Digiplex DGP-48 User manual

Digiplex Control Panel - V2.14/2.20ACC
DGP-48
Reference and Installation Manual


TABLE OF CONTENTS
INTRODUCTION.................................................................................................................................41.0
1.1 Features .......................................................................................................................................................... 4
1.2 Specifications .................................................................................................................................................. 4
ACCESSORIES ..................................................................................................................................52.0
INSTALLATION...................................................................................................................................73.0
3.1 Location & Mounting ....................................................................................................................................... 7
3.2 Earth Ground .................................................................................................................................................. 7
3.3 AC Power ........................................................................................................................................................ 7
3.4 Backup Battery ............................................................................................................................................... 7
3.5 Auxiliary Power Terminals .............................................................................................................................. 7
3.6 Telephone Line Connection ............................................................................................................................ 7
3.7 Bell/siren Output ............................................................................................................................................. 7
3.8 Calculating Power Requirements ................................................................................................................... 9
3.9 Programmable Outputs .................................................................................................................................10
3.10 Bus Zone Connections ............................................................................................................................... 11
3.11 Single Zone Connections ............................................................................................................................ 11
3.12 Double Zone Connections .......................................................................................................................... 12
3.13 Keypad Zone Connections ......................................................................................................................... 12
3.14 Keyswitch Connections ............................................................................................................................... 12
3.15 Fire Circuits ................................................................................................................................................. 12
3.16 Connecting the ZX4 .................................................................................................................................... 13
PROGRAMMING METHODS ...........................................................................................................14 4.0
4.1 Panel Programming Mode ............................................................................................................................ 14
4.2 Module Programming Mode ......................................................................................................................... 14
4.3 Feature Select Programming ........................................................................................................................ 14
4.4 Decimal Programming .................................................................................................................................. 14
4.5 Hexadecimal Programming .......................................................................................................................... 14
4.6 Level Programming ....................................................................................................................................... 14
4.7 Paradox Memory Key ................................................................................................................................... 15
ZONE PROGRAMMING ...................................................................................................................16 5.0
5.1 Zone Numbering ........................................................................................................................................... 17
5.2 Zone Definitions ............................................................................................................................................ 17
5.3 Zone Partition Assignment ............................................................................................................................ 18
5.4 Zone Options ................................................................................................................................................ 18
5.5 Input Speed .................................................................................................................................................. 19
5.6 EOL Zones .................................................................................................................................................... 19
5.7 Zone Doubling (ATZ) .................................................................................................................................... 20
KEYSWITCH PROGRAMMING........................................................................................................21 6.0
6.1 Keyswitch Numbering ................................................................................................................................... 22
6.2 Keyswitch Definitions .................................................................................................................................... 22
6.3 Keyswitch Partition Assignment .................................................................................................................... 22
6.4 Keyswitch Options ........................................................................................................................................ 22
ARMING & DISARMING OPTIONS..................................................................................................23 7.0
7.1 Arming Follows Partition ............................................................................................................................... 23
7.2 No Arming On Battery Fail ............................................................................................................................ 23
7.3 No Arming On Tamper .................................................................................................................................. 23
7.4 No Arming On Supervision Loss ................................................................................................................... 23

7.5 Timed Auto-Arming ........................................................................................................................................23
7.6 No Movement Auto-Arming ...........................................................................................................................23
7.7 Auto-Arming Options .....................................................................................................................................24
7.8 One-touch Features .......................................................................................................................................24
7.9 Exit Delay ......................................................................................................................................................24
7.10 Keypad Lock-out Feature ............................................................................................................................24
7.11 Maximum Bypass Entries ............................................................................................................................25
7.12 Display “Bypass” If Armed ...........................................................................................................................25
7.13 Bell Squawk .................................................................................................................................................25
7.14 Ring-back ....................................................................................................................................................25
7.15 Switch To Stay Arming ................................................................................................................................25
ALARM OPTIONS.............................................................................................................................26 8.0
8.1 Bell/alarm Output ...........................................................................................................................................26
8.2 Bell Cut-off Timer ...........................................................................................................................................26
8.3 Wireless Transmitter Supervision Options ....................................................................................................26
8.4 Tamper Recognition Options .........................................................................................................................26
8.5 Keypad Panic Options ...................................................................................................................................27
EVENT REPORTING ........................................................................................................................28 9.0
9.1 Reporting Enabled .........................................................................................................................................29
9.2 Report Codes ................................................................................................................................................29
9.3 Central Station Phone # ................................................................................................................................31
9.4 Partition Account # ........................................................................................................................................31
9.5 Reporting Formats .........................................................................................................................................31
9.6 Event Call Direction .......................................................................................................................................32
9.7 Recent Close Delay .......................................................................................................................................32
9.8 Auto Test Report ...........................................................................................................................................32
9.9 Power Fail Report Delay ................................................................................................................................32
9.10 Disarm Reporting Options ...........................................................................................................................32
9.11 Zone Restore Report Options ......................................................................................................................32
9.12 Pager Delay .................................................................................................................................................32
9.13 Auto Report Code Programming .................................................................................................................33
DIALER OPTIONS.............................................................................................................................3410.0
10.1 Telephone Line Monitoring ..........................................................................................................................34
10.2 Tone/pulse Dialing .......................................................................................................................................34
10.3 Pulse Ratio ..................................................................................................................................................34
10.4 Busy Tone Detection ...................................................................................................................................34
10.5 Switch To Pulse ...........................................................................................................................................34
10.6 Bell On Communication Fail ........................................................................................................................34
10.7 Dial Tone Delay ...........................................................................................................................................34
PROGRAMMABLE OUTPUTS..........................................................................................................3511.0
11.1 PGM Activation Event ..................................................................................................................................35
11.2 PGM Deactivation Option ............................................................................................................................35
11.3 PGM1 Is Smoke Input .................................................................................................................................36
PGM PROGRAMMING TABLE.........................................................................................................3712.0
SYSTEM SETTINGS & COMMANDS...............................................................................................4013.0
13.1 Hardware Reset ...........................................................................................................................................40
13.2 Software Reset ............................................................................................................................................40
13.3 Battery Charge Current ...............................................................................................................................40
13.4 Installer Code Lock ......................................................................................................................................40
13.5 Partitioning ...................................................................................................................................................40

