domat AERASGARD KLQ-W Repair manual

AERASGARD
®
KLQ- W
AERASGARD
®
KLQ- SD
{
G
{
Návod k použití
Kanálový snímač kvality vzduchu (VOC) a měřicí převodník
vč. montážní příruby, s autokalibrací, s vícerozsahovým
spínáním a aktivním / spínacím výstupem
G
Operating Instructions, Mounting & Installation
Duct air quality sensors (VOC) and measuring transducers,
including installation flange, self-calibrating, with multi-range
switching and active ⁄ switching output
KLQ - W
(IP 65)
KLQ - SD
(IP 54)
6000-3440-0000-1XXD1 34400-2020-D1 V106 08 ⁄ 2020
Domat Control System s.r.o.
U Panasonicu 376
530 06 Pardubice-Stare Civice
CZ Česká republika
Tel.: +420 461 100 823
Fax: +420 226 013 092
info@domat.cz
www.domat-int.com
Gratulujeme!
Zakoupili jste produkt německé kvality.
Congratulations!
You have bought a German quality product.

AERASGARD
®
KLQ- W
AERASGARD
®
KLQ- SD
{
G
MFT - 20 - K
Plastová montážní příruba
Mounting flange, plastic
Montážní schéma
Mounting diagram
> ø 250 mm
> 115 mm
> ø 250 mm
> 115 mm
Rozměry
Dimensional drawing
KLQ - W
KLQ - SD
KLQ - W
KLQ - SD
14.8
37.8
M16x1.5
ø32.3
12
13.4
202.5 37.8
ø20
60
87
~30
32
62
ø
5.2
ø
20
M4
ø
4.3
39
49
~107
72
64
14.8
37.8
M16x1.5
ø32.3
12
13.4
202.5 37.8
ø20
60
87
~30
32
62
ø
5.2
ø
20
M4
ø
4.3
39
49
~107
72
64

{
G
AERASGARD
®
KLQ- W
Schéma zapojení
KLQ-W
Connecting diagram
KLQ-W
Instalační schéma
KLQ - SD - U
1
2
3
UB+ 24V st/ss
Výst. kvalita vzduchu
0-10V
UB– GND
Schematic diagram
KLQ - SD - U
1
2
3
UB+ 24V AC/DC
Output
air quality
0-10V
UB– GND
1234
ON DIP
SET
Zero
OFFSET
13 11 12 123
Rozp. kont.
Spín. kont.
Výst. kvalita vzduchu
–UB GND
+UB 24V st/ss
1234
ON DIP
SET
Zero
OFFSET
13 11 12 123
Breaker
Normally
open contact
Output air quality
–UB GND
+UB 24V AC/DC
Zero
123
12
ON
DIP
VOC
Výst. kvalita vzduchu 0-10V
–UB GND
+UB 24V st/ss
Schéma zapojení
KLQ - SD - U
Zero
123
12
ON
DIP
VOC
Output air quality 0-10V
–UB GND
+UB 24V AC/DC
Connecting diagram
KLQ - SD - U
1
2
3
12
11
13
UB+ 24V st/ss
Výst. kvalita vzduchu
0-10V/4...20mA
UB– GND
Rozp. kont.
Spín. kont.
C/O
24V/1A
Instalační schéma
KLQ-W
1
2
3
12
11
13
UB+ 24V AC/DC
Output air quality 0-10V / 4...20mA
UB– GND
Breaker changeover
24V/1A
Normally
open contact
Schematic diagram
KLQ-W

{
AERASGARD®KLQ - SD
/
KLQ - W
Rev. 2020 - V34
Patentovaná kvalita (patent č. DE 10 2014 010 719.1)
Bezúdržbové kanálové čidlo
AERASGARD
®
KLQ-SD
s aktivním výstupem, automatickou kalibrací, (fixně nastavenou) v kompaktním krytu, s
naklapovacím víkem, slouží k detekci kvality vzduchu ve třech úrovních citlivosti (nízká, střední, vysoká). Převádí naměřené hodnoty na standardní
signál 0-10 V.
Bezúdržbové kanálové čidlo
AERASGARD
®
KLQ-W
s aktivním / spínacím výstupem, s automatickou kalibrací (lze vypnout) v kompaktním plastovém
krytu s rychloupínacími šrouby, se používá pro měření kvality vzduchu ve třech úrovních citlivosti (nízká, střední, vysoká). Naměřená hodnota je
převedena na standardní signál 0-10 V nebo 4…20 mA (přepínatelné).
