Devair PROdry User manual

7610.724.11B 10/01
INSTRUCTION MANUAL
SERVICE DEPARTMENT: (800) 475-5660
PROdry
High Inlet
Temperature
refrigerated
compressed air
dryers
General Safety Information
1. Pressurized devices
This equipment is a pressure containing device.
•Do not exceed maximum operating pressure as
shown on equipment serial number tag.
•Make certain equipment is depressurized before
servicing.
2. Electrical
This equipment requires electricity to operate.
•Install equipment in compliance with national and
local electrical codes.
•Standard equipment is supplied with NEMA 1
electrical enclosures and is not intended for
installation in hazardous environments.
•Disconnect power supply to equipment when per-
forming any electrical service work.
3. Breathing air
•Air treated by this equipment may not be suitable
for breathing without further purification. Refer to
OSHA standard 1910.134 for the requirements for
breathing quality air.
Contents
1.0 INSTALLATION ....................................................... 2
2.0 OPERATION ........................................................... 3
3.0 MAINTENANCE ..................................................... 4
TROUBLESHOOTING GUIDE ........................................... 6
SPECIFICATIONS ......................................................... 7-8
ELECTRICAL SCHEMATICS .............................................. 9
DIMENSIONS AND WEIGHTS ................................... 10-12
PARTS LIST ............................................................. 13-14
WARRANTY ................................................................. 16
TM

2
2. Location in the compressed air system
A. Maximum working pressure - 175 psig,
12.3 kgf/cm 2. Do not exceed unit’s Maximum Working
Pressure.
1) For maximum capacity, install unit in air system at
highest pressure possible (e.g. before pressure
reducing valves)
2) For maximum capacity, install unit at coolest
compressed air temperature possible. Maximum
inlet compressed air temperature: 180 °F, 82°C. If
inlet air exceeds this temperature, precool the air
by extending the piping between the compressor
and the dryer.
B. Air Outlet - Connect air outlet to downstream air lines.
C. By-pass piping - If servicing the unit without interrupt-
ing the air supply is desired, piping should include inlet
and outlet isolation valves and an air by-pass valve.
D. Condensate drain - It is advisable to connect drain
outlet to the condensate drainage system.
NOTE: Drain discharge is at system pressure. Drain line
should be anchored to prevent whipping.
1.4 Electrical connections
A. Dryer is designed to operate on power supply (volt-
age) listed on serial number tag located on the back of
the dryer.
B. Dryer is supplied with an electrical cord. Install in
receptacle of proper voltage.
NOTE: Models 50 and 75 (115v only) - Install plug
in receptacle rated for 20 amps. Units are
supplied with 20 amp plug.
NOTE: Refrigeration system is designed to run continu-
ously and should NOT be wired to cycle on/off with the air
compressor.
IO
e a m e
Ta
Ambient Air Filter
Electrical
Connection
Control
Panel
Air Inlet
Connection
Serial
Number
Tag
Drain
Connection Air Outlet
Connection
Separator and
Integral Filter
kcaBtnorFediStfeL Right Side
Strainer
(shipped
separately)
Drain
Mechanism
Pipe Nipple
1.0 INSTALLATION
1.1 Location
A. Air compressor intake - Locate air compressor so that
contaminants potentially harmful to the dryer are not
drawn into the air system.
B. Free air flow - Do not block either side of the cabinet.
Observe minimum installation clearances as shown.
1.2 Mounting
Dryer is suitable for floor or shelf mounting.
1.3 Piping connections
A. Air Inlet - Connect compressed
air line from air compressor to
air inlet using strainer supplied.
1. Install strainer (included in
shipping carton) prior to
dryer inlet using pipe nipple
supplied or other piping as
required.
NOTE: Observe flow direction arrows on strainer.
NOTE: Install strainer where it is easily accessible for
cleaning.
NOTE: Use vibration dampener, if vibration exists in air line
at inlet to dryer.
24"
12"
wall
6"
36"
Plug