13.6 Installer Function Keys ............................................................................................................................... 40
13.7 System Date & Time ................................................................................................................................... 41
13.8 Shabbat Feature ......................................................................................................................................... 41
13.9 Access Control ............................................................................................................................................ 41
13.10 Module Reset ............................................................................................................................................ 41
13.11 Locate Module .......................................................................................................................................... 41
13.12 Module Programming ............................................................................................................................... 41
13.13 Module Broadcast ..................................................................................................................................... 41
13.14 Remove Module ........................................................................................................................................ 41
13.15 Serial Number Viewing ............................................................................................................................. 41
13.16 Power Save Mode .................................................................................................................................... 42
13.17 Auto Trouble Shutdown ............................................................................................................................ 42
13.18 No AC Fail Display .................................................................................................................................... 42
ACCESS CODES..............................................................................................................................4314.0
14.1 Installer Code .............................................................................................................................................. 43
14.2 Access Code Length ................................................................................................................................... 43
14.3 System Master Code .................................................................................................................................. 43
14.4 Programming Access Codes ...................................................................................................................... 43
14.5 User Options ............................................................................................................................................... 43
14.6 User Partition Assignment .......................................................................................................................... 44
14.7 Access Control ............................................................................................................................................ 44
14.8 Multiple Action Feature ............................................................................................................................... 44
WINLOAD SOFTWARE....................................................................................................................4515.0
15.1 Answering Machine Override ...................................................................................................................... 45
15.2 Ring Counter ............................................................................................................................................... 45
15.3 Panel Identifier ............................................................................................................................................ 45
15.4 PC Password .............................................................................................................................................. 45
15.5 PC Telephone Number ............................................................................................................................... 45
15.6 Call WinLoad .............................................................................................................................................. 45
15.7 Answer WinLoad ......................................................................................................................................... 45
15.8 Event Buffer Transmission .......................................................................................................................... 45
15.9 Call Back Feature ....................................................................................................................................... 45
USER FEATURES............................................................................................................................4616.0
16.1 Arming and Disarming Features ................................................................................................................. 46
16.2 Bypass Programming .................................................................................................................................46
16.3 Chime Zones .............................................................................................................................................. 47
16.4 Access Codes ............................................................................................................................................. 47
16.5 Normal and Confidential Modes ................................................................................................................. 47
16.6 Keypad Settings .......................................................................................................................................... 47
16.7 Trouble Display ........................................................................................................................................... 48
16.8 Event Record Display .................................................................................................................................49
INDEX ...............................................................................................................................................5017.0
FCC WARNINGS..............................................................................................................................5418.0
WARRANTY......................................................................................................................................5519.0

4REFERENCE& INSTALLATIONMANUAL
1 INTRODUCTION
Paradox Security Systems has once again redefined the
boundaries of the security industry and is proud to introduce the
Digiplex Control Panel. A new generation in control panel
technology, the Digiplex Control Panel uses a quad-wire
communication bus that provides power and two-way
communication for up to 95 modules (keypads, motion detectors,
expansion modules, etc.). This, combined with four true partitions,
event call direction and the zone numbering feature, simplifies the
task of installing or making changes to your security system. The
innovative new programming method makes programming the
control panel logical and much simpler to execute. This new
generation of control panels offers increased capabilities with
countless new features without compromising its user-friendliness.
If anything, these new control panels are easier to use and easier
to install, making the Digiplex Control Panel the ultimate in reliable
security protection.
1.1 FEATURES
•Four-wire Communication Bus:
uProvides power and two-way communication to all
modules connected to the bus.
u95 module support
uAll bus modules have Plug and Play capability
uConnect modules up to 3000ft (914m) from the
control panel.
uFull System Supervision.
•48 fully programmable zones
•8 independent keyswitch zones (does not use any of the 48
zones)
•4 on-board hardwired input terminals for use with non-bus
detection devices (expandable to 48).
•4 True Partitions:
Most features and options in the Digiplex System can be
independently set for each partition such as event
reporting, entry/exit delay, bell squawk, quick arming,
panics and many more. All zones, keyswitches, user
codes and keypads are assigned to specific partitions,
making this a true partitioned system.
•95 User Codes, 1 Installer and 1 System Master
•Up to 4 fully programmable outputs (PGMs) are available.
PGM1 can be set as a two-wire smoke detector input. Optional
5A relay also available.
•Simple, direct and logical programming
•Event Call Direction:
The Digiplex Control Panel events are divided into three
event groups for each partition and two system event
groups. Each event group can be programmed with a
separate dialing sequence for each partition.
•4 Central Station Telephone Numbers
•SIA, Contact ID, Pager Format and many more Communicator
Formats
•Upload/download capability using new WinLoad Security
System Management software for Windows®.
•And much, much, more…
1.2 SPECIFICATIONS
CONTROLPANEL
•AC Power: 16VAC, 20/40VA, 50-60Hz
•Battery: 12VDC, 4Ah minimum
•Aux. Power: 12VDC 600mA typical, 700mA maximum,
fuseless shutdown at 1.1A
•Bell Output: 1A, fuseless shutdown @ 3A
•PGM Output: PGM1 (100mA), PGM2 - PGM4 (50mA) and
PGM5 (5A optional relay)
•Event Buffer: 1024 events
•All control panel outputs are rated to operate between 10.8Vdc
and 12.1Vdc