Čidlo se používá v kancelářích, hotelech, konferenčních centrech, bytech, obchodech, atd. pro účely vyhodnocení klima. Toto použití čidla také ve
ventilaci pro potřeby zvýšení pobytového komfortu a snížení provozních nákladů díky úsporám energie.
Kvalita vzduchu je detekována
čidlem VOC
(těkavé organické látky). Čidlo se používá pro kvalitativní hodnocení znečistění vzduchu v místnosti se
znečisťujícími plyny (cigaretový kouř, tělesný pach, vydechovaný vzduch, výpary rozpouštědel, emise ze stavebních zařízení a čistící prostředky).
S ohledem na očekávané znečištění vzduchu je možné čidlo nastavit na jednu ze tří úrovní citlivosti.
TECHNICKÉ ÚDAJE
Napájení: 24 V st ⁄ ss (± 10%)
Spotřeba: < 1,5W ⁄ 24 V ss typicky;
< 2,9 VA ⁄ 24 V st typicky; špičkový proud 200 mA
Senzor: VOC senzor (metal oxid) (volatile organic compounds), s manuální kalibrací (pomocí tlačítka Zero),
KLQ - SD
s automatickou kalibrací (trvale)
KLQ - W
s automatickou kalibrací (deaktivovatelná pomocí DIP přepínačů)
Měřící rozsah: 0...100 % kvalita vzduchu; podle kalibračního plynu;
vícerozsahové spínání
(rozsah volitelný pomocí DIP přepínačů)
VOC citlivost nízká, střední, vysoká
Výstup: (0 V = čistý vzduch, 10V = znečištěný vzduch)
KLQ - SD
0 -10 V (pevný)
KLQ - W
0 -10 V
nebo
4...20 mA, pracovní odpor < 800 Ω (volitelný pomocí DIP přepínačů),
s offsetovým potenciometrem (± 10% z měřícího rozsahu)
Výstup relé:
KLQ - SD
bez přepínacího kontaktu
KLQ - W
s bezpotenciálovým
přepínacím kontaktem
(24 V / 1 A), spínací bod nastavitelný
Přesnost měření: typicky ± 20 % z konečné hodnoty (dle kalibračního plynu)
Životnost: > 60 měsíců (za podmínky normálního zatížení),
v závislosti na typu zatížení a koncentrace plynu
Výměna plynů: difuzí
Doba zahřívání: cca. 1 hodina
Doba odezvy: cca. 1 minuta, minimální průtok 0,3 m/s (vzduch)
Pracovní teplota: –10...+60 °C
Elektrické připojení: 0,14 - 1,5 mm2, pomocí šroubových svorek
Kryt: plastový, odolný vůči UV záření, materiál: polyamid, vyztužený 30 %, skleněných kuliček,
barva: bílá (podobná RAL 9016),
KLQ - SD
s naklapovacím víkem,
KLQ -W
s rychloupínacími šrouby
(kombinace s drážkou ⁄ hlavou Phillips)
Rozměry krytu: 72 x 64 x 37,8mm (Tyr 1/Tyr01 bez displeje)
Kabelové připojení:
kabelová průchodka
z plastu (M 16 x 1,5; s odlehčením tahu,
vyměnitelná, max. vnitřní průměr 10,4 mm
Ochranná trubice:
PLEUROFORM
TM, materiál: polyamid (PA6), s ochranou proti zkroucení,
Ø 20 mm, NL = 202,5 mm, vmax = 30 m/s (vzduch)
Procesní připojení: pomocí plastové montážní příruby (součást dodávky)
Třída ochrany: III (podle EN 60 730)
Krytí:
KLQ - SD IP 54
(podle EN 60 529)
*
Krytí testováno ! TÜV SÜD, Zpráva číslo 713160960A (Tyr 01)
KLQ - W IP 65
(podle EN 60 529)
*
Krytí testováno ! TÜV SÜD, Zpráva číslo 713139052 (Tyr 1)
*
kryt ve vestavěném stavu (propustný: PLEUROFORM: IP 30)
Shoda se standardy: CE konformita, elektromagnetická kompatibilita podle EN 61 326, směrnice EMC 2014 ⁄ 30 ⁄ EU
AERASGARD
®
KLQ - SD
Kanálový senzor kvality vzduchu nebo měřící převodník, Standard
AERASGARD
®
KLQ - W
Kanálový senzor kvality vzduchu nebo měřící převodník, Premium
Type ⁄ WG02 Měřící rozsah
VOC
Výstup
VOC
Zařízení
Označení
KLQ - SD
(pevný)
IP 54
KLQ-SD-U 0...100 % 0 -10 V
–
9501-3170-1001-200D1
KLQ - W
(přepínatelný)
IP 65
KLQ-W 0...100 % 0 -10 V ⁄
4...20 mA
Přepínací kontakt 9501-3150-7301-200D1
Poznámka
: Toto zařízení
nesmí
být použito jako bezpečnostní prvek!