3
2.0 OPERATION
NOTE: Installations above 6000 feet, 1825 meters
Unit is adjusted to operate in altitudes up to 6000 feet,
1825 meters. If unit is installed in an altitude above this,
and has not been preset at the factory for this altitude,
contact Manufacturer’s Service Department.
2.1 Start-up
Start refrigeration system by pushing the on/off switch to
the ON position (depress rocker switch on side marked
“I”).
NOTE: The fault light may illuminate when unit is ener-
gized. Light should go out approximately 5 minutes
after start-up. If light remains lit after 30 minutes or
illuminates after going out, refer to Troubleshooting
Guide.
2.2 Operating check points
Check the following on a periodic basis:
A. Rocker switch is in the ON position.
B. Amber fault light is out.
C. Condensate is being regularly discharged.
2.3 Minimum/maximum operating conditions
A. Minimum/Maximum air pressure: 20/175 psig,
1.4/12.3 kgf/cm 2
B. Maximum inlet air temperature: 180 °F, 82°C
C. Minimum/Maximum ambient temperature:
35/110°F, 2/43 °C
Control Panel
I
O
On/Off Switch Fault Light
2. For dryers with an aftercooler installed upstream
Flow capacity in scfm (m 3/min) @ 100 °F, 38°C inlet
temperature, 100 °F, 38°C inlet pressure dew point,
100°F, 38°C ambient temperature, 50 °F, 10°C outlet
pressure dew point, and less than 10 psi, 0.7 kgf/cm 2
pressure drop.
175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0)
20 23 (0.65) 22 (0.62) 20 (0.57) 18 (0.51)
25 29 (0.82) 27 (0.76) 25 (0.71) 23 (0.65)
35 41 (1.16) 38 (1.08) 35 (0.99) 32 (0.91)
Model 50 58 (1.64) 54 (1.53) 50 (1.42) 45 (1.27)
75 87 (2.46) 81 (2.29) 75 (2.12) 68 (1.93)
100 116 (3.29) 108 (3.06) 100 (2.83) 91 (2.58)
125 145 (4.12) 135 (3.82) 125 (3.54) 114 (3.23)
D. Maximum flow capacity
1. For dryers without an aftercooler installed upstream
Flow capacity in scfm (m 3/min) @ 180 °F, 82°C inlet
temperature, 160 °F, 71°C inlet pressure dew point,
95°F, 35°C ambient temperature, 50 °F, 10°C outlet
pressure dew point, and less than 5 psi, 0.35 kgf/cm 2
pressure drop.
175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0)
20 20 (0.57) 18 (0.51) 17 (0.48) 15 (0.42)
25 24 (0.68) 23 (0.65) 21 (0.59) 19 (0.54)
35 31 (0.88) 29 (0.82) 27 (0.76) 24 (0.68)
Model 50 58 (1.64) 54 (1.53) 50 (1.42) 45 (1.27)
75 71 (2.01) 66 (1.87) 61 (1.73) 55 (1.56)
100 97 (2.75) 90 (2.55) 83 (2.35) 76 (2.15)
125 121 (3.43) 112 (3.17) 104 (2.95) 95 (2.69)
50 HZ
60 HZ
60 HZ
50 HZ
Inlet Pressure
psig (kgf/cm2)
Inlet Pressure
psig (kgf/cm2)
175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0)
20 32 (0.91) 30 (0.85) 28 (0.79) 25 (0.71)
25 40 (1.13) 37 (1.05) 34 (0.96) 31 (0.88)
35 55 (1.56) 51 (1.44) 47 (1.33) 43 (1.22)
Model 50 78 (2.21) 73 (2.07) 67 (1.90) 61 (1.73)
75 118 (3.34) 110 (3.12) 102 (2.89) 92 (2.61)
100 157 (4.45) 146 (4.14) 136 (3.85) 123 (3.48)
125 197 (5.58) 183 (5.18) 170 (4.82) 155 (4.39)
Inlet Pressure
psig (kgf/cm2)
175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0)
20 27 (0.76) 25 (0.71) 23 (0.65) 21 (0.59)
25 33 (0.93) 31 (0.88) 29 (0.82) 26 (0.74)
Model 35 43 (1.22) 40 (1.13) 37 (1.05) 33 (0.93)
50 78 (2.21) 73 (2.07) 67 (1.90) 61 (1.73)
75 96 (2.72) 90 (2.55) 83 (2.35) 75 (2.12)
100 131 (3.71) 122 (3.46) 113 (3.20) 102 (2.89)
125 164 (4.65) 152 (4.31) 142 (4.02) 129 (3.65)
Inlet Pressure
psig (kgf/cm2)

