  9. Ditek DTK-240X12 User manual

Ditek DTK-240X12 User manual

DTK-240X12
User Guide
DITEK CORPORATION
One DITEK Center 1720 Starkey Road Largo, Fl 33771
1-800-753-2345 www.diteksurgeprotection.com
DITEK
Surge Protection
MODULE
STATUS
DTK-DFXXXM
XXXVAC
R
ENERGIZED
GROUNDED
GOOD
REPLACE
MADE IN USA
DEFLECTOR
SERIES
Pat. www.diteksurgeprotection.com/patents
Model: DTK-DFXXXM SPD TYPE 2CA
Electrical Ratings: XXXVAC, 20A, 50/60 Hz, Single Phase
Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA
MCOV Rating: 150 L-N, 150 L-G
VPR: 600 L-N, 600 L-G
Suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amperes, XXX Volts maximum when pro-
tected by a 20 ampere circuit breaker rated 120 volts minimum.
Convient a des circuits produisant au plus 10,000 A eff.
WARNING - SHOCK HAZARD - DO NOT OPEN
AVERTISSEMENT - RISQUE DE CHOC
NE PAS OUVRIR
CU
R
US
DTK-240X12
(Mounting Dimensions)
Ø0.22
TYP 4 PLCS
7.00
8.25
DITEK
Surge Protection
MODULE
STATUS
DTK-DFXXXM
XXXVAC
R
ENERGIZED
GROUNDED
GOOD
REPLACE
MADE IN USA
DEFLECTOR
SERIES
Pat. www.diteksurgeprotection.com/patents
Model: DTK-DFXXXM SPD TYPE 2CA
Electrical Ratings: XXXVAC, 20A, 50/60 Hz, Single Phase
Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA
MCOV Rating: 150 L-N, 150 L-G
VPR: 600 L-N, 600 L-G
Suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amperes, XXX Volts maximum when pro-
tected by a 20 ampere circuit breaker rated 120 volts minimum.
Convient a des circuits produisant au plus 10,000 A eff.
WARNING- SHOCK HAZARD - DO NOT OPEN
AVERTISSEMENT- RISQUE DE CHOC
NEPAS OUVRIR
CU
R
US
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
11.50
2.34 2.34
3/4" NPT CONDUIT FITTING
1/2" NPT CONDUIT FITTING
3/4" NPT CONDUIT FITTING
1/2" NPT CONDUIT FITTING
3/4" NPT CONDUIT FITTING
1/2" NPT CONDUIT FITTING
3/4" NPT CONDUIT FITTING
1/2" NPT CONDUIT FITTING
10.00
DTK-240X12 (240VAC 20A + 12 Low Voltage Circuit Series Surge Protective Device)
Read All Instructions Before Beginning Installation!
CAUTION: Risk of Electric Shock - Only intended for installation in accordance with
National Electric Code, ANSI/NFPA-70, Article 398.
Warning: Turn power off at the main circuit breaker panel before beginning install.
Note: Connect this device in series between the 240VAC power supply and the load that requires
protection. Use 12 AWG Stranded, Cu only conductors with a 3/8” strip length when terminating
the wires at the power lugs. The conductors used to connect the SPD, to the supply or buss and to
ground, shall not be any longer than necessary and shall avoid unnecessary bends.
1. Remove (4) screws securing the cover, save screws.
2. Remove cover.
3. Connect a Ground (green or bare conductor) to the EARTH lug at the LINE side.
4. Connect the Neutral (white conductor) supply wire to the NEUT lug at the LINE side..
5. Connect the Phase (black conductor) supply wire to the LINE IN lug at the LINE side.
6. Connect the Ground, Neutral and Phase wires from the LOAD side to the control panel, or your
equipment’s AC inputs.
Note: Tightening torque for the 240VAC power connections is 20 in-lb.
7. Use 3/4” conduit fittings for the AC circuit and a 1/2” conduit fitting for dry contacts. Best practice
dictates the use of separate conduit feeds to isolate the unprotected “LINE” wiring from protected
“LOAD” wiring
8. After all connections have been made and no hazards exist, proceed to the Low Voltage Surge
Module Wiring Diagram.
NC C NO
DRY CONTACT
120VAC(+)
NEUTRAL(-)
LOAD: 120VAC, 1AMP (MAX)
30VDC, 2AMP (MAX)
EXAMPLE MONITORING CIRCUIT
