
II
C (T4)
Tamb = –40°C to +85°C
Electronic assembly must be
installed in a suitable locked NRTL
labeled Type rated enclosure.
ATEX:
II
3 G
Ex nA nC
II
C T4 Gc
DEMKO 10 ATEX 150744X
Tamb = –40°C to +85°C
Compliance with: EN 60079-0:2012
EN 60079-15:2010
Special conditions for safe use:
The EQ3750ASH shall be used in an area of no more
than pollution degree 2 per IEC 60664-1, and in an
enclosure with a tool removal cover that complies with
all relevant requirements of EN 60079-15, rated at least
IP54, and be connected to supply circuits where the
rated voltage cannot be exceeded by 40% caused by
transient disturbances.
The EQ3750ASH may only be installed, connected or
removed when the area is known to be non-hazardous.
The maximum surface temperature inside the EQ3750ASH
does not exceed 130°C.
Transient protection shall be provided that is set at a
level not exceeding 140% of the peak rated voltage
value at the supply terminals to the equipment.
Installation instructions:
For ambient temperatures below –10°C and above
+60°C, use field wiring suitable for both minimum and
maximum ambient temperatures.
The screw terminals are to be tightened with a minimum
torque of 0.5 Nm.
IECEx: ULD 10.0004X
Ex nA nC
II
C T4 Gc
Tamb = –40°C to +85°C
Compliance with: IEC 60079-0:2011
IEC 60079-15:2010
The ASH Module can not be used for
applications that fall within the scope
of the CPD directive.
US Coast Guard: As part of the EQP System. Reference
the EQP instruction manual (95-8533)
for more details.
INSTALLATION
All electrical connections are made to the field wiring
connectors furnished with the module. Refer to Figure 7
for identification of module wiring terminals.
CONFIGURATION
SETTING ASH MODULE NETWORK ADDRESS
One unique network address must be assigned to the
ASH Module. The address is set by the 8 switch DIP
assembly on the module (see Figure 8). The address
is binary coded and is equal to the added value of all
closed switches.
LON
S-LOOP
7
8
9
10
11
12
COM 1 SHLD
COM 1 B
COM 1 A
COM 2 SHLD
COM 2 B
COM 2 A
SHLD
B
A
SHLD
B
A
LON FROM
PREVIOUS DEVICE
LON TO
NEXT DEVICE
LOOP IN
LOOP OUT
P2
P3
P1
SHLD
L1 – IN
L2 + IN
L1 – OUT
L2 + OUT
SHLD
SHLD
L1 –
L2 +
SHLD
L1 –
L2 +
DBG**
13
14
15
16
17
18
19
20
21
COM
RX
TX
POWER
1
2
3
4
5
6
SHLD
–
+
SHLD
–
+
SHLD*
–
+
SHLD*
–
+
24 VDC
INPUT VOLTAGE
24 VDC
INPUT VOLTAGE
EQ3750ASH
*SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES.
**FOR FIELD SERVICE USE ONLY.
B2534
Figure 7—ASH Module Wiring Terminals
FM
APPROVED
®

5.1
95-8654
8
Det-Tronics’ S3Safety System Software is used for device
configuration. For complete configuration details, please
refer to the S3User’s Guide (95-8560).
APOLLO DEVICES
Apollo Discovery and Apollo XP95 detectors and manual
call points have the following specific configurable
parameters that must be set within the Apollo Editor in S3:
Loop Device Type
All the Apollo loop devices supported by the ASH Module
are listed. Once a device has been chosen from the list,
different parameters must be configured based on the
selected device.
Group Address (Sounders)
Sounders and sounder control units may be configured to
operate in a group mode. All the sounders in a particular
group will activate simultaneously, whether continuous
or pulsed. For synchronized evacuation signalling,
approved signalling devices must be connected.
Time Delay
A time delay between 0 and 30 seconds may be
configured for the time an Apollo device must be
continuously in alarm before the controller annunciates
the condition. The alarm must be present for the entire
delay time.
Day/Night Mode
The day/night mode is an option to allow the response
mode (sensitivity) of Apollo detectors to be automatically
adjusted to 1 of 2 values throughout a 24-hour period
(this mode applies to loop device detectors only). This
feature is useful for adjusting detector sensitivity where
occasional time specific interference may occur.
Day mode Start / Stop time
The day/night mode is enabled simply by setting the
day response mode to a different value than the night
response mode. The start and stop times are then set
according to the desired switchover time. At the start
time, the response mode is set to the “Day Mode Start
Time” setting. At the stop time, the response mode is set
to the “Day Mode Stop Time” setting.
If the day response mode value is set equal to the night
response mode, the day/night mode functionality is
effectively disabled. The default value for the start time
is 8:00 AM, and 10:00 PM for the stop time. The start and
stop times are processed in 15-minute increments.
Response modes (Sensitivity)
All Discovery detectors have a sensitivity parameter that
may be set to 1 of 5 different levels. The most sensitive
level is 1, and the least sensitive level is 5. The default
value for both the day response mode and the night
response mode is 3. See the table below for all the
sensitivity levels.
Mode Sensitivity
1 Very High
2 High
3 Medium (Default)
4 Low
5 Very Low
Flashing led mode
The flashing LED mode is a configuration parameter that
is part of Apollo Discovery loop devices. When this mode
is active, the local LEDs on the loop device will flash
when they are polled.
Limitations
In order to prevent current overload, the number of
sounder control modules must be limited to 20 modules.
Loop devices in alarm will have their local LEDs activated.
To limit the amount of current on the loop, the maximum
number of local LEDs that may be active at any one time
is 10.
Inhibit
Using the point display within S3, each Apollo device can
be inhibited individually. Furthermore, using the “Global
Inhibit” function within S3’s device display will inhibit the
ASH Module, causing all devices on an ASH loop to be
inhibited.
Figure 8—Location of Network Address Switches
NETWORK
ADDRESS
SWITCHES