DIGIPLEX CONTROLPANEL5
2 ACCESSORIES
The following modules are compatible with the Digiplex DGP-48 Control Panel.
WINLOAD
This Windows®-based Security System Management Software can perform remote diagnostics and
adjustments, provide on-site communication at 300baud with the ADP-1 or at 19,200 baud with the
306 Adapter, facilitate programming and event loading, and customize control panel default settings.
This user-friendly software is compatible with most modems.
LCD KEYPAD (DGP-641)
48-zone, 32-character programmable LCD keypad that connects to the bus. Most messages in the
LCD keypad are programmable. View zone, event and trouble status for one or more partitions,
display entry/exit delay, adjust contrast, backlight, and many other features. On-board PGM output
and hardwired zone input.
ACCESS CONTROLLCD KEYPAD (DGP-641ACC)
The DGP-641ACC is an LCD Keypad that can be used with the Access Control feature available
through the Digiplex Control Panel. The Access Control feature allows you to monitor and control the
access of up to 32 doors in the Digiplex system. The DGP-641ACC is the same as a DGP-641
except it allows you to program the access control features, view logged access events as well as
communicate the status of a Posiprox (CR-R880) card reader, a Paradoor (460), a door lock, and a
door contact to the Digiplex system.
LED KEYPADS(DGP-610, DGP-620 & DGP-648)
The cost-effective 10-zone, 20-zone and 48-zone LED keypads connect to the bus and provide a
user-friendly display of the system's status. Includes an on-board PGM output and hardwired zone
input. This modern and stylish keypad will enhance any decor while helping you make the most of the
Digiplex security system.
ZX1 ZONEEXPANSIONBUSMODULE(DGP-ZX1)
Connected to the Digiplex communication bus, this fully supervised zone expansion module will add
1 hardwired input terminal to the Digiplex System (2 zones if ATZ is enabled).
ZX8 ZONEEXPANSIONMODULE(DGP-ZX8)
Connected to the Digiplex communication bus, this zone expansion module will add 8 hardwired
input terminals to the Digiplex System (16 zones if ATZ is enabled). Each module has one on-board
PGM output.
PGM1 EXPANSIONMODULE(DGP-PGM1)
When connected to the Digiplex communication bus, this module will add one 5A programmable
output (PGM) to the Digiplex System.
ZX4 ON-BOARD ZONEMODULE(DGP-ZX4)
Connected to the Digiplex control panel's EXPANSION input, this module will add 4 hardwired input
terminals to the Digiplex System (8 zones with ATZ enabled).

6REFERENCE& INSTALLATIONMANUAL
DIGITALBUSDETECTORS(DGP-25 & DGP-60)
Totally software-driven, digital detectors are more intelligent and more powerful than any other
detection device. This patent-pending, breakthrough technology revolutionizes the security industry
in the same way the compact disc revolutionized music and home entertainment. By connecting
directly onto the bus, you no longer have to set jumpers and complicated dip switches. Simply
program their sensitivity and other settings through any keypad in the system.
HIGH-SECURITYPIR FORDEMANDINGAREASWITHPETIMMUNITY(DGP-70)
Animal lovers can maximize their security protection thanks to the power of true digital analysis with
an intelligent patent-pending “pet-friendly” lens. There's no need to compromise performance or
detector sensitivity to deliver pet immunity.
LIBERATORTM WIRELESS BUSMODULE(DGP-319)
Connected to the Digiplex communication bus, this module will allow you to add up to 16 fully
supervised wireless zones using the LiberatorTM detectors and contact switches as well as 16
programmable remote controls. This module also includes up to two programmable 5A relays.
PRINTERMODULE(DGP-PRT1)
The Printer Module provides you with the ability to automatically print events as they occur in the
Digiplex system or the events can be stored in the module’s event buffer so you can print the events
manually. The events can be sent to a dot matrix printer or can be viewed and printed from a
computer. Includes a 50mA PGM output. Ideal for monitoring users when using the Access Control
feature.
PGM4 (DGP-PGM4)
When connected to the Digiplex communication bus, this module will provide four additional 5A
programmable outputs to the Digiplex system.
COMING SOON:
CONTACTBUSVOICEDIALERAND X-10 MODULE
ZC1 DOOR/WINDOWBUSCONTACTSWITCH

DIGIPLEX CONTROLPANEL7
3 INSTALLATION
3.1 LOCATION& MOUNTING
Before mounting the cabinet, push the five white nylon mounting
studs into the back of the cabinet. Pull all cables into the cabinet
and prepare them for connection before mounting the circuit board
into the back of the cabinet. Select an installation site that is not
easily accessible to intruders and leave at least 2" around the
panel box to permit adequate ventilation and heat dissipation. The
installation site should be dry and close to an AC source, ground
connection and telephone line connection.
3.2 EARTHGROUND
Connect the zone and dialer ground terminals from the control
panel to the cabinet and cold water pipe or grounding rod as per
local electrical codes.
For maximum lightning protection, use separate earth
grounds for the zone and dialer grounds as shown in
Figure 3-3 on page 8.
3.3 AC POWER
Use a 16.5VAC (50/60Hz) transformer with a minimum 20VA rating
to provide sufficient AC power. For increased power you can use a
transformer with a 40VA rating. For UL Listed systems, you can
use model #BE156240CAA. For CSA listed systems, use model
#BE116240AAA. Do not use any switch-controlled outlets to power
the transformer. Connect the transformer as shown in Figure 3-3
on page 8.
Do not connect the transformer or the backup battery
until all wiring is completed.
3.4 BACKUPBATTERY
In order to provide power during power loss, connect a 12VDC 4Ah
rechargeable acid/lead or gel cell backup battery (YUASA model
#NP7-12 recommended) as shown in Figure 3-3 on page 8.
Connect the backup battery after applying AC power. When
installing, verify proper polarity, as reversed connections will blow
the battery fuse. For information on how to set the Battery Charge
Current to either 350mA or 700mA, please refer to section 13.3 of
this manual
3.4.1 Battery Test
The control panel conducts a dynamic battery test under load every
64 seconds. If the battery is disconnected, if its capacity is too low
or if the battery voltage drops to 10.5 volts or less when there is no
AC, the “Battery Trouble” message will appear in the Trouble
Display. At 8.5 volts, the panel shuts down and all outputs close.
3.5 AUXILIARYPOWERTERMINALS
You can use the auxiliary power supply to power the motion
detectors, keypads and other accessories in your security system.
A fuseless circuit protects the auxiliary output against current
overload and automatically shuts down if the current exceeds 1.1A.
Auxiliary power will resume once the overload condition has
restored. For details on available output power, please refer to
Figure 3-3 on page 8. For more information on how to calculate
system consumption, refer to Calculating Power Requirements on
page9.
3.6 TELEPHONELINECONNECTION
Connect the incoming telephone company wires into the TIP and
RING connections of the control panel. Then run the wires from T1
and R1 to the telephone system as shown in Figure 3-1.
Figure 3-1: Telephone Line Connections
3.7 BELL/SIRENOUTPUT
The BELL+ and BELL- terminals power bells and/or other warning
devices that require a steady voltage output during an alarm. The
bell output supplies 12VDC upon alarm and can support two 20-
watt or two 30-watt sirens. The bell output uses a fuseless circuit
and will automatically shut down if the current exceeds 3A. If the
load on the BELL terminals returns to normal (≤3A), the control
panel will re-instate power to the BELL terminals. When connecting
sirens, please verify correct polarity as shown in Figure 3-2. Please
note that PGM5 is rated at 5A and can be used to power bells and/
or other warning devices (see Figure 3-2: Bell/Siren)by
programming it as a bell/siren output. Please refer to
Programmable Outputs in section 11.
When the bell/siren output is not used, the “Bell
Absent” message will appear in the Trouble Display.
To avoid this, connect a 1kΩΩ resistor across the bell
output.
Figure 3-2: Bell/Siren