DRY CONTACT CIRCUIT INFORMATION
EARTH
NEUT
LINE IN
EARTH
NEUT
LINE OUT
DITEK
Surge Protection
R
NC C NO
EXAMPLE REMOTE MONITORING
USING FACP FOR NOTIFICATION
EARTH
NEUT
LINE
240VAC TO FACP
TO FACP AUXILIARY CONTACTS OR
ADDRESSABLE MONITOR MODULE
240VAC, 20AMP SINGLE
POLE BREAKER TO BE
FIELD VERIFIED
NC C NO
-LINE SIDE
-INPUT
-UNPROTECTED
240VAC, 20AMP
-LOAD SIDE
-OUTPUT
-PROTECTED
240VAC, 20AMP
POWER LUGS
#12 AWG
INPUT/LINE
LOAD
LINE
Wiring Diagram-240VAC Protection Circuit
POWER LUGS
#12 AWG
OUTPUT/LOAD
#30-12 AWG
DTK-240X12
(Wiring Diagram-Low Voltage Surge Modules With Dry Contact Circuit)
DTK-2MHTP (2-Pair Modular Hybrid Telco Protector)
1. Connect the tele-communication circuit(s) from the field to the side marked UN-PROTECTED. The first pair is connected to the
terminals marked 1+ and 1- . If a second pair is used, connect to the terminals marked 2+ and 2- .
2. Connect the tele-communication circuits(s) for the alarm panel supply wiring, for the dialer circuit, to the side marked PROTECTED.
1. Connect the SLC, IDC, PIV*or NAC*loop circuit wiring from the field to the side marked UN-PROTECTED. The first pair is connected
to the terminals marked 3+ and 3- . If a second pair is used, connect to the terminals marked 4+ and 4- . If additional circuits need
to be protected, continue with 5+, 5- and 6+, 6- through 12+, 12-.
* Do not use DTK-2MHLPxxF for PIV or NAC circuits.
2. Connect the SLC, IDC, PIV or NAC loop circuit wiring, for the alarm panel inputs, to the side marked PROTECTED.
3. After all connections have been made and no hazards exist, replace cover, and proceed to the surge module installation sections.
DTK-2MHLPXXB, DTK-2MHLPXXF (2-Pair Modular Hybrid Line Protector)
Notes: Connect this device in series between the field wiring and the control panel supply wiring.
• These Low Voltage protection circuits are equipped with a removable plug and header assembly. Simply remove the plug from the
header, terminate your wires, then replace the plug making sure it seats and snaps into place.
•There are up to 6 positions for surge modules available for protection of any combination of Dialer Circuit, SLC (Signaling),
IDC (Initiating), PIV (Valve) or NAC (Notifying) circuits. Each module will protect 2 pairs or circuits of the same voltage.
•All modules have been factory pre-wired for ground. It is not necessary to make any additional ground connections.
•Allow for sufficient reaction time by providing a minimum of 3 wire feet between the DTK-240X12 and the alarm panel inputs.
•Use separate conduit feeds to isolate the unprotected “INPUT” wiring from the protected “OUTPUT” wiring.
•Use appropriately sized conduit fittings and conduit (not included).
-FIELD WIRING
-INPUT*
-UNPROTECTED
-SUPPLY
-OUTPUT*
-PROTECTED
#30-12 AWG
DITEK
Surge Protection
R
1-2 3-4
5-6 7-8
9-10 11-12
EARTH
NEUT
LINE IN
EARTH
NEUT
LINE OUT
2- 2+ 1- 1+4- 4+ 3- 3+6- 6+ 5- 5+12- 12+ 11- 11+ 10- 10+ 9- 9+ 8- 8+ 7- 7+
2- 2+ 1- 1+
4- 4+ 3- 3+6- 6+ 5- 5+
12- 12+ 11- 11+ 10- 10+ 9- 9+ 8- 8+ 7- 7+
NC C NO
LOAD
LINE
UN-PROTECTEDPROTECTED
WHEN USING
THE DRY CONTACT
CIRCUIT, USE THIS
1/2” CONDUIT
SOLELY FOR THE
DRY CONTACT
CONDUCTORS
DTK-2MHTP (2-Pair Modular Hybrid Telco Protector)
1. Connect the tele-communication circuit(s) from the field to the side marked UN-PROTECTED. The first pair is connected to the
terminals marked 1+ and 1- . If a second pair is used, connect to the terminals marked 2+ and 2- .
2. Connect the tele-communication circuits(s) for the alarm panel supply wiring, for the dialer circuit, to the side marked PROTECTED.