{
Montáž a uvádění do provozu
Rev. 2020 - V34
POZOR !
Neexistuje celosvětově jednotná norma vztahující k senzorům
VOC
(Volatile Organic Compounds = těkavých organických látek). Vzhledem k tomu, že
ve
vzduchu se nachází velké množství látek, nepůsobí čidlo selektivně na jednotlivé
složky, ale odráží celkovou kvalitu vzduchu. V principu nemůže být
určení
“špatného” nebo “dobrého” vzduchu striktně splněno, jelikož se jedná o subjektivní
pocit.
Výměna plynu v senzorovém elementu probíhá difuzí. V závislosti na změně
koncentrace a rychlosti proudění vzduchu v prostředí snímače může být
reakce
zařízení na změnu koncentrace zpožděna. Montážní poloha zařízení musí být zvolena tak, aby okolo snímače proudil vzduch. V opačném případě
může být výměna plynu významně zpomalena nebo omezena.
Automatická kalibrace kvality vzduchu (výchozí)
Automatická kalibrační logika je samokalibrační technika vhodná pro použití v aplikacích,
kde kvalita vzduchu pravidelně klesá na úroveň čerstvého vzduchu.
To většinou nastává v době, kdy jsou místnosti neobsazeny.
Senzor dosahuje své normální přesnosti po 24 hodinách nepřetržitého provozu v
prostředí s přísunem /přístupem čerstvého vzduchu. Chyby a odchylky zůstávají
minimální, pokud je snímač vystaven čerstvému vzduchu minimálně čtyřikrát během
28 dnů. Správný provoz vyžaduje nepřetržitý pracovní cyklus trvající déle než 24 hodin.
Manuální kalibrace kvality vzduchu
Po připojení zařízení dbejte na zajištění nepřetržitého provozu po dobu nejméně dvou
hodin s kvalitou vzduchu nastavenou na “normální”.
Manuální kalibraci lze spustit stisknutím tlačítka ZERO (po dobu cca 5 sekund) bez
ohledu na polohu přepínače DIP 3. Započetí procesu kalibrace je indikováno blikáním
LED. Následně proběhne kalibrace.
Následně proběhne kalibrace. Během této fáze LED stále svítí a běží odpočet
(600 sekund).
Uvádění do provozu
Po zapnutí zařízení se provede automatický test a čidlo je temperováno.
Tento proces trvá přibližně 30 až 50 minut, v závislosti na okolních podmínkách.
Následně lze volitelně provést manuální kalibraci. Je důležité zajistit, aby kalibrace
probíhala na čerstvém vzduchu bez znečištění působícího na snímač.
Nastavení spínacího bodu
Pomocí potenciometru SET lze zvolit spínací bod mezi 10 % a 95 % rozsahu měření.
Bezpotenciálový přepínací kontakt je možné použít jako dvoustavový výstup.
Offset
Offset (posun) změřené hodnoty VOC může být nastaven potenciometrem Offset.
Rozsah nastavení je ± 10 % z měřicího rozsahu.
DIP přepínače
KLQ - W
VOC citlivost DIP 1 DIP 2
LOW - NÍZKÁ OFF OFF
MEDIUM - STŘEDNÍ (výchozí)
O N
OFF
HIGH - VYSOKÁ OFF
O N
VOC automatická nula DIP 3
Deaktivovaná OFF
Aktivovaná (default)
O N
Výstup DIP 4
Napětí 0 -10 V (default) OFF
Proud 4...20 mA
O N
DIP přepínače
VOC citlivost DIP 1 DIP 2
LOW - NÍZKÁ OFF OFF
MEDIUM - STŘEDNÍ (výchozí)
O N
OFF
HIGH - VYSOKÁ OFF
O N

{
Důležité poznámky
– Toto zařízení smí být používáno pouze v neznečištěném bezprašném prostředí bez přetlaku nebo podtlaku působícího na snímač.
– Napěťový výstup je zkratuvzdorný.
– Přepětí může zničit nebo poškodit zařízení.
– V případě znečištění doporučujeme provést vyčištění a rekalibraci.
– Pracovní rozsah zařízení je 10...95 % r.H. nebo 0...+50 °C.
Mimo tento rozsah mohou nastat chyby měření.
– Pokud je zařízení používáno mimo stanovený rozsah, veškerá záruka zaniká.