8REFERENCE& INSTALLATIONMANUAL
Figure 3-3: Digiplex Control Panel PCB Layout

DIGIPLEX CONTROLPANEL9
3.8 CALCULATINGPOWERREQUIREMENTS
STEP 1: Using Table1: Power Unit Consumption Table, calculate the total number of power units (PU) required by each
device, module, and accessory in the system. Please take into account devices connected to the control panel’s
PGM outputs. Since the BELL output has its own power supply, do not include the sirens connected to it in the
calculation.
STEP 2: If the value recorded in box “A” is less than the value in box “B”, go to step 3. If the value is greater, you will require an
external power supply (see Figure 3-5 on page 10) to provide the additional power needed. Proceed with step 3 and
refer to the example in Figure 3-4 on page 10.
STEP 3: Due to the degradation of a power signal over long distances, EACH length or run of wire in the system can
support only a specific number of power units (PU). Using Table2: Power Unit (PU) Limitations For Each Run of Wire,
determine how many power units each length of wire can support. Please note that the total number of power units
(PU) can never surpass the value in box “B”.
Table 1: Power Unit Consumption Table
Description QTY. PU used by each Total PU
LCD Keypads (DGP-641): _______ X 80PU = __________ PU
Access Control LCD Keypads (DGP-641ACC): _______ X 150PU = __________ PU
LED Keypads (DGP-610/620/648): _______ X 45PU = __________ PU
Bus Detectors (DGP-25/60/70): _______ X 25PU = __________ PU
ZX1 Zone Expansion Bus Modules (DGP-ZX1) _______ X 25PU = __________ PU
ZX8 Zone Expansion Bus Modules (DGP-ZX8) _______ X 40PU = __________ PU
Liberator Wireless Bus Modules (DGP-319): _______ X 70PU = __________ PU
PGM1 Expansion Bus Module (DGP-PGM1): _______ X 25PU = __________ PU
Printer Module (PRT1) _______ X 40PU = __________ PU
Other devices such as hardwired motion detectors (1mA = 1PU) __________ PU
GRAND TOTAL A: __________ PU
B: Maximum available power units = 700PU
Table 2: Power Unit (PU) Limitations For Each Run of Wire
Gauge: 18AWG,Surface: 0.823mm2Gauge: 22AWG,Surface: 0.326mm2Gauge: 24AWG,Surface: 0.205mm2
Length of each
run of wire AvailablePower
Units (PU) Length of each
run of wire AvailablePower
Units (PU) Length of each
run of wire AvailablePower
Units (PU)
100ft. (30m) 700 100ft. (30m) 700 100ft. (30m) 700
200ft. (61m) 700 200ft. (61m) 682 200ft. (61m) 429
300ft. (91m) 700 300ft. (91m) 454 300ft. (91m) 286
400ft. (122m) 700 400ft. (122m) 341 400ft. (122m) 214
500ft. (152m) 690 500ft. (152m) 273 500ft. (152m) 171
600ft. (183m) 575 600ft. (183m) 227 600ft. (183m) 143
700ft. (213m) 493 700ft. (213m) 195
800ft. (244m) 431 800ft. (244m) 170
900ft. (383m) 383 900ft. (383m) 151
1000ft. (305m) 345 1000ft. (305m) 136
1500ft. (457m) 230
2000ft. (610m) 172
2500ft. (762m) 138
3000ft. (914m) 115

10 REFERENCE& INSTALLATIONMANUAL
Figure 3-4: Sample Power Requirement Calculations
If in the above example you were to add an LCD Keypad (80PU) to
the 100 foot or 300 foot wire, you would not exceed the wire’s limit.
Although, adding the LCD Keypad to the 1,000 foot wire would
exceed the wire’s limits, thereby causing devices to function at
decreased capacity.
Figure 3-5: External Power Supply Connections
Do not use the same transformer for the control panel and the external power supplies. Modules should never be
installed more than 3,000 feet (914m) from the control panel.
3.9 PROGRAMMABLEOUTPUTS
The Digiplex Control Panel comes standard with PGM1 and
PGM2. PGM3 to PGM5 are optional. When a specific event or
condition occurs in the system, a PGM can be programmed to
reset smoke detectors, activate strobe lights, open/close garage