MAINTENANCE
To ensure reliable protection, it is important to check
the ASH Module on a regularly scheduled basis. The
frequency of checks is determined by the requirements
of the particular installation.
REPLACEMENT PARTS
The ASH Module is not designed to be repaired in the
field. If a problem should develop, first carefully check for
proper wiring and programming. If it is determined that
the problem is caused by an electronic defect, the device
must be returned to the factory for repair.
NOTE
When replacing a device, be sure that all rocker
switches on the replacement are set the same
as the original device. Consult the settings
documented during system installation and setup
to determine proper settings for the new device.
Remove power before removing a device or
plugging in a replacement unit. When a device is
replaced with an identical device set to the same
address, conguration is done automatically.
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest local
Detector Electronics office so that the Return Material
Identification (RMI) number can be assigned.
A written statement describing the malfunction
must accompany the returned device or component
to assist and expedite nding the root cause of the
failure.
Pack the unit properly. Always use sufficient packaging
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.
Return all equipment transportation prepaid to the factory
in Minneapolis.
ORDERING INFORMATION
When ordering, please specify:
EQ3750ASH Addressable Smoke
and Heat Module
Refer to the ASH Module Model Matrix for details.
MODEL DESCRIPTION
EQ3750 Addressable Smoke and Heat Module (ASH)
TYPE MOUNTING OPTION
DDin Rail
PPanel Mount*
TYPE APPROVAL AGENCY
WFM/CSA/ATEX/CE/IECEx
*U.S. Coast Guard approved, for use in Marine applications.
For additional information or for assistance in designing
a system to meet the needs of a specific application,
please contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.det-tronics.com
E-mail: det-tronics@det-tronics.com
For information on ordering ASH Module loop field
devices, contact Detector Electronics.

EQUIPMENT SAFETY SYMBOLS
Direct current
Alternating current
Both direct and alternating current
Three-phase alternating current
Earth (ground) current
Protective conductor terminal
Frame or chassis terminal
On (power)
O (power)
Equipment protected throughout
by double insulation or reinforced
insulation
Caution, possibility of electric shock
Caution, hot surface
Caution*
In position of bi-stable push control
Out position of bi-stable push control
Ionizing radiation
Symbol Description
* Manufacturer to state that documentation must be
consulted in all cases where this symbol is marked.

95-8654
X3301 Multispectrum
IR Flame Detector
FlexSonicTM Acoustic
Leak Detector
PointWatch Eclipse®IR
Combustible Gas Detector
FlexVu®Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier®
Safety System
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
Phone: +1 952.941.6665
Toll-free: +1 800.765.3473
Fax: 952.829.8750
det-tronics@carrier.com
Specications subject to change without notice.
All trademarks are the property of their respective owners.
© 2020 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certied to ISO 9001—
the world’s most recognized quality management standard.
Table of contents
Other Det-Tronics Control Unit manuals
Popular Control Unit manuals by other brands

ProFlo
ProFlo PF4001PTD installation instructions

Pickering
Pickering 40-574 user manual

DMP Electronics
DMP Electronics 711S installation guide

BERMAD
BERMAD 42T Installation operation & maintenance

ProSoft Technology
ProSoft Technology ControlLogix inRAx MVI56E-MNETR user manual

National Instruments
National Instruments NI FlexRIO PXIe-7971R Getting started guide