4
3.0 MAINTENANCE
DRYER IS A PRESSURE CONTAINING DEVICE.
DEPRESSURIZE BEFORE SERVICING.
3.1 Ambient air filter- Clean accumulated dust and dirt
from ambient air filter monthly or more often if air
flow across the condenser is impeded.
A. Remove top panel.
B. Remove ambient air filter by sliding upwards.
C. Wash with soap and water and allow to dry before re-
installing.
NOTE: Do not use solvents to clean ambient air filter.
D. Reinstall filter and top panel.
3.2 Inlet strainer- clean inlet strainer monthly or more
often if rapid clogging occurs.
A. Shut-off compressed air supply to the strainer
and depressurize.
B. Remove screen and clean or replace.
C. Reinstall.
Screen
3.3 Replace separator/filter element yearly or
more often if pressure drop across the dryer
is excessive.
A. Shut-off compressed air supply to the dryer and
depressurize.
B. Remove top panel.
C. Remove two screws holding side panel and remove
side panel by sliding upwards.
D. Disconnect drain tube from bulkhead fitting
in cabinet base. To remove, press the plastic
collar in, toward the fitting, while pulling the tube out
of the fitting.
E. Remove bowl - push bowl up, turn bowl 1/8th turn to
your left, and pull straight down.
F. Clean filter bowl.
G. Replace element.
1. Replacing complete element
a) Pull off old element and discard.
b) Make certain O-ring inside top of
replacement element is in place and push
element onto filter head.
2. Replacing sleeve only
a) Pull element straight down to remove.
b) Remove bolt and bottom cap and remove
disposable filter sleeve.
c) Clean separator core with soap and water
if necessary
d) Slide new filter sleeve over separator core and
replace bottom cap and hand tighten bolt.
e) Make certain O-ring inside top of element is in
place and push element onto filter head.

5
H. After making sure that O-ring and wave spring inside
top of bowl are in place, reassemble bowl to head.
NOTE: Make certain O-ring is generously lubricated
NOTE: Wave spring ends should be pointed down
to prevent the wave spring from interfering
with reassembly.
I. Reconnect drain tube to bulkhead fitting by pushing
tube into fitting until it locks in position.
J. Reinstall side and top panels.
K. Repressurize dryer and resume operation.
Element o-ring Separator Element
Bowl o-ring
Drain Mechanism
Wave Spring
Tube
Hose
Barb
3.4 Automatic condensate drain
•Check daily to be sure automatic drain is
discharging.
•Replace drain mechanism yearly.
A. Shut-off compressed air supply to the dryer
and depressurize.
B. Remove top panel.
C. Remove two screws holding side panel then
remove side panel by sliding upwards.
D. Disconnect drain tube from bulkhead fitting in
cabinet base. To remove, press the plastic collar in,
toward the fitting, while pulling the tube out of the
fitting.
E. Remove bowl - push bowl up, turn 1/8th turn to
your left, and pull bowl straight down.
F. Remove drain tube fitting from bottom of bowl.
G. Remove old drain mechanism by turning knurled
fitting to the right (clockwise) and remove.
H. Install new drain mechanism. If necessary, use a
wire or pencil to guide the new mechanism into
place.
I. Reassemble drain tube fitting to bowl.
J. After making sure that large O-ring in filter head is
in place, reassemble bowl to head.
K. Reconnect drain tube to bulkhead fitting by
pushing tube into fitting until it locks in position.
L. Reinstall top and side panels.
M. Repressurize dryer and resume operation.