DIGIPLEX CONTROLPANEL11
doors and much more. For details on how to program the PGMs,
refer to section 11.
PGM1 provides a maximum 100mA output, PGM2 to PGM4
provide a maximum 50mA output and PGM5 is a relay output that
provides a maximum of 5A. If the current draw on the PGM is to
exceed the current output, we recommend the use of a relay as
shownin Figure 3-6. PGM1 to PGM4 are normally open outputs
and PGM5 is a normally open or normally closed 5A relay. Also,
note that PGM1 can be programmed as a 2-wire smoke detector
input. For more information, refer to section 3.15.1 and section
11.3 of this manual.
Figure 3-6: PGM Relay Output
3.10 BUSZONECONNECTIONS
The bus is a 4-wire communication bus that provides power and
two-way communication between the control panel and all modules
connected to it. All bus detectors, keypads and Digiplex modules
are connected to the bus, which can support up to 95 modules.
Connect the four terminals labeled RED, BLK, GRN and YEL of
each detector, keypad or module to the corresponding terminals of
the control panel as shown in Figure 3-3 on page 8. Please note
that all bus modules can be connected in a star and/or daisy chain
configuration. The final device on the communication bus should
not be more than 3000ft (914m) from the control panel. For
information on how to assign a detection device to a zone in the
control panel, please refer to Zone Programming on page16.
Before connecting a bus module to the control panel,
shutdown the control panel by removing AC and
battery power.
3.11 SINGLEZONECONNECTIONS
In addition to the bus, the Digiplex Control Panel includes four
hardwired input terminals for use with traditional hardwired (non-
bus) door contacts, smoke detectors and/or detectors. The control
panel also supports one on-board Expansion Module, the ZX4. The
ZX4 will add four hardwired input terminals to the control panel.
The ZX1 or ZX8 Zone Expansion Bus Modules can provide one or
eight additional hardwired input terminals when connected to the
bus. Devices connected to hardwired input terminals must be
assigned to a zone and the zone's parameters must be defined.
Please refer to Zone Programming on page16 for more
information. Figure 3-7 demonstrates single zone (ATZ disabled)
hardwire input terminal connections recognized by the Digiplex
system. For UL listed installations, use EOL resistor part
#2011002000.
Figure 3-7: Single Zone Input Connections

12 REFERENCE& INSTALLATIONMANUAL
3.12 DOUBLEZONECONNECTIONS
Enabling the ATZ feature (see section 5.7) allows you to install two
detection devices per input terminal. The ATZ feature is a software
oriented feature. Simply connect the devices as shown in Figure 3-
8. Devices connected to input terminals must be assigned to a
zone and the zone's parameters must be defined. Please refer to
Zone Programming on page16 for more information. For UL listed
installations, use EOL resistor part #2011002000.
Figure 3-8: Double Zone Connections
3.13 KEYPAD ZONECONNECTIONS
Each keypad has one hardwired input terminal allowing you to
connect a detector or door contact directly to the keypad. For
example, a door contact located at the entry point of an
establishment can be wired directly to the input terminal of the
entry point keypad instead of all the way to the control panel.
Even with the ATZ feature enabled in the control
panel, only one device can be connected to the
keypad’s hardwired input terminal. Tamper is not
recognized on keypad zones. The keypad zone follows
the control panel’s EOL definition.
A device connected to the keypad’s input terminal must be
assigned to a zone in the control panel and the zone’s parameters
must be defined (see Zone Programming on page16). The keypad
will communicate the status of the zone to the control panel via the
communication bus. The detection device is connected as shown
in Figure 3-3 on page 8.
3.14 KEYSWITCH CONNECTIONS
Connect the keyswitches to the keypad, control panel, or Zone
Expansion Module's hardwired input terminals as shown in Figure
3-9. Once a keyswitch is connected, it must be assigned a
keyswitch zone and its parameters must be defined as described in
Keyswitch Programming on page21.
Figure 3-9: Keyswitch Connections
3.15 FIRECIRCUITS
Connect the smoke detectors used in the security system using
any of the following methods. Smoke detectors connected to the
control panel or zone expansion input terminals must be assigned
to a zone in the control panel and the zone's parameters must be
defined as a Fire Zone. For more details, refer to Zone
Programming on page16.
3.15.1 Smoke Detector Installation (2-Wire)
PGM1 can be defined as a 2-wire smoke detector input (see
section 11.3) enabling smoke detectors to be connected as shown
in Figure 3-10 on page 13. Fire Zones must use a 1kΩEOL
resistor. If there is a line short or if the smoke detector becomes
active, whether the system is armed or disarmed, the control panel
will generate an alarm. If the line is open, the “Zone Fault” trouble
indication will appear in the Trouble Display and will transmit the
appropriate report code to the central station (if programmed).
3.15.2 ESL CleanMeTM Installation
The Digiplex control panel supports the use of ESL smoke
detectors that have the CleanMeTM feature. The ESL smoke
detectors are connected exactly like standard smoke detectors as

DIGIPLEX CONTROLPANEL13
shown in Figure 3-10. Please note that you should avoid
connecting more than 20 ESL smoke detectors. When an ESL
smoke detector sends a CleanMeTM signal, the control panel will
generate a Zone Fault trouble and if programmed will transmit the
Fire Loop report code to the central station. The trouble will be
cleared if there is no CleanMeTM signal for 255 seconds. If an
alarm occurs, the trouble will be cleared until it is detected again.
Figure 3-10: PGM1 2-wire Smoke Detector Input
3.15.3 Smoke Detector Installation (4-Wire)
Connect the 4-wire smoke detectors and a relay as shown in
Figure 3-11. Recommended: The System Sensor model 2112/24D
smoke detectors. To comply with UL955, the 4-wire smoke
detectors must be installed using 18 gauge wire. In the event
power is interrupted, the relay will cause the control panel to
transmit the Fire Loop Trouble report if programmed in section
[707]. To reset (unlatch) the smoke detector after an alarm, verify
that the negative (-) of the smoke detector is connected to a PGM
as shown in Figure 3-11. Then program the PGM with the “Smoke
Reset” activation event (see section 11.1 of this manual) to
interrupt power to the smoke detector for four seconds when the
[CLEAR]and [ENTER] keys are pressed and held for two seconds.
Figure 3-11: Fire Zones
3.16 CONNECTINGTHEZX4
The ZX4 is a 4-Zone Hardwire Expansion Module that connects
directly to the control panel through its on-board EXPANSION
connector as shown in Figure 3-12. It provides four additional
hardwired input terminals (8 zones with ATZ enabled). Connect
detection devices to the ZX4's terminals in the same way they are
connected to the control panel as shown in Figure 3-7 on page 11
or Figure 3-8 on page 12. Devices connected to hardwired input
terminals must be assigned to a zone and the zone's parameters
must be defined (see section 5).
Figure 3-12: Connecting the ZX4

