Diginet DGEMSR360P2 Manual

User and Installation Guide DGEMSR360Px
DIGINET.NET.AU
Recessed Flush Mount 360oPIR Presence Sensor
Designed in Australia to meet Australian Standards and installation conditions.
PATENT PENDING/REGISTERED DESIGN

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 2of 16
Diginet Control Systems Pty Ltd
ABN –89 095 788 864
96-112 Gow Street
Padstow NSW 2211
PO Box 314
Padstow NSW 2211
Contact
Fax: 1300 95 3257
A member of the Gerard Lighting Group
Disclaimer
Diginet Control Systems Pty Ltd (Diginet) reserves the right to alter the specifications, designs or other features of
any items and to discontinue any items at any time without notice and without liability. While every effort is
made to ensure that all information in this user and installation guide is correct, no warranty of accuracy is given
and Diginet shall not be liable for any error.
Trademarks
The identified trademarks and copyrights are the property of Diginet Control Systems Pty Ltd unless otherwise
noted.
Copyright
This user and installation guide is copyright to Diginet Control Systems Pty Ltd. Except as permitted under
relevant law, no part of this user and installation guide may be reproduced by any process without written
permission of and acknowledgement to Diginet.
V1.0 April 2013

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 3of 16
Table of Contents
1. Product Item.........................................................................................................................................................4
2. Important Notes and Safety Information .............................................................................................................4
3. Product Summary .................................................................................................................................................4
4. Product Capabilities..............................................................................................................................................4
5. Installation and Wiring Connections ....................................................................................................................5
5.1. Control Module.....................................................................................................................................................5
5.2. Override ‘OFF’.......................................................................................................................................................6
5.3. Sensor Head..........................................................................................................................................................7
6. Operation and Configuration................................................................................................................................8
7. Presence/Occupancy Detection ...........................................................................................................................9
8. Power Surges ......................................................................................................................................................11
9. Insulation Resistance Testing .............................................................................................................................11
10. Product Specifications ........................................................................................................................................11
11. Standards and Compliance.................................................................................................................................13
12. Product Warranty ...............................................................................................................................................14

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 4of 16
1. Product Item
This guide provides installation and configuration information for the Diginet recessed flush mount 360 degree
passive infrared (PIR) presence sensor with one and two channel 16A control modules.
Table 1 - DGEMSR360Px part numbers and components
Package Version
Sensor Head
Control Module
DGEMSR360P1
ILSM02-D 360oPIR Sensor
ILSCM01-D, 1 Channel 16A (screw terminals)
DGEMSR360P2
ILSM02-D 360oPIR Sensor
ILSCM02-D, 2 Channel 16A (screw terminals)
2. Important Notes and Safety Information
WARNING –Electric shock may result in serious injury or death. Follow all warnings in this guide and on the
product while working in accordance with the latest electrical safety practices.
The installer must be suitably qualified and should work in accordance with standard safety procedures
for mains-powered electrical equipment.
There are no user serviceable parts inside the sensor head or control module. Do not attempt to
disassemble or operate the presence sensor with any covers removed.
The presence sensor is intended for indoor use only.
Consult the manufacturer’s instructions for loads connected to the control module output terminals.
If you require information or assistance regarding the installation, configuration, or operation of the presence
sensor, contact Technical Services at Diginet Control Systems. Contact details are on the back cover of this guide
and at www.diginet.net.au.
3. Product Summary
The presence sensor package consists of two items: a small 360 degree passive infrared (PIR) sensor head and a
control/relay module.
The sensor head is recessed into ceilings and has a low profile trim and opaque dome lens for sensing movement
across short and long range plus ambient light level. Adjustment sliders for time and light level are discreetly
hidden in the patented sensor head which pops out providing configuration after installation without any tools.
One and two channel control modules for switching loads are slim line and easily fit into the ceiling space through
the sensor head aperture.
4. Product Capabilities
Designed for both minor and major movement, the sensor head has 864 fields of view (FOV) ensuring reliable
operation up to 7m diameter in different applications (e.g. office or corridor installations). Time delay range is 5
min to 25 min plus a walk test setting of 5 seconds.
Control modules are rated at 16A for switching inductive/capacitive loads with volt free relays. The 2 channel
model provides a run-on feature whereby Relay 2 will switch off 5 minutes after the time delay expires.
Both control modules have a switch input that allows for manual override off control of the Relay 1 output.