6
TROUBLESHOOTING GUIDE
C) Fault Alarm
A) Water downstream of dryer 1. Residual free moisture remaining in
downstream pipelines
2. Air by-pass system is open
3. Inlet and Outlet connections are
reversed
4. Temperatures surrounding air lines
downstream of dryer have dropped
below dryers dew point rating.
5. Excessive free moisture (bulk liquid)
at dryer inlet
6. Condensate not being automatically
drained
Drain mechanism is clogged or
inoperative.
Drain line is restricted or frozen.
7. Dryer overloaded resulting in
elevated dew point.
8. Refrigeration system not functioning
properlyresulting in elevated dew
point.
1. Inlet air strainer clogged
2. Excessive air flow
3. Separator filter clogged.
4. Freezing of moisture in evaporator
because of refrigeration system
improperly functioning.
1. Dryer overloaded resulting in high
air outlet temperature.
2. Refrigeration system not function-
ing properly resulting in high air
outlet temperature.
3. Unit functioning normally but
thermostatic switch is malfunction-
ing or not securely mounted.
Blow out system with dry air
Check valve positions
Check for correct connection
Insulate or heat trace air lines exposed
to low ambients or dry air to lower
dew point
Install separator ahead of dryer
B) High pressure drop across
dryer
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
Replace drain mechanism if inoperative
Open drain line
Check inlet air temperature and
pressure, flow rate (compressor
capacity) and ambient air temperature
See D below
Clean inlet air strainer
Check flow rate
Replace filter sleeve
See D below
See A 7
See D below
Contact qualified refrigeration repair-
man or manufacturer’s service depart-
ment
Check power to unit
Close disconnect switch
Check for continuity
Have electrician check electrical
connections
Check minimum/maximum tempera-
ture ranges
Clean ambient air filter
Clean condenser
Replace fan motor or fan control
switch
Contact qualified refrigeration repair-
man or manufacturer's service depart-
ment
Check wiring
D) Refrigeration system not
functioning properly
1. When dryer on/off switch in on or
"I" position
2. Refrigerant compressor cycles on
and off
a. Power failure
b. Line disconnect switch open
c. Blown fuses, open breaker
d. Faulty wiring, loose terminals
a. High or low ambient conditions
b. Ambient air filter clogged
c. Condenser fins clogged
d. Fan motor or fan control switch
malfunction
e. Refrigerant leak
f. Low voltage