14 REFERENCE& INSTALLATIONMANUAL
4 PROGRAMMING METHODS
The Digiplex Control Panel can be programmed using the WinLoad
software, the Paradox Memory Key, or manually by using a
keypad. We highly recommend programming the control panel with
WinLoad as it greatly simplifies the process and reduces potential
data errors. Please refer to WINLOAD SOFTWARE on page45 for
details on how to set up the control panel to function with WinLoad.
You can also copy the programmed contents of one Digiplex
control panel into as many Digiplex control panels as you need by
using the Paradox Memory Key (see section 4.7). Each control
panel is programmed in less than 5 seconds.
Keypads and other bus modules can also be programmed easily
by using Module Broadcast (see section 13.13). Once a module is
programmed, its sections can be sent to other similar modules
through the bus.
4.1 PANELPROGRAMMINGMODE
Use the Programming Guide to keep track of which sections were
programmed and how. In order to program anything in the Digiplex
Control Panel you must enter the programming mode.
After entering the required data, the control panel will save the data
and automatically advance to the next section or press the [ENTER]
key to save whatever data has been entered and automatically
advance to the next section. Press the [CLEAR]key to revert to the
preceding step or to erase the current data entry when you are
entering data.
4.2 MODULEPROGRAMMINGMODE
All modules connected to the communication bus are programmed
through any keypad in the system. To do so, simply enter Module
Programming Mode as shown below.
The control panel will redirect all programming to the selected
module. To exit the Module Programming Mode, press the [CLEAR]
key as many times as needed to return to the desired screen.
Please note that a module's serial number can be located on the
module's PC board or it may already be recorded in the module's
Installation Guide.
4.3 FEATURESELECTPROGRAMMING
Most of the Digiplex Control Panel options are programmed using
the Feature Select Method, where each number from 1 to 8
corresponds to a specific feature or option. Set these options by
turning the number corresponding to the feature ON or OFF. The
option is considered ON when the number appears within the
brackets on the LCD keypad or when the number is illuminated on
an LED Keypad. You turn options ON and OFF by pressing the
corresponding keys on the keypad. Press the keys as many times
as you need to select the desired options and then press [ENTER]to
save.
4.4 DECIMALPROGRAMMING
Certain sections may require the entry of a 3-digit decimal value
from 000 to 255.
4.5 HEXADECIMALPROGRAMMING
Certain sections may require the entry of one or more Hexadecimal
values from 0 to F. Press:
[0] to [9] = values 0 to 9 respectively
[STAY] key = A [DISARM]key = D
[FORCE]key = B [BYP]key = E
[ARM] key = C [MEM]key = F
4.6 LEVELPROGRAMMING
In the sections requiring Level Programming, only one option can
be enabled. To enable the option use the [p] and [q]keys. Press
[ENTER]to save.
TOENTERCONTROLPANELPROGRAMMINGMODE:
Step 1: Press and hold [0] key
Step 2: Key in the [INSTALLERCODE](Default is 000000)
Step 3: Key in the 3-digit [SECTION]
Every feature and or option is programmed into a three-
digit section starting at [001].
Step 4: Key in required [DATA]
The type of data required will be detailed in the
Programming Guide and/or explained in the
appropriate sections of this manual.
TOENTERTHEMODULEPROGRAMMINGMODE:
Step 1: Press & hold [0] key
Step 2: Key in [INSTALLERCODE](Default is 000000)
Step 3: Key in section [953]
Step 4: Key in 8-digit [SERIALNUMBER]of the module you wish
to program
Step 5: Key in 3-digit [SECTION]and required [DATA]
Refer to the module’s Programming Guide or the
module’s Installation Guide for details.

DIGIPLEX CONTROLPANEL15
4.7 PARADOXMEMORYKEY
Copy the programmed contents of one Digiplex Control Panel into
the Paradox Memory Key. Then copy the contents of the Paradox
Memory Key into as many Digiplex Control Panels as you need.
This saves you a lot of time. All you have to do is program one
Digiplex Control Panel, then download the programmed contents to
other control panels in less than 5 seconds.
Copy to Memory Key from SOURCE Control Panel
1) Remove the AC and battery
power from the control panel.
2) Place Memory Key on the
connector labeled MEMKEY of
the control panel that you
want to copy. Make sure that
the write protect jumper is on.
3) Enter section:
[965] to copy the contents of the panel except sections
[001] to [048] (device serial numbers) and [049] to
[056] (keyswitch serial numbers) to the key.
[966] to copy all of the contents including sections [001]
to [048] and [049] to [056] from the panel to the key.
4) When the keypad emits a Confirmation Beep, wait 10
seconds before removing the Memory Key. Remove the
jumper if you do not wish to accidentally overwrite the
contents of the Memory Key.
Download to DESTINATION Control Panel
1) Remove the AC and battery
power from the control panel.
2) Place the Memory Key on the
connector labeled MEMKEY of
the control panel that is to
receive the contents of the
Memory Key.
3) Enter section:
[961] to download the contents except sections [001] to
[048] (device serial numbers) and [049] to [056]
(keyswitch serial numbers) from the key to the
panel.
[962] to download all of the contents including sections
[001] to [048] and [049] to [056] from the key to the
panel.
4) When the keypad emits a Confirmation Beep, wait 10
seconds before removing the Memory Key.
Figure 4-1: Using the Memory Key