1. Connect the SLC, IDC, PIV*or NAC*loop circuit wiring from the field to the side marked UN-PROTECTED. The first pair is connected
to the terminals marked 3+ and 3- . If a second pair is used, connect to the terminals marked 4+ and 4- . If additional circuits need
to be protected, continue with 5+, 5- and 6+, 6- through 12+, 12-.
* Do not use DTK-2MHLPxxF for PIV or NAC circuits.
2. Connect the SLC, IDC, PIV or NAC loop circuit wiring, for the alarm panel inputs, to the side marked PROTECTED.
3. After all connections have been made and no hazards exist, replace cover, and proceed to the surge module installation sections.
DTK-2MHLPXXB, DTK-2MHLPXXF (2-Pair Modular Hybrid Line Protector)
Notes: Connect this device in series between the field wiring and the control panel supply wiring.
• These Low Voltage protection circuits are equipped with a removable plug and header assembly. Simply remove the plug from the
header, terminate your wires, then replace the plug making sure it seats and snaps into place.
•There are up to 6 positions for surge modules available for protection of any combination of Dialer Circuit, SLC (Signaling),
IDC (Initiating), PIV (Valve) or NAC (Notifying) circuits. Each module will protect 2 pairs or circuits of the same voltage.
•All modules have been factory pre-wired for ground. It is not necessary to make any additional ground connections.
•Allow for sufficient reaction time by providing a minimum of 3 wire feet between the DTK-240X12 and the alarm panel inputs.
•Use separate conduit feeds to isolate the unprotected “INPUT” wiring from the protected “OUTPUT” wiring.
•Use appropriately sized conduit fittings and conduit (not included).
-FIELD WIRING
-INPUT*
-UNPROTECTED
-SUPPLY
-OUTPUT*
-PROTECTED
#30-12 AWG
DITEK
Surge Protection
R
1-2 3-4
5-6 7-8
9-10 11-12
EARTH
NEUT
LINE IN
EARTH
NEUT
LINE OUT
2- 2+ 1- 1+4- 4+ 3- 3+6- 6+ 5- 5+12- 12+ 11- 11+ 10- 10+ 9- 9+ 8- 8+ 7- 7+
2- 2+ 1- 1+4- 4+ 3- 3+6- 6+ 5- 5+
12- 12+ 11- 11+ 10- 10+ 9- 9+ 8- 8+ 7- 7+
NC C NO
LOAD
LINE
UN-PROTECTEDPROTECTED
IF NOT USING
THE DRY CONTACT
CIRCUIT, THIS
1/2” CONDUIT CAN
BE USED FOR THE
LOW VOLTAGE
LOOP CIRCUITS
DTK-240X12
(Wiring Diagram-Low Voltage Surge Modules Without Dry Contact Circuit)
DTK-DF240M
(240VAC Surge Module Installation)
The DTK-240X12 is a series connected Surge Protective Device, for 240VAC power plus up to 12
individual low voltage circuits, with a replaceable surge module for the 240VAC power and every
2-Pairs of low voltage circuits. The LED indicators on the top face of the DTK-DF240M surge
module provide power, ground and surge module health status. When the DTK-DF240M surge
module has gone end of life, the large “REPLACE” RED LED will illuminate and the “GOOD”
Green LED will turn off. Also, the audible alarm will sound to provide an extra alert to indicate
the surge module’s health. To silence the alarm, remove the dead module and replace it with a
new, unused module. If a new module is not available, the alarm can be silenced by pressing the
tactile switch, located at the end of the enclosure, into BYPASS mode for 24 hours. When a new
DTK-DF240M surge module is installed, the audible alarm will be cancelled. The red polarizing
keys insure that the correct voltage module will mate with its correct base.
WARNING: When the DTK-DF240M module has gone end of life, or is missing, the base is
susceptible to damage from surge energy. Make sure you always have a spare module