7
SPECIFICATIONS- Models 20 thru 75
ledoMnoitpircseD
20 25 35 50 75
Operating Conditions
Rated Capacity scfm 60 / 50 Hz 20 / 17 25 / 21 35 / 27 50 / 50 75 / 61
@125 psig, 8.8 kgf/cm 2* m 3/min 60 / 50 Hz 0.57 / 0.48 0.71 / 0.59 0.99 / 0.76 1.42 / 1.42 2.12 / 1.7
mc/fgk3.21(gisp571erusserPgnikroWmumixaM 2)
081erutarepmeTtelnImumixaM �F (82�C)
011-53erutarepmeTtneibmA.xaM/niM �F (2-43�C)
Pressure Drop @ psi 60 / 50 Hz 4.5 / 2.9 3.3 / 2.4 4.7 / 2.9 4.5 / 4.5 3.8 / 2.2
rated capacity (kgf/cm 2)60 / 50 Hz (0.32 / 0.20) (0.23 / 0.17) (0.33 / 0.20) (0.32 / 0.32) (0.27 / 0.15)
Refrigeration System Data
roticapaCtilpStnenamreP,yratoR,citemreHepyTrosserpmoC
BTU/HR - Refrigeration Only
@ ASRE-T Conditions 60 / 50 Hz 6800 / 5500 6800 / 5500 6800 / 5500 12850 / 10100 12850 / 10100
Outlet Air Temperature
551)snoitidnocdetar@lanimon( �F (68�C)
Refrigerant Type R-407C
Refrigerant Charge oz (grams) 60 / 50 Hz 11.0 (312) 12.0 (340) 12.0 (340) 18.0 (510) 20.5 (581)
mc/fgk7.4(gisp76gnitteSerusserPnoitcuS 2)
Factory Test (design) Pressure
mc/fgk5.21/2.32(gisp871/033ediswol/edishgih 2)
mc/fgk7.21-9.61(gisp081-042)tuo-ni(gnitteShctiwSnaFresnednoC 2)
Air Flow Across Condenser cfm 60 / 50 Hz 280 / 235 280 / 235 280 / 235 620 /515 620 / 515
(m 3/min) 60 / 50 Hz (7.9 / 6.7) (7.9 / 6.7) (7.9 / 6.7) (17.6 / 14.6) (17.6 / 14.6)
Electrical Data
Unit 115/1/60
VAC/phase/Hz 115/1/60
Minimum/maximum volts 98-127
0.310.319.79.79.7)ALF(SpmAdaoLlluF
0202515151)spma(eziSesuFtiucriChcnarB
Compressor
Volts/phase/Hz 115/1/60
1.111.117.67.67.6)ALR(spmadaoLdetaR
0.360.360.730.730.73)ARL(spmarotoRdekcoL
05210521546546546)tupni(sttaW
Overload Thermal and Current (Auto Reset)
Condenser fan motor
53/1/51153/1/51152/1/51152/1/51152/1/511)tuptuo(sttaW/esahp/stloV
6.16.12.12.12.1)ALF(spmAdaoLlluF
Other Loads
2.0/200.0/5112.0/200.0/5112.0/200.0/5112.0/200.0/5112.0/200.0/511sttaW/spma/stloV
Unit 220-240/1/50
VAC/phase/Hz 220-240/1/50
Minimum/maximum volts 198-264
0.60.65.35.35.3)ALF(spmAdaoLlluF
5151515151)spma(eziSesuFtiucriChcnarB
Compressor
Volts/phase/Hz 220-240/1/50
1.51.59.29.29.2)ALR(spmadaoLdetaR
0.820.820.410.410.41)ARL(spmarotoRdekcoL
099099045045045)tupni(sttaW
Overload Thermal and Current (Auto Reset)
Condenser fan motor
6.52/1/042-0226.52/1/042-0223.81/1/042-0223.81/1/042-0223.81/1/042-022)tuptuo(sttaW/esahp/stloV
8.08.06.06.06.0)ALF(spmAdaoLlluF
Other Loads
4.0/200.0/042-0224.0/200.0/042-0224.0/200.0/042-0224.0/200.0/042-0224.0/200.0/042-022sttaW/spma/stloV
*Capacity @ 180°F, 82°C inlet temperature. 160°, 71°C inlet pressure dew point, 95°F, 35°C ambient temperature, 50°F, 10°C outlet
pressure dew point, and less than 5 psi. 0.35 kgf/cm pressure drop.
°
2

8
SPECIFICATIONS-Models 100 and 125
ledoMnoitpircseD
100 125
Operating Conditions
Rated Capacity scfm 60 / 50 Hz 100 / 83 125 / 104
@125 psig, 8.8 kgf/cm 2* (m 3/min) 60 / 50 Hz (2.83 / 2.35) (3.54 / 2.95)
mc/fgk3.21(gisp571erusserPgnikroWmumixaM 2)
081erutarepmeTtelnImumixaM °F (82°C)
011-53erutarepmeTtneibmA.xaM/niM °F (2-43°C)
Pressure Drop @ psi 60 / 50 Hz 3.5 / 2.6 4.6 / 3.1
rated capacity (kgf/cm 2)60 / 50 Hz (0.25 / 0.18) (0.32 / 0.22)
Refrigeration System Data
roticapaCtilpStnenamreP,yratoR,citemreHepyTrosserpmoC
BTU/HR - Refrigeration Only
@ ASRE-T Conditions 60 / 50 Hz 25100 / 20385
Outlet Air Temperature
551)snoitidnocdetar@lanimon( °F (68°C)
C704-RepyTtnaregirfeR
Refrigerant Charge oz (grams) 60 / 50 Hz 30 (851) 31 (880)
mc/fgk17.4(gisp76gnitteSerusserPnoitcuS 2)
Factory Test (design) Pressure
mc/fgk5.11/2.22(gisp361/513ediswol/edishgih 2)
mc/fgk7.21-9.61(gisp081-042)tuo-ni(gnitteShctiwSnaFresnednoC 2)
Air Flow Across Condenser cfm 60 / 50 Hz 830 / 690
(m 3/min) 60 / 50 Hz (23.5 / 19.5)
Electrical Data
Unit 208-230/1/60
06/1/032zH/esahp/CAV
352-781stlovmumixam/muminiM
Full Load Amps (FLA) 13.3
02)spma(eziSesuFtiucriChcnarB
Compressor
06/1/032-802zH/esahp/stloV
Rated Load amps (RLA) 12.2
Locked Rotor amps (LRA) 65.8
0932)tupni(sttaW
)teseRotuA(tnerruCdnalamrehTdaolrevO
Condenser fan motor
06/1/032)tuptuo(sttaW/esahp/stloV
Full Load Amps (FLA) 1.1
Other Loads
4.0/200.0/032sttaW/spma/stloV
Unit 220-240/1/50
05/1/042-022zH/esahp/CAV
462-891stlovmumixam/muminiM
Full Load Amps (FLA) 10.7
51)spma(eziSesuFtiucriChcnarB
Compressor
05/1/042-022zH/esahp/stloV
Rated Load amps (RLA) 9.6
Locked Rotor amps (LRA) 48.5
0991)tupni(sttaW
)teseRotuA(tnerruCdnalamrehTdaolrevO
Condenser fan motor
05/1/032)tuptuo(sttaW/esahp/stloV
Full Load Amps (FLA) 1.1
Other Loads
4.0/200.0/042-022sttaW/spma/stloV
* Capacity @ 180°F, 82°C inlet temperature, 160°F, 71°C inlet pressure dew point, 95°F,
35°C ambient temperature, 50°F, 10°C outlet pressure dew point, and less
than 5 psi, 0.35 kgf/cm
2pressure drop.