16 REFERENCE& INSTALLATIONMANUAL
5 ZONE PROGRAMMING
All detection devices connected to the control panel, keypads and zone expansion modules must be assigned to a zone and that zone must
be defined as described in this section:
Zone Numbering [001] to [048]:
•Serial number of the device/module
•Input number of the device/module
Zone Parameters [101] to [148]:
•Zone Definition
•Zone Partition Assignment
•Zone Options
The Zone Numbering feature is used to individually assign each detection device to any desired zone in the Digiplex system (see section
5.1). The Zone Parameters define the type of zone, the zone's partition assignment and how the control panel will react when an alarm
condition occurs on that zone (see section 5.2 to section 5.4). For more information on the installation of devices and modules, please refer
to Figure 3-3 on page 8 or to their respective Installation Guides.
Figure 5-1: Zone Programming
Press & hold the
[0]
key
Zone Definition
First Digit
Zone Partition
Assignment
Second Digit
Zone Options
Feature Select
Enter the 8-digit
[SERIAL NUMBER]
of the bus
detection device or bus
module that has a hardwire
device connected to it.
Enter the module's 3-digit
[INPUT NUMBER]
where the
hardwire device is connected.
NOTE:
For motion detectors and
keypads no input # is required
Key in the
[INSTALLER CODE]
Zone Definitions
0- Disabled (Default)
1- Entry Delay 1 8- 24Hr Burglary
2- Entry Delay 2 9- Delayed 24Hr Fire
3- Entry Delay 3 A- Standard 24Hr Fire
4- Entry Delay 4 B- Stay Delay 1
5- Follow C- Stay Delay 2
6- Instant D- Stay Delay 3
7- 24Hr Buzzer E- Stay Delay 4
Zone Partition Assignment
1- Zone Assigned to Partition 1 (Default)
2- Zone Assigned to Partition 2
3- Zone Assigned to Partition 3
4- Zone Assigned to Partition 4
Zone Options
[1] Auto Zone Shutdown
[2] Bypass Zone (Default)
[3] Stay Zone
[4] Force Zone
[5] [6] Zone Alarm Type
off off Audible Alarm (steady)
off on Audible Alarm (pulsed)
on off Silent Alarm
on on Generates only a report
[7] Intellizone
[8] Delay before transmission
Press
[ENTER]
Key in 3-digit
[SECTION]
Select one only
Zone Parameters
Sections
[101]
to
[148]
represent
zones 1 to 48 respectively Select
one only
Zone Numbering
Sections
[001]
to
[048]
represent
zones 1 to 48 respectively
Select one
or more

DIGIPLEX CONTROLPANEL17
5.1 ZONENUMBERING
SECTIONS[001] TO [048]
The Zone Numbering feature allows you to assign any detection
device in the system to any of the 48 zones. This feature tells the
control panel where the device is connected and which of the 48
zones is assigned to that device (see Figure 5-2: Zone
Numbering).
•To assign a bus detector connected to the bus, program the
detector's serial number into the section corresponding to the
desired zone (i.e. program zone 34 in section [034]).
•To assign a detection device connected to a module or control
panel's hardwired input terminal, program the module's or
control panel's serial number and the input number where the
device is connected into the section corresponding to the
desired zone. Refer to the appropriate module's Installation
Guide for details of its input numbers. Note: an input number is
not required for keypad zones.
If PGM1 is defined as a smoke detector input (see
section 11.3), the control panel will recognize it as
input # 255.
Figure 5-2: Zone Numbering
5.2 ZONEDEFINITIONS
Select one of the 15 available zone definitions described below
(also refer to Figure 5-1 on page 16).
5.2.1 Zone Disabled
SECTIONS[101] TO [148]: FIRSTDIGIT= 0
Disables the corresponding zone. All zones are disabled by
default.
5.2.2 Entry Delays 1 to 4
SECTIONS[101] TO [148]: FIRSTDIGIT= 1 TO 4
When an armed zone defined as an Entry Delay opens, the control
panel will not generate an alarm until the programmed Entry Delay
Timer has elapsed. A zone can be defined with one of four Entry
Delays. Each Entry Delay is associated with an Entry Delay Timer.
To program the Entry Delay Timer, key in the desired 3-digit delay
value (000 to 255 seconds) into the corresponding section:
•Entry Delay 1 Timer: [230]
•Entry Delay 2 Timer: [231]
•Entry Delay 3 Timer: [232]
•Entry Delay 4 Timer: [233]
Please note these are the same timers used for Stay Delay zones
(see section 5.2.9). Entry Delay zones are commonly used at the
entry/exit points of the protected area (i.e. front/back door or
garage). Using different Entry Delays is useful when, for example,
one entry point requires a longer delay than the other entry point or
in a partitioned system where each partition may require a different
Entry Delay.
5.2.3 Follow Zones
SECTIONS[101] TO [148]: FIRSTDIGIT= 5
If an armed Follow zone opens, the control panel will immediately
generate an alarm. If an armed Entry Delay zone (see section
5.2.2) opens before the Follow zone, the control panel will wait until
the end of the Entry Delay before generating an alarm. If more than
one Entry Delay zone opens before the Follow zone, the control
panel will wait until the end of the first Entry Delay before
generating an alarm.
5.2.4 Instant Zones
SECTIONS[101] TO [148]: FIRSTDIGIT= 6
When an armed Instant zone opens, the control panel immediately
generates an alarm. Instant zones are commonly used for
windows, patio doors, skylights and other perimeter type zones.
5.2.5 24Hr Buzzer Zones
SECTIONS[101] TO [148]: FIRSTDIGIT= 7
Whenever a 24Hr Buzzer zone opens, whether the zone is armed
or disarmed, the control panel will activate the keypad buzzer to
indicate that the zone was breached. The control panel will report
the alarm, but will not enable the bell/siren output. Enter any valid
access code on the keypad to stop the buzzer.
The keypads must be assigned to the same partition
as the 24Hr Buzzer zone. Otherwise, the buzzer will
not activate.
.
5.2.6 24Hr Burglary Zones
SECTIONS[101] TO [148]: FIRSTDIGIT= 8
Whenever a 24Hr Burglary zone opens, whether the system is
armed or disarmed, the control panel will immediately generate an
alarm.
5.2.7 Delayed 24Hr Fire Zone
SECTIONS[101] TO [148]: FIRSTDIGIT= 9
The Delayed 24Hr Fire Zone definition described in Figure 5-3 on
page 18 is commonly used in residential homes where a smoke
detector often generates false alarms (i.e. cigarette smoke, burning
bread, etc.). When a zone is programmed as a Fire zone, the zone
becomes normally open and requires an EOL resistor. The zone
will not function as normally closed.
The keypads must be assigned to the same partition
as the Delayed 24Hr Fire zone for the buzzer to
activate.
Input 2
Hardwired
Device B
Digiplex
Control Panel
SN#:000000A2
ZX8 Module
SN#: 30000041
Input 5
Bus Detector A
SN#: 21000033
B
US
Input Terminals
1 2 3 4
Input Terminals
1 2 3 4 5 6 7 8
Bus Detector A:
Hardwired Device A:
Hardwired Device B:
Hardwired Device C:
Zone#
1 =
2 =
3 =
4 =
Section#
[001]
[002]
[003]
[004]
Serial#
21000033
11000252
000000A2
30000041
Input#
N/A
N/A
002
005
Digiplex Keypad
SN#: 110000252
Keypad Zone
Hardwired
Device C
Hardwired
Device A

