Operating instructions
1592001620
1592001620 XC450D GB R1.0 10.07.2009 XC450D 3/3
did LL liquid alarm delay: 0 ÷ 255 min. Delay between the detection of the LL
liquid alarm condition and its signalling.
iP4 Alarm stop polarity from pressure switch: oP: the digital input is activated by
opening the contact; CL: the digital input is activated by closing the contact.
iP5 By-pass input polarity: oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
ALIP Alarm input for compressors and fans polarity
oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
COMPRESSORS REGULATION
Pbd Proportional band or neutral zone width (0.10÷10.0 bar). The band (or zone)
is symmetrical compared to the target set point, with extremes: SET-Pbd/2 and
SET+Pbd/2.
Onon Minimum time between 2 following switching ON of the same compressor
(0÷255min).
oFon Minimum time between the switching off of a compressor and the
following switching on (0÷255min)
don Time delay between the insertion of two different compressors (0÷99.5
min; ris. 10s).
doF Time delay between switching off of two different compressors (0÷99.5
min; ris. 10s).
odo Count time with by-pass input ON (0÷255min)
LSE Minimum set point for compressors.
HSE Maximum set point for compressors.
ALARMS – COMPRESSOR SECTION
PAo: Alarm probe exclusion at power on. it is the period starting from instrument
switch on, before an alarm probe is signalled. (0÷255 min). During this time if the
pressure is out of range all the compressor are switched on.
LAL: Low pressure (temperature) alarm: The measurement unit depends on dEU
parameter. It’s always subtracted to the set point. When the value SET-LAL is
reached the A03C alarm is enabled, (possibly after the tAo delay time).
HAL: High pressure (temperature) alarm: The measurement unit depends on dEU
parameter. It’s always added to the set point. When the value SET+HAL is
reached the A04C alarm is enabled, (possibly after the tAo delay time).
tAo: Low and High pressure (temperature) alarms delay: (0÷255 min) time
interval between the detection of a pressure (temperature) alarm condition and
alarm signalling.
SPr: Number of steps engaged with faulty probe. (0÷#compr).
OTHER
tbA Alarm relay silencing: by pushing one of the keypad buttons. no= alarm relay
stays on; yES=alarm relay is switched off by pushing any keys.
OAP Alarm relay output polarity: cL=closed when activated; oP= opened when
activated
oFF Switching ON/OFF enabling from keyboard: (no = disabled; yES= enabled)
It permits the switching ON/OFF of the instrument by pressing the SET key for
more than 4s.
Ad1: Compressors address (1 –247) It is used in monitoring system.
Ad2: Fans address (1 –247) It is used in monitoring system.
Ptb Parameter table code: readable only.
rEL Software release for internal use.
Pr2 Access to the protected parameter list (read only).
TYPE OF REGULATION
- OFF: the instrument doesn’t make the regulation; it detects the LL liquid alarm and the
P1 broken transducer.
- REGULATION ON: when the digital input is activated or set manually by pushing the
DOWN key for 3s. Compressors depends on th SetC and Pbd parameters.
- RESET REGULATION ON: turning off and on the controller, or with DOWN key during
3”.
Functioning mode:
rtY=db neutral zone: If the pressure (temperature) is inside this zone the controller
maintains the same number of loads switched on and off, without changing anything.
When the pressure (temperature) go out from the zone, regulation starts.
rtY=Pb proportional band: The regulation band (Pbd) is divided into as many parts
as there are stages. The numbers of stages switched ON is proportional to the value
of the input signal: when this distances itself from the target set point and enters the
various bands, the compressors are switched ON, to be then turned OFF when the
signal brings near the set point. In this way if the pressure is greater than regulation
band, all the compressors are on, if the pressure (temperature) is lower than the
regulation band all the compressors are off.
SAFETY TIMES
A load is turned ON onlyif the safety times onon, oFon, donF are over.
Regulation stops when the pressure (temperature) come back into the neutral zone.
CONFIGURATION AND ALARM DIAGNOSTICS
DIGITAL INPUTS FOR COMPRESSOR SAFETY
ALIP: It establishes if the input is activated by closing (ALIP=cL) or by opening (ALIP=oP)
the id1, id2, id3 contacts.