9
ELECTRICAL SCHEMATICS
Models 20 thru 75 - All Voltages
Only Models 50 and 75 - 115-1-50/60
Only Models 50 and 75 - 115-1-50/60
3
LINE
SW
G
1
2
3
3
4
A
TEMPERATURE
FPS
8
FM
CONDENSER
FAN MOTOR
4
RC
HTS
7
5
M
LT
R
C S
6
REFRIGERANT
COMPRESSOR
4
4
HIGH
4
WIRING SCHEMATIC
Models 100 and 125 - All Voltages
FPS
TB
HTS
FM
OLT
LT
SW
M
Front of Dryer
(Outside)
Right Side of Dryer
(Inside)
COMPONENT LOCATIONS
RC
Models 20 thru 125 - All Voltages
LT
SW
FPS
CT
HTS
FM
OLT
M
RC
Front of Dryer
(Outside)
Right Side of Dryer
(Inside)
COMPONENT LOCATIONS
LEGEND
SW - On/Off Switch
OLT - Thermal Overload
M - Compressor Motor
RC - Run Capacitor
HTS - High Temperature Switch
LT - Fault Light
FPS - Fan Pressure Switch
FM - Fan Motor
TB - Terminal Block
CT - Contactor w/115V Coil
Only Models 50 and 75 - 115-1-50/60
TEMPERATURE
CONDENSER
FAN MOTOR
REFRIGERANT
COMPRESSOR
HIGH
NEMA 5-20P
PLUG 20A, 125V

10
DIMENSIONS AND WEIGHTS
Models 20, 25, 35
Model Weight
20 79 lbs (36 kg)
25 80 lbs (36 kg)
35 81 lbs (37 kg)
718 mm
317 mm
105mm
1.9/16 "
40mm
5mm 217 mm
1" 25 mm
6mm
257mm
5.1/16 "
128 mm
257mm
216mm
41mm
130mm
105mm
287mm
1.1/2"
38mm
168mm
21mm
327 mm

11
DIMENSIONS AND WEIGHTS
Models 50 and 75
Model Weight
50 150 lbs (68 kg)
75 155 lbs (70 kg)
933mm
117mm
1.1/2"
38mm
429mm
5mm
419mm
25mm
21mm
15 1/4"
387mm
8 7/16"
213mm
425mm
6mm
129mm
39mm
175mm
160mm
232mm
59mm