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 5of 16
5. Installation and Wiring Connections
Installing the presence sensor requires a cut-out in the plasterboard ceiling to mount the sensor head and
adequate clearance to fit the control module up through the hole if there is no ceiling space access.
The sensor head connects to the control module using the supplied 5 core cable with pre-terminated connector.
Note: The presence sensor must be installed/connected by a suitably qualified person and it is the
responsibility of the installer to ensure it is completed in accordance with local wiring regulations.
5.1. Control Module
Using a screwdriver, lever the terminal cover on both sides to remove from the housing. Each of the terminals in
the control module accommodates 2x1.5mm2or 1x2.5mm2conductors. Figure 1 details the recommended cable
strip lengths for terminating TPS cable to the control module.
10 - 15mm
6 - 7mm
Conductors
Double
Insulated
Figure 1 –Conductor strip lengths for control module termination.
The one channel control module has two terminals labelled “Loop”. These terminals have no electrical connection
internally and may be used as spare terminals if required. Figures 2 and 3 detail the electrical connections
required for the one and two channel control modules respectively.
Loop 2
Loop 1
S 1
S 2
N
A/L
R1
Load
Active - any phase and/or circuit
See Section 5.2 for override
switch connections
Switched Active
Neutral
Active
Neutral
Figure 2 –DGEMSR360P1 electrical connections (ILSCM01-D one channel module).

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 6of 16
R1
R2
N
A/L
S 2
S 1
Load 1
Load 2
Active –any phase and/or circuit
Active –any phase and/or circuit
Switched Active
Switched Active
See Section 5.2 for override
switch connections
Neutral
Active
Neutral
Neutral
Figure 3 –DGEMSR360P2 electrical connections (ILSCM02-D two channel module).
5.2. Override ‘OFF’
The presence sensor has an override ‘OFF’ function that is activated by an external switch connected to the
control module. This function only operates Relay 1 for both one and two channel control modules. Relay 2 in the
two channel model will continue to operate under presence detection mode.
The override switch has two methods of connection: dry contact switch input across both terminals to make a
closed circuit or a switched active input. A latched contact/switch (not momentary/push button) must be used in
both methods. Refer to Figure 4 for the electrical connections of the two methods for operating the override
function.
Note: Terminals S1 and S2 require a consistent polarity if installing one or more switches to a single
or multiple control modules.
Active
(same circuit as A/L)
n/c
Dry contact
S 2
S 1
S 2
S 1
Latched contact / switch
Figure 4 –Override ‘OFF’ switch connection options.

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 7of 16
5.3. Sensor Head
The sensor head is designed to be installed in plasterboard ceiling or ceiling tiles with a thickness of 10mm -
16mm thickness. A 52mm diameter cut-out is required to recess mount the sensor head. Figure 5 shows a cross
section of the sensor head installation. A cut-out template is on the presence sensor box for ease of making the
cut-out.
Figure 5 –Installation cross section of sensor head installed in plasterboard ceiling or ceiling tile.
Note: Avoid placing the sensor in positions close to hot or cold air vents and where the field of view
extends through doorways. This will reduce the risk of false triggering of the sensor.
The sensor head should be connected to the control module prior to pushing into the ceiling cut-out. Using a
screw driver, lift the tab on the control module (refer to Figure 6) to expose the 5 pin connector for the sensor
head. Using the supplied 5 core cable with pre-terminated connector, plug the sensor head onto the connector
and close the tab, ensuring the cable is gripped properly. The sensor head cable length is 450mm and if required,
can be extended to a maximum length of 1 metre.
Figure 6 –Lift tab to connect the sensor head to the control module.
Minimum 10mm
plaster board

