INSTRUCTION MANUAL
POWER SUPPLY
TYPE FP9000 P
GENERAL DESCRIPTION
Power supply, type FP9000 P is an independent feeding device of combined type –back up battery and battery
charger.
Its function is to ensure continuous power supply for devices in fire-alarming and fire-detecting installations and
automation of the fire protection equipment.
The feeder complies with the provisions set in the European Standard EN 54-4.
FP9000 P consists of:
−feeding module ;
−two back up batteries; The back up batteries are not included in the content of the delivery.
−Connecting terminals and a fuser 220V
The power supply front panel provides indication for the following conditions:
−Duty Mode (green LED)
−Fault condition (yellow LED). The fault condition could be mains voltage failure 220V or interrupted fuse AC; fault
or missing back up battery; interrupted fuse ACU; interrupted fuse User ;
–Low battery, back up battery or interrupted fuse ACU (yellow LED);
–mains voltage failure 220V AC or interrupted fuse AC (yellow LED);
–interrupted fuse User (yellow LED).
Upon fault condition the relay output is switched, too.
On the supply module the following terminals are located for connection to:
−the relay contacts for fault condition;
−voltage terminal 28V / 2.0A ;
TECHNICAL DATA
−Input voltage: - (187-253)V AC, 50 / 60 Hz
−Maximum current consumption - 56VА
−Output voltage - (17-27.6)V DC
−Output current - 2.0А
−Maximum output current - 3.5А for 15 minutes
−Middle charging current - 0.8А
−Overcharging protection - at voltage < 17V
−Output for fault condition - relay, potential free switching, 1А / 30V DC
−Maximum section of the connecting wires - 2,5 mm2