12
DIMENSIONS AND WEIGHTS
Models 100 and 125
Model Weight
100 187 lbs (85 kg)
125 189 lbs (86 kg)
1"
1"

Maintenance Kits
For Dryer Models Kit Number
20, 25, 35 4KMTIH
50 HITMK6
75 HITMK5
13
PARTS LIST
PARTS DESCRIPTION 20 25 35 50 75
Separator
*Separator/Filter Cartridge E9-16 E9-16 E9-16 E9-20 E9-24
42-9S02-9S61-9S61-9S61-9SeveelSretliF
80-0714.5080-0714.5080-0714.5080-0714.5080-0714.50msinahceMniarD*
60-0180.3050-0180.3040-0180.3040-0180.3040-0180.30lwoB
61.255.023961.255.023941.255.023941.255.023941.255.0239lwoBgnir-O*
Inlet (Compressed Air) Strainer
2.537.13742.537.13741.537.13741.537.13741.537.1374telni,reniartS
7.537.13747.537.13745.537.13745.537.13745.537.1374reniarts,neercS*
Electrical
7.607.01167.607.01167.607.01167.607.01167.607.0116ffo/nohctiwS
Light, Fault (amber) 115/1/60 6350.451.10 6350.451.10 6350.451.10 6350.451.10 6350.451.10
Light, Fault (amber) 220-240/1/50 6350.451.11 6350.451.11 6350.451.11 6350.451.11 6350.451.11
Cord Set 115/1/60 03.7133-10 03.7133-10 03.7133-10 03.7133-11 03.7133-11
Cord Set 230/1/60 03.7133-24 03.7133-24 03.7133-24 03.7133-25 03.7133-25
Cord Set 220-240/1/50 03.7133-12 03.7133-12 03.7133-12 03.7133-12 03.7133-12
Capacitor, run 115/1/60 5910.103.17 5910.103.17 5910.103.17 5910.103.13 5910.103.13
Capacitor, run 220-240/1/50 5910.103.18 5910.103.18 5910.103.18 5910.103.49 5910.103.50
Capacitor, run 208-230/1/60 5910.103.18 5910.103.18 5910.103.18 5910.103.49 5910.103.49
Overload, Compressor 115/1/60 5925.571.12 5925.571.12 5925.571.12 5925.571.15 5925.571.15
Overload, Compressor 208-230/1/60 5925.571.13 5925.571.13 5925.571.13 5925.571.16 5925.571.16
Overload, Compressor 220-240/1/50 5925.571.14 5925.571.14 5925.571.14 5925.571.14 5925.571.14
Switch, fault light w/conn. 03.7419-02 03.7419-02 03.7419-02 03.7419-03 03.7419-03
Condenser Fan
Fan Motor 115/1/60 6105.226.2 6105.226.2 6105.226.2 6105.226.7 6105.226.7
Fan Motor 220-240/1/50 6105.226.4 6105.226.4 6105.226.4 6105.226.9 6105.226.9
Fan Motor 208-230/1/60 6105.226.4 6105.226.4 6105.226.4 6105.226.9 6105.226.9
Fan Blade 115-1-60 6105.378.2 6105.378.2 6105.378.2 6105.378.4 6105.378.4
Fan Blade 208-240-1-50/60 --- --- --- 6105.378.6 6105.378.6
Refrigeration System
Compressor 115/1/60 4130.106.67 4130.106.67 4130.106.67 4130.106.70 4130.106.70
Compressor 208-230/1/60 4130.106.68 4130.106.68 4130.106.68 4130.106.71 4130.106.71
Compressor 220-240/1/50 4130.106.69 4130.106.69 4130.106.69 4130.106.72 4130.106.72
51.211.031451.211.031431.211.031431.211.031431.211.0314resnednoC
Hot gas by-pass valve 4130.690.21 4130.690.21 4130.690.21 4130.690.22 4130.690.22
21.561.031421.561.031421.561.031421.561.031421.561.0314reyrD/retliF
Fan Pressure Switch 4130.139.21 4130.139.21 4130.139.21 4130.139.21 4130.139.21
Cabinet
4.332.06444.332.06443.332.06443.332.06443.332.0644riAtneibmA,retliF*
Grommet (light & switch, front panel) 9320.302.11 9320.302.11 9320.302.11 9320.302.11 9320.302.11
2.032.03392.032.03392.032.03392.032.03392.032.0339gnitnuom,tooF
* Maintenance kits for the above models are available "*" indicates items included in the kits.