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 8of 16
6. Operation and Configuration
Upon power-up the sensor performs an initialisation which will take approximately 45 secs. During this period the
relay will close and open forcing the connected load to turn on and off. Once the initialisation has completed,
normal operation commences at which full sensitivity is reached after a period of 5 mins.
When the presence sensor is powered and functional, green and red LEDs within the sensor head will indicate
mode/operation as defined in Table 2.
Table 2 –LED indicators for each of the operational conditions
Mode
LED Indicator
Condition
Normal Operation
Green LED OFF
Ambient light below threshold setting
Green LED ON
Ambient light above threshold setting
Red LED ON
Manual override activated
Walk Test Mode*
Green LED “Flashing”
Ambient light above threshold setting
Red LED “Flashing”
Movement detected
*Override mode is disabled during walk test mode.
The time delay and light level threshold settings are easily configured after installation by using the patented push
in-pop out mechanism as detailed in Figures 7 and 8.
Figure 7 - Press gently on the lens until a click is heard then release to access sensor adjustment sliders
Figure 8 - Press gently on the head until click is heard to return to normal operating position.
As shown in Figure 8, the adjustable sliders for time delay and light level threshold are accessed when the sensor
head is in the out position. Tables 3 and 4 detail the parameters for the time delay and ambient light level
adjustable settings.

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 9of 16
Table 3 –Settings for adjustable time delay
Position
Time Delay *
Typical Application
5 Sec
†Walk test: test light level
setting and
to confirm effective field of view
5
5 Mins
Halls & passages
10
10 Mins
Store rooms
15
15 Mins
Tea rooms
20
20 Mins
Enclosed
offices,
meeting
rooms,
bathr
ooms
25
25 Mins
Open
plan offices,
reception
ar
eas
* Relay 2 will switch off 5 minutes after Relay 1 has switched off (DGEMSR360P2 only).
†In Walk Test Mode all relay channels will activate for 5 seconds only.
Table 4 - Settings for adjustable light level threshold
Position
Lux Threshold*
Typical Application
∞
Disabled
Test
setting
to confirm effective field of view
1
20 Lux
Halls and passages
2
40 Lux
Store rooms, tea rooms, bathrooms
3
80 Lux
Closed of
fices
4 (Factory default)
160 Lux
Open
plan offices,
meeting rooms
5
320 Lux
Reception areas
* If the ambient light has exceeded the set threshold, Relay 1 will not switch on. Relay 2 will not be affected by the threshold
setting and will operate as per normal (DGEMSR360P2 only).
Note: The lux level threshold values shown in Table 4 refer to the minimum light level incident on the
sensor. Typical room light levels are considerably larger. Surfaces and materials in the space being
controlled will determine the amount of reflected light onto the sensor head.
7. Presence/Occupancy Detection
The Passive Infra-red (PIR) sensor uses an advanced detector and lens array to provide the ultimate coverage in its
class. The sensor head has two distinct detection sensitivity zone categories, major movement and minor
movement.
Major Movement1(Occupancy) is defined as a 60kg person, walking at >1m/s, across the field of view, with a
background ambient temperature of 20°C.
The PIR sensor will detect Major Movement within a 7m diameter circular area of its position when mounted at
2.7m from the floor as shown in Figure 9.
Minor Movement1(Presence) is defined as a hand and forearm at 0.9m from the floor moving through a 90° arc
in <1.5 sec with a background ambient temperature of 20°C.
The PIR sensor will detect Minor Movement within a 3.5m diameter circular area of its position when mounted at
2.7m from the floor as shown in Figure 9.
1Referenced from the NEMA Guide Publication WD 7-2011, Occupancy Motion Sensors Standard, National Electrical Manufacturers Association, Virginia,
USA, 2012

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 10 of 16
Figure 9 –Detection coverage when mounted at 2.7m
Note: Additional detection outside these areas may be noticed subject to external temperature,
mounting height and movement activity.
The advanced lens array of the sensor allows for superior occupancy/presence detection with 864 zones as
outlined in Table 5.
Table 5 –Fields of View (FOV)
Range
Long Range
Mid-range
Short-range
Look-down
Total
Fields of view (FOV)
192
384
256
32
864
The FOV patterns in Figures 10 and 11 (top-view) show the dense array of sensitivity available for maximum
detection from the advanced lens array at floor and desk level with sensor mounting height of 2.7m.
Radius (m)
Figure 10 –FOV intersection with desk (0.8m high),
top-view, mounted at 2.7m
Figure 11 –FOV intersection with floor, top-view,
mounted at 2.7m
Radius (m)