18 REFERENCE& INSTALLATIONMANUAL
Figure 5-3: Delayed 24-hr. Fire Zone
5.2.8 Standard 24Hr Fire Zone
SECTIONS[101] TO [148]: FIRSTDIGIT= A
For information on how to connect smoke detectors to the control
panel, refer to Fire Circuits in section 3.15. When a zone is
programmed as a Fire zone, the zone becomes normally open and
requires an EOL resistor. The zone will not function as normally
closed. Whenever a Standard 24Hr Fire Zone is triggered, whether
it is armed or disarmed, the control panel can:
•send the appropriate Zone Alarm report code (see section
9.2.5) to the central station.
•send a Fire Loop Trouble Report (see section 9.2.11) to the
Central Station if a tamper/wiring fault occurs on a Fire Zone.
A “Zone Fault Trouble” will also appear in the keypad's
Trouble Display.
•generate a Fire alarm, which is always audible, regardless of
other settings. Fire alarms will generate an intermittent bell/
siren output signal as demonstrated in Figure 5-4.
Figure 5-4: Bell/Siren Output During Fire Alarm
5.2.9 Stay Delay Zone
SECTIONS[101] TO [148]: FIRSTDIGIT= B TO E
When a Stay Delay zone is armed using the Regular or Force
arming methods, the control panel will process the zone as an
Instant zone (see section 5.2.4). When a Stay Delay zone is armed
using the Stay or Instant arming methodsand the zone is triggered,
the control panel will not generate an alarm until the programmed
Stay Delay has elapsed. A zone can be defined with one of four
Stay Delays. Each Stay Delay is associated with an Entry Delay
Timer. To program the Entry Delay Timer, key in the desired 3-digit
delay value (000 to 255 seconds) into the corresponding section:
Stay Delay 1 = Entry Delay 1 Timer in section [230]
Stay Delay 2 = Entry Delay 2 Timer in section [231]
Stay Delay 3 = Entry Delay 3 Timer in section [232]
Stay Delay 4 = Entry Delay 4 Timer in section [233]
Please note that the Entry Delay Timers are the same timers used
for Entry Delay zones.
5.3 ZONEPARTITIONASSIGNMENT
SECTIONS[101] TO [148]: SECONDDIGIT= 1 TO 4
The control panel provides the option of partitioning the security
system into two, three, or four completely independent systems.
Therefore, each zone must be assigned to one partition as
described in Figure 5-1 on page 16. For more information on
Partitioning, refer to section 13.5.
5.4 ZONEOPTIONS
Each zone can be programmed with one or more of the options
described below. Program the zone options as described in Figure
5-1 on page 16.
5.4.1 Auto Zone Shutdown
SECTIONS[101] TO [148]: OPTION[1]
When option [1] is disabled and an armed zone is breached, the
control panel generates an alarm: it may send an alarm report (see
section 9.11), activate the bell output, etc.. If the same zone re-
opens during the same alarm, another alarm report may be sent,
the bell output may re-activate and so on. When option [1] is
enabled on a zone, the control panel will stop generating an alarm
when the Auto Zone Shutdown Limit is reached during one armed
period. The control panel will ignore zones with the Auto Zone
Shutdown option that have surpassed the programmed limit. To
program the Auto Zone Shutdown Limit, key in the desired 3-digit
counter (000 to 015) into section [217]. Entering 000 disables this
feature. The Auto Zone Shutdown Limit resets every time the
system is armed.
Delayed Fire Zone
Triggered
Activate bell/siren output & delay
report transmission for 30 seconds.
Yes
Yes
Any key on
keypad pressed
within 30
seconds?
Bell/siren silenced. Delay report
transmission an additional 90 sec.
Problem
corrected?
Latch alarm and transmit
report code as described
in the section "Standard
24Hr. Fire Zone".
END
Alarm Disabled
No
Has a 2nd
Delayed Fire
Zone opened in
30 sec.?
No
Yes
Yes
No
Has the zone
closed within
30 seconds?
Yes
No
Table of contents
Other Digiplex Control Panel manuals
Popular Control Panel manuals by other brands

Bosch
Bosch D7412G Installation & Troubleshooting Quick Reference Guide

ABB
ABB CP600-eCo Operating instruction

Honeywell
Honeywell AQ25A Series instruction manual

Ayyeka
Ayyeka WAVELET - V2 quick start guide

Extron electronics
Extron electronics IPCP Pro Series Setup guide

Zanussi
Zanussi Supertredilwash 641141 brochure

Siemens
Siemens UP 588/135 Operating and mounting instructions

ELCOS
ELCOS NEC-685/500 quick start guide

Danfoss
Danfoss AK-RC 113 installation guide

Global Fire Equipment
Global Fire Equipment JUNIOR MINI-REP installation manual

Bentel Security
Bentel Security Academy8L manual

Cooper Menvier
Cooper Menvier Scantronic 9751 Installation and programming guide