Naše “Všeobecné obchodní podmínky “společně s “Všeobecnými podmínkami pro dodávky výrobků a služeb v elektrotechnickém a elektronickém
průmyslu "(podmínky ZVEI) včetně dodatečné doložky "Výhrady vlastnictví "platí jako výhradní podmínky.
Dále prosím dbejte na dodržení následujících bodů:
– Před instalací zařízení a uvedením do provozu si přečtěte tyto pokyny a všechny poznámky uvedené v těchto pokynech!
– Přístroje smí být připojeny pouze k bezpečnému nízkonapěťovému napájení. Aby se předešlo poškození a chybám zařízení (např. indukcí napětí),
je třeba používat stíněné kabely, je třeba se vyhnout jejich pokládce paralelně s proudovými vodiči a dodržovat směrnice EMC.
– Toto zařízení se smí používat pouze k určenému účelu. Musí být dodrženy příslušné bezpečnostní předpisy vydané VDE, TÜV, státy, jejich kontrolními
orgány a místní energetickou společností. Kupující musí dodržovat stavební a bezpečnostní předpisy a musí předcházet nebezpečí jakéhokoli druhu.
– Na závady a škody vzniklé v důsledku nesprávného používání tohoto zařízení se nevztahují záruky.
– Na následné škody způsobené poruchou v tomto zařízení se nevztahuje záruka nebo odpovědnost.
– Montáž a uvádění do provozu smí provádět pouze školená osoba.
– Technické údaje, podmínky montáže a provozní návod dodané společně se zařízením jsou bez výhrady platné.
Odchylky od katalogové prezentace nejsou výslovně zmíněny a jsou možné z hlediska technického pokroku a neustálého zlepšování našich produktů.
– V případě jakýchkoli změn provedených uživatelem záruka zaniká.
– Toto zařízení nesmí být umístěno v blízkosti zdrojů tepla nebo být vystaveno jejich vlivu.
Také se zcela vyhněte přímému dopadu slunečního záření nebo ozařování zařízení zpodobných zdrojů světla.
– Používání zařízení v blízkosti jiných zařízení, která neodpovídají směrnicím EMC, může ovlivnit jeho funkčnost.
– Toto zařízení nesmí být používáno jako bezpečnostní prvek, pro monitorovací aplikace, které slouží k ochraně osob před nebezpečím, zraněním nebo jako
NOUZOVÝ VYPÍNAČ pro systémy, stroje anebo pro jiné podobné účely, kde selhání může vést ke škodám na majetku, zdraví či životním prostředí.
– Rozměry krytu nebo příslušenství mohou vykazovat malé odchylky od údajů uvedených v tomto návodu.
– Změny těchto záznamů jsou zakázány.
– Reklamace bude uznána pouze u zařízení vrácených v kompletním originálním balení.
Pokyny k uvádění do provozu:
Přístroj byl kalibrován, nastaven a testován za normovaných podmínek. Při provozu za jiných podmínek doporučujeme ruční justování na místě instalace při
uvádění do provozu a poté v pravidelných intervalech.
Uváděni do provozu je nutnou součástí instalace a musí být provedeno odborným personálem!
Před instalací a uvedením zařízení do provozu se důkladně seznamte se všemi výše uvedenými pokyny a instrukcemi!
Schéma zapojení
Paralelní použití
Schéma zapojení
Samostatné použití
NAPÁJECÍ NAPĚTÍ:
Pro ochranu proti přepólování provozního napětí je v této variantě zařízení
integrován jednocestný usměrňovač nebo ochranná dioda proti přepólování.
Tento vnitřní jednocestný usměrňovač také umožnuje napájet střídavým
proudem i zařízení s výstupem 0-10 V.
Výstupní signál lze měřit měřicím přístrojem. Výstupní napětí je měřeno
proti nulovému potenciálu (0 V) vstupního napětí.
Pokud je toto zařízení napájeno
stejnosměrným napájecím napětím
, musí
být pro napájení UB+ použito 15…36 V ss, svorka UB- nebo GND je pak
použita pro uzemnění!
V případě napájení více těchto zařízení jedním napájecím zdrojem
o napětí
24 V
st musí být zajištěno, aby všechny “kladné” vstupní svorky (+)
provozního napětí byly vzájemně propojeny a všechny vstupní svorky
“záporného” (= referenčního) potenciálu byly vzájemně propojeny (shodná
polarita instalovaných čidel). Všechny výstupy propojených zařízení musí
mít stejný potenciál!
V případě obrácené polarity v jednom z propojených zařízení může toto
zařízení způsobit zkrat