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 11 of 16
8. Power Surges
The presence sensor control module should only be connected to a mains supply within the range stated in
Section 10. Nominal fluctuations in mains supply voltage will have no effect on the control module as the dc
output to the sensor head remains stable. However induced voltages or surges may occur on electrical circuits in
an installation as a result of excessive voltages from external influences which can damage electronic equipment.
It is strongly recommended that the electrical installation be fitted with suitable over-voltage protection at the
electrical switchboard to avoid these situations.
9. Insulation Resistance Testing
Generally it is not a requirement to perform an IR test on the PIR control module. In the event it is required, the
PIR control module cables must be disconnected from the mains supply to conduct the test and then
reconnected.
10. Product Specifications
Parameter
Specification
DGEMSR360P1
(1 channel model)
DGEMSR360P2
(2 channel model)
Input voltage (control/power module)
220 –240 ac
Input current (control/power module)
2mA (Relay Off)
11mA (Relay ON)
2mA (Relay Off)
20mA (Relays ON)
Frequency
50/60Hz
Output rated current (control/power module)
16A per relay channel
Output voltage (sensor head)
12V dc nominal
Output current (sensor head)
8mA nominal under normal detection with a single sensor.
Isolation
≥3.75kV ac (Mains/Sensor Head) / SELV
Remote Override
A maximum of 10 remote switches can be connected with up to
20m of cable on the same circuit.
Start-up time
45 sec initialisation (5 mins for full sensitivity)
Ambient operating temperature
-10°C to +45°C
Ambient storage temperature
-10°C to +60°C
Humidity
10% –95% RH, non-condensing
Sensor head cable
Factory fitted –0.45m
Maximum custom –1.0m
Mains supply terminals (including override)
Screwed –2 x 1.5mm2or 1 x 2.5mm2
Conductor strip length
6-7mm
Ingress protection
IP20
Material
Flame retardant polycarbonate
Weight
178g
192g
Ceiling cut-out
52mm diameter
Dimensions
Refer to Figures 12 and 13
Compliance

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 12 of 16
Figure 12 –Dimensions of PIR sensor head
Figure 13 –Dimensions of sensor control module

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 13 of 16
11. Standards and Compliance
The DGEMSR360Px product is designed to meet/exceed the following Australian and International standards:
Australian/New Zealand EMC and Electrical Safety Frameworks and Standards
Regulation
Standard
Title
Electrical Safety
AS/NZS 61347.1:2002
Lamp controlgear - General and safety requirements
(IEC 61347-1:2000, MOD)
AS/NZS 61347.2.2
Lamp controlgear - Particular requirements for d.c. or
a.c. supplied electronic step-down convertors for
filament lamps (IEC 61347-2-2, Ed. 1.2 (2006) MOD)
EMC
AS/NZS CISPR 15:2011
Limits and methods of measurement of radio
disturbance characteristics of electrical lighting and
similar equipment (CISPR 15, Ed.7.2 (2009) MOD)
Other International Directives and Standards
Regulation
Standard
Title
EMC
EN 55015:2006
Limits and methods of measurement of radio
disturbance characteristics of electrical lighting and
similar equipment
EN 61547:2009
Equipment for general lighting purposes - EMC
immunity requirements
EN 61000-3-2:2006
Electromagnetic compatibility (EMC) - Part 3-2: Limits
- Limits for harmonic current emissions (equipment
input current ≤16A per phase)
EN 61000-3-3:2008
Electromagnetic compatibility (EMC) - Part 3-3: Limits
- Limitation of voltage changes, voltage fluctuations
and flicker in public low-voltage supply systems, for
equipment with rated current ≤16A per phase and
not subject to conditional connection