available. No substitutions shall be permitted.
DITEK
Surge Protection
MODULE
STATUS
DTK-DF240M
240VAC
R
ENERGIZED
GROUNDED
GOOD
REPLACE
MADE IN USA
DEFLECTOR
SERIES
Pat. www.diteksurgeprotection.com/patents
Model: DTK-DF240M SPD TYPE 2CA
Electrical Ratings: 240VAC, 20A, 50/60 Hz, Single Phase Nominal
Discharge Current Rating: (In): 5kA, SCCR: 10kA
MCOV Rating: 300 L-N, 300 L-G
VPR: 1200 L-N, 1200 L-G
Suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amperes, 240 Volts maximum when pro-
tected by a 20 ampere circuit breaker rated 240 volts minimum.
Convient a des circuits produisant au plus 10,000 A eff.
WARNING - SHOCK HAZARD - DO NOT OPEN
AVERTISSEMENT - RISQUE DE CHOC
NE PAS OUVRIR
CU
R
US
Front Back
MODULE
STATUS
ENERGIZED
GROUNDED
GOOD
REPLACE
DITEK
Surge Protection
MODULE
STATUS
DTK-DFXXXM
XXXVAC
R
ENERGIZED
GROUNDED
GOOD
RE-
MADE IN USA
DEFLECTOR
SERIES
Pat. www.diteksurgeprotection.com/patents
Model: DTK-DFXXXM SPD TYPE 2CA
Electrical Ratings: XXXVAC, 20A, 50/60 Hz, Single Phase
Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA
MCOV Rating: 150 L-N, 150 L-G
VPR: 600 L-N, 600 L-G
Suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amperes, XXX Volts maximum when pro-
tected by a 20 ampere circuit breaker rated 120 volts minimum.
Convient a des circuits produisant au plus 10,000 A eff.
WARNING- SHOCK HAZARD - DO NOT OPEN
AVERTISSEMENT- RISQUE DE CHOC
NEPAS OUVRIR
CU
R
US
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DITEK R
DTK-2MHLP
DTK-2MHTP
5 12 24 36 48 75 130
MODULAR SURGE PROTECTION
VOICE - DATA - SIGNAL
DTK-240X12
(Low Voltage Surge Modules Installation)
Remove the slide cover from the low voltage surge modules compartment. Insert the appropriate
low voltage surge module into the corresponding position according to your connection circuits.
When a DTK-2MHTP tele-communications surge module has expired (gone end of life), there will
be interference or an open circuit to the control panel, indicating the circuit requires service.
When a DTK-2MHLPxxB low voltage surge module has expired (gone end of life), there will be a
ground fault indicating the circuit requires service.
When a DTK-2MHLPxxF* low voltage surge module has expired (gone end of life), there will be an
open circuit, indicating the circuit requires service. *Do not use with PIV or NAC circuits.
After all modules are inserted, replace slide cover and fasten.
Restore power and verify correct operation.
DITEK
Surge Protection
MODULE
STATUS
DTK-DFXXXM
XXXVAC
R
ENERGIZED
GROUNDED
GOOD
REPLACE
MADE IN USA
DEFLECTOR
SERIES
Pat. www.diteksurgeprotection.com/patents
Model: DTK-DFXXXM SPD TYPE 2CA
Electrical Ratings: XXXVAC, 20A, 50/60 Hz, Single Phase
Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA
MCOV Rating: 150 L-N, 150 L-G
VPR: 600 L-N, 600 L-G
Suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amperes, XXX Volts maximum when pro-
tected by a 20 ampere circuit breaker rated 120 volts minimum.
Convient a des circuits produisant au plus 10,000 A eff.
WARNING- SHOCK HAZARD - DO NOT OPEN
AVERTISSEMENT- RISQUE DE CHOC
NEPAS OUVRIR
CU
R
US
Audible alarm bypass switch. This is push button tactile switch that will silence the alarm for 24 hours.
When a new DTK-DF240M surge module is installed, the alarm will reset.
Slide Cover
DITEK CORPORATION
One DITEK Center 1720 Starkey Road Largo, Fl 33771
1-800-753-2345 www.diteksurgeprotection.com Doc # INT-100203-001
Part No. 191646 Rev. 1
DTK-240X12
THIS PAGE LEFT INTENTIONALLY BLANK
Drawn By: B. Aycock 5-7-2020
Revised By: R. Mitchell 6-18-2020

This manual suits for next models

1

Other Ditek Surge Protector manuals

Ditek DTK-TSS5 User manual

Ditek

Ditek DTK-TSS5 User manual

Ditek DR Series User manual

Ditek

Ditek DR Series User manual

Ditek DEFLECTOR Series User manual

Ditek

Ditek DEFLECTOR Series User manual

Ditek D50-2403D Configuration guide

Ditek

Ditek D50-2403D Configuration guide

Ditek DTK-RM12NETS Configuration guide

Ditek

Ditek DTK-RM12NETS Configuration guide

Ditek DTK-SNAP-LITE Series User manual

Ditek

Ditek DTK-SNAP-LITE Series User manual

Ditek D200-277/4803Y Configuration guide

Ditek

Ditek D200-277/4803Y Configuration guide

Ditek DTK-110C6A Configuration guide

Ditek

Ditek DTK-110C6A Configuration guide

Ditek DTK-TSS2 User manual

Ditek

Ditek DTK-TSS2 User manual

Ditek DTK-DF120S1 User manual

Ditek

Ditek DTK-DF120S1 User manual

Ditek D200-120/2401 Configuration guide

Ditek

Ditek D200-120/2401 Configuration guide

Ditek D200-347/6003Y Configuration guide

Ditek

Ditek D200-347/6003Y Configuration guide

Ditek DTK-TSS4D Configuration guide

Ditek

Ditek DTK-TSS4D Configuration guide

Ditek DTK-DF240S12 User manual

Ditek

Ditek DTK-DF240S12 User manual

Ditek DTK-RM12POE Configuration guide

Ditek

Ditek DTK-RM12POE Configuration guide

Ditek ZEUS Series User manual

Ditek

Ditek ZEUS Series User manual

Ditek D200-120/2083Y Configuration guide

Ditek

Ditek D200-120/2083Y Configuration guide

Ditek DTK-WM4 Series Configuration guide

Ditek

Ditek DTK-WM4 Series Configuration guide

Ditek DTK-RM12ETH Configuration guide

Ditek

Ditek DTK-RM12ETH Configuration guide

Ditek DR Series User manual

Ditek

Ditek DR Series User manual

Ditek D50-277/4803Y Configuration guide

Ditek

Ditek D50-277/4803Y Configuration guide

Ditek D200-4803D Configuration guide

Ditek

Ditek D200-4803D Configuration guide

Ditek DTK-DP4P User manual

Ditek

Ditek DTK-DP4P User manual

Ditek DTK-RM12POE Configuration guide

Ditek

Ditek DTK-RM12POE Configuration guide

Popular Surge Protector manuals by other brands

CyberPower CPS1090 quick guide

CyberPower

CyberPower CPS1090 quick guide

MTL Surge Technologies TP-P48 installation guide

MTL Surge Technologies

MTL Surge Technologies TP-P48 installation guide

Panamax MR4300 reference guide

Panamax

Panamax MR4300 reference guide

M-system MAT2 Series instruction manual

M-system

M-system MAT2 Series instruction manual

CyberPower B704 user manual

CyberPower

CyberPower B704 user manual

Genie GSP manual

Genie

Genie GSP manual

Sven CLASSIC user manual

Sven

Sven CLASSIC user manual

Furman M-85 Merit Series owner's manual

Furman

Furman M-85 Merit Series owner's manual

Liebert Liebert LPGE Series Technical specifications

Liebert

Liebert Liebert LPGE Series Technical specifications

Chenzhu CZLB-EX Series user manual

Chenzhu

Chenzhu CZLB-EX Series user manual

CyberPower 649532008957 Specification sheet

CyberPower

CyberPower 649532008957 Specification sheet

Leviton 5480 installation instructions

Leviton

Leviton 5480 installation instructions

Transtector CPX Series installation instructions

Transtector

Transtector CPX Series installation instructions

Nixzen NX-N-USP201V user manual

Nixzen

Nixzen NX-N-USP201V user manual

IFTOOLS ISOUSB-PLUS operating manual

IFTOOLS

IFTOOLS ISOUSB-PLUS operating manual

Siemens TPS3 11 user manual

Siemens

Siemens TPS3 11 user manual

Current Technology CGC Series Installation, operation and maintenance manual

Current Technology

Current Technology CGC Series Installation, operation and maintenance manual

M-system MD7RB-FF instruction manual

M-system

M-system MD7RB-FF instruction manual