PARTS LIST
PARTS DESCRIPTION 100 125
Separator
*Separator/Filter Cartridge E9-24 E9-24
42-9S42-9SeveelSretliF
80-0714.5080-0714.50msinahceMniarD*
60-0180.3060-0180.30lwoB
61.225.023961.225.0239gnir-O*
3.537.13743.537.1374telni,reniartS
8.537.13748.537.1374reniarts,neercS*
Electrical
7.607.01167.607.0116ffo/nohctiwS
11.154.053611.154.0536v032tluaF,thgiL
52-3317.3052-3317.30teSdroC
Capacitor, run 230/1/60 5910.103.50 5910.103.50
Capacitor, run 220-240/1/50 5910.103.13 5910.103.13
Switch, fault light w/conn. 03.7419-03 03.7419-03
Condenser Fan
9.622.50169.622.5016rotoMnaF
5.873.50165.873.5016edalBnaF
Refrigeration System
Compressor 230/1/60 4130.106.73 4130.106.73
Compressor 220-240/1/50 4130.106.74 4130.106.74
91.211.031491.211.0314resnednoC
Hot gas by-pass valve 4130.690.22 4130.690.22
21.561.031421.561.0314reyrD/retliF
Fan Pressure Switch 4130.139.21 4130.139.21
Cabinet
6.332.06446.332.0644riAtneibmA,retliF*
Grommet (light & switch, front panel) 9320.302.11 9320.302.11
2.032.03392.032.0339gnitnuom,tooF
* Maintenance kits for the above models are available "*" indicates
items included in the kits.
Maintenance Kits
For Dryer Models Kit Number
B3KMDR001
B3KMDR521
14

NOTES
15

SERVICE DEPARTMENT: (800) 475-5660
M & S Service Co. Inc.
739 Airway Drive, Allegan, MI 49010
Tel: (800) 475-5660
Warranty
The manufacturer warrants the product manufactured by it, when properly installed, operated, applied and
maintained in accordance with procedures and recommendations outlined in the manufacturer’s instruction manuals,
to be free of defects in material and workmanship for a period of one (1) year from date of purchase at the retail level
by the end user, not to exceed eighteen (18) months from the date of manufacture, provided such defect is
discovered and brought to the manufacturers attention within the aforesaid warranty period.
The manufacturer will repair or replace any product or part determined to be defective by the manufacturer within
the warranty period, provided such defect occurred in normal service and not as the result of misapplication, misuse,
abuse, neglect, incorrect maintenance, accident, or normal wear. Normal maintenance items requiring routine
replacement are not warranted.
The warranty covers parts and labour for the warranty period. Repair or replacement shall be made at the sole option
of the manufacturer. Any service performed on the product by anyone other than the manufacturer must first be
authorized by the manufacturer. Unauthorized service voids the warranty and any resulting charge or subsequent
claim will not be paid.
Products repaired or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to
the original product, based on the original date of purchase and/or date of manufacture, as outlined above.
There is no other expressed warranty. Implied warranties including those of merchantability and fitness for a particular
purpose are limited to one (1) year from date of purchase to the extent permitted by law and any and all implied
warranties are excluded. This is the exclusive remedy. Liability for consequential damages under any and all warranties
are excluded to the extent exclusion is permitted by law.
This warranty gives you specific legal rights, and you may also have other rights within your jurisdiction.
This warranty does not cover:
1. Merchandise that has become inoperative because of ordinary wear, misuse, negligence, accident, or improper
and unauthorized repair or alteration.
2. Costs occasioned by the removal, replacement, or repair of merchandise (other than by Devair) without
previous written authorization.
3. Expenses incurred in travel or lodging beyond a 40 kilometer (25 mile) distance from the nearest Devair
Authorized Service Centre, unless approved by Devair in advance.
4. Products, parts, materials, components, or accessories manufactured by others or supplied in connection with
the sale of the manufacturers products.
5. Repair and transportation costs of merchandise determined not to be defective under the terms and
conditions of this warranty.
All decisions by Devair Inc. with regard to this policy shall be final. Devair will not be responsible for any claimed
defective materials returned other than in accordance with this statement of policy or without our prior authorization.
Table of contents
Other Devair Dryer manuals