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 14 of 16
12. Product Warranty
The Recessed Flush Mount 360oPIR Presence Sensor and Control Module have a two-year warranty against
manufacturing defects in accordance with the following terms:
1. Nothing in this Warranty affects any person's rights under the Australian Consumer Law. The benefits to any
person under the DIGINET Warranty are in addition to the rights and remedies available under any Consumer
Guarantees.
2. Subject to the other clauses of this Warranty, DIGINET warrants that the Goods will be free of manufacturing
defects and will perform to DIGINET's specifications.
3. The benefit of the DIGINET Warranty extends only to the owner of the property in which the Goods are
installed (the Owner) for two (2) years after the date of purchase (Warranty Period).
4. If within the Warranty Period the Goods fail to perform to DIGINET's specifications as a result of some defect
in material or workmanship in the Goods (Defect) then DIGINET will, at its option, repair the Goods or supply
replacement Goods free of charge.
5. The DIGINET Warranty will not apply to Goods:
5.1. installed by any person other than a qualified tradesperson; or
5.2. subjected to misuse, neglect, negligence or accidental damage; or
5.3. operated in any way contrary to any operating or maintenance instructions; or
5.4. improperly handled, installed or maintained; or
5.5. altered or modified prior to or after installation.
6. The DIGINET Warranty does not apply to faulty or defective design of Goods unless DIGINET has designed the
Goods and DIGINET expressly accepts responsibility for such design in writing.
7. In order to make a claim under the DIGINET Warranty, the Owner must:
7.1. contact DIGINET to obtain a Returned Goods Authorisation Number for the Goods and to be notified
of DIGINET's return address for the Goods by:
7.1.1. freecall 1300 95 DALI (3254); or
7.1.2. post to PO Box 314, Padstow NSW 2211; or
7.1.3. fax to 1300 95 3257; or
7.1.4. email to [email protected].au.
7.2. return the Goods at the Owners expense to the return address notified by DIGINET together with all
accessories, instructions, specifications or other material supplied with the Goods and a notice in
writing:
7.2.1. stating the Returned Goods Authorisation Number for the Goods;
7.2.2. describing in detail the defect or fault in the Goods;
7.2.3. setting out the Owner's contact details (including postal address, email address and
telephone numbers at which the Owner can be contacted during usual business hours).
7.3. DIGINET will not accept any returned Goods which have not been returned strictly in accordance with
the above instructions.
8. DIGINET will examine any returned Goods and if DIGINET determines that they are defective through no fault
of the Owner and are otherwise undamaged, DIGINET will repair or replace the Goods free of charge.
9. DIGINET will notify the Owner whether it accepts the Goods are defective within a reasonable time of return.
10. DIGINET will not be responsible for any costs of de-installation, re-installation, returning Goods or for
redelivery of the Goods (whether original or repaired and/or replacement Goods) by DIGINET and any other
related expenses of the Owner in claiming under the DIGINET Warranty.

DIGINET ENERGY MANAGEMENT Recessed Flush Mount 360oPIR Presence Sensor
Diginet Control Systems Pty Ltd Page 15 of 16
11. DIGINET will not be responsible for any loss or damage to the Goods occurring while the Goods are in transit
(either on return to DIGINET or upon redelivery to the Owner of the original or repaired and/or replacement
Goods).
12. DIGINET will not be responsible (whether arising in contract or tort (including negligence) or under any
statute) for any special, indirect, incidental, consequential or economic losses or damages (including loss of
data, business, profits, revenue, anticipated savings, bargain, opportunity or goodwill) whether or not the
possibility of those losses or damages being suffered had been brought to the attention of DIGINET.
The Australian Consumer Law requires the inclusion of the following statement with the DIGINET Warranty:
Our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled
to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss
or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable
quality and the failure does not amount to a major failure.

DIGINET.NET.AU
Product of Diginet Control Systems Pty Ltd
ABN –89 095 788 864
96-112 Gow Street
Padstow NSW 2211
Contact
Fax: 1300 95 3257
A member of the Gerard Lighting Group
V1.0 April 2013 Item 14-09-030-003-01
Printed on recycled paper
This manual suits for next models
1
Table of contents
Popular Security Sensor manuals by other brands

B.E.G. LUXOMAT
B.E.G. LUXOMAT PD4-M-HCL-FC Application description

Risco
Risco Lumin8 4012 installation instructions

Optoelectronics
Optoelectronics R506 user manual

Orbis
Orbis MOVICAM CR quick start guide

Lince
Lince ZENITH GOLD 869 Series Installation and operating manual

Lunos
Lunos 9/IBE installation manual