1. 2 95-87693
SYSTEM COMPONENTS
EQP SYSTEM COMPONENTS
The following devices can be used in EQ3900K
enclosures as part of the EAC Approved Eagle
Quantum Premier System:
EQ3XXX - EQP Controller
EQ3700DCIO - Discrete Input/Output Module
EQ3710AIM - Analog Input Module
EQ3720RM - Relay Module
EQ3730EDIO - Enhanced Discrete Input/Output Module
EQ3LTM - LON Termination Module
EQ2100PSM - Power Supply Monitor
EQ2220GFM - Ground Fault Monitor
EQ3750ASH - Addressable Smoke and Heat Module
EQ24EMNE - Network Extender, Panel Mount
Phoenix RS-232/RS-485 - Ethernet Converters
Refer to the Eagle Quantum Premier manual (number
95-8533) for operation details.
The quantity and type of modules are always project
specific per Sales Order and drawing packet supplied
with the order. The I/O allocation may be moved from
factory assigned terminals after notification to Det-
Tronics.
NOTES
1. New inputs/outputs may be wired onto spare
channels after factory notication.
2. One-for-one replacement of failed modules is
permitted.
3. Modications and/or repairs should be performed
by trained personnel only.
OPERATORS
Enclosures may be equipped with selector switches,
pilot lights and push buttons, and panel horns. Contact
Det-Tronics for information regarding model and type
of operators approved for use with EQ3900K series
enclosures. The quantity, type of operators and their
application are always project specific per Sales
Order and drawing packet supplied with the order.
Approved push button quantities for use in
Acknowledge and Silence applications vary depending
on manufacturer. The I/O allocation may be moved
from factory assigned terminals after notification to
Det-Tronics. See Notes 4 and 5 in Figures 1 thru 3 for
configuration change details.
NOTE
Per NFPA 72 requirements, Acknowledge and
silence pushbuttons must be used with
padlocking covers with locks as guards against
unauthorized operations. Padlocking covers are
offered by Det-Tronics and factory installed as
guards with Acknowledge and Silence push
buttons. Locks are not included.
ACTIVATION RELAYS
Five activation relays (two Tyco and three Phoenix
Contact relays) are available for use with the EQP
system. Activation relays are intended for occasional
use. They are typically used for HVAC control where
they become actuated primarily when the protected
area is in an alarm condition. For relay wiring
connections, see Figure 1 for Tyco relays and Figures
2 and 3 for Phoenix Contact relays. Tyco relays can be
installed inside the EQ3900K enclosure, or inside the
customer's provided enclosure at site, while still
connected to I/O modules within the EQ3900K
enclosure. When Tyco relays are located in the
customer's enclosure, installation, wiring and operation
of Tyco relays must meet all requirements of the local
Authority Having Jurisdiction (AHJ). Phoenix Contact
relays are installed only within EQ3900K enclosures.
For additional information regarding relays, see Tyco
product catalog 1308242 or Phoenix Contact product
data sheets 101780-en-02 and 100516-03-en.