Actions
Every time one input is activated the corresponding output is turned off.
P1 probe failure alarm
It is generated by failure in the transducer.
SPr: number of steps engaged with faulty probe.
It is an alarm signal with the activation of: relay, buzzer and P1 and P2 code display.
Recovery
Automatic as soon as probe restarts working.
HA, LA: LA2 High and low pressure (temperature) alarms
This alarm signals that the pressure (temperature) is out of limits established by
parameters LAL – SetC+ HAL.
The tAo and AFd parameters set the delay between alarm condition and alarm signalling.
Action
The alarm is signalled with standard action. The outputs are unchanged.
ALARM MUTING
Press any buttons to silence the buzzer during an alarm condition.
Hold pressed for more than 3 seconds switch off the alarm relay during an alarm condition
PARAMETERS – DEFAULT VALUES
Name bar Level Description Range
SEtc 3.0 -- Set Point for pressure LSE ÷ HSE
oA4 Cpr Pr2 Output 4 configuration cPr / FAn / StP / ALr / Lin/
nu/Liq/MAn
oA5 Cpr Pr2 Output 5 configuration cPr / FAn / StP / ALr / Lin/
nu/Liq/MAn
oA6 Cpr Pr2 Output 6 configuration cPr / FAn / StP / ALr / Lin/
nu/Liq/MAn
rtY db Pr2 Typeof regulation db, pb
StY yES Pr2 Compressor rotation no / YES
PA04 0,5 Pr2 Adjustment of read out for the Probe at 4mA 0.0 bar ÷ PA20
PA20 8,0 Pr2 Adjustment of read out for the Probe at 20mA
PA04 ÷ 51.0 bar
cAL 0 Pr2 Probe 1 calibration -12.0 ÷ 12.0
DIGITAL INPUTS
i1C CL Pr2 Liquid alarm polarity oP / cL
did 60 Pr2 Liquid alarm signalling delay 0 ÷ 255 min.
iP4 CL Pr2 Alarm stop polarity from pressure switch oP / cL
iP5 CL Pr2 By-pass input polarity oP / cL
ALiP CL Pr2 Alarm input for compressors and fans polarity oP / cL
REGULATION
Pbd 0.6 Pr2 Proportionalband of compressors > 0 ÷ 10.0 bar
onon 5 Pr2 Minimum time between 2 following switching
ON 0 ÷ 255 min.
oFon 2 Pr2 Minimum time between the switching off and
on 0 ÷ 255 min.
don 0,3 Pr2 Time delaybetween the insertion of two
different compressors 0 ÷ 99.5 min.( res. 10 “)
doF 0,1 Pr2 Time delaybetween switching off of two
different compressors 0 ÷ 99.5 min. (res.10”. )
odo 10 Pr2 Regulation delay on start-up 0 ÷ 255 minuti
LSE 0,5 Pr2 Minimum set point for compressors PA04 ÷ HSE
HSE 4,0 Pr2 Maximum set point for compressors LSE ÷ PA20
PRESSURE ALARMS
PAo 30 Pr2 Alarm probe exclusion at power on 0 ÷ 255 min.
LAL 10 Pr1 Low pressure (temperature) alarm –
compressor section > 0 ÷ 30.0 bar
HAL 10 Pr1 High pressure (temperature) alarm–
compressor section > 0 ÷ 30.0
tAo 10 Pr1 Low and High pressure (temperature) alarms
delay– compressor section 0 ÷ 255 min.
SPr 2 Pr2 Number of steps engaged with faulty probe 0 ÷ oA6
tbA no Pr2 Alarm relay silencing no / YES
OAP cL Pr2 Alarm relayoutput polarity oP ÷ cL
OTHER
oFF Yes Pr2 Switching ON/OFF enabling from keyboard no / YES
Ad1 1 Pr2 Serialaddress 1 ÷ 247
rEL - Pr2 Release micro readable only
Ptb - Pr2 Parameter table code readable only
Pr2 Pr1 Password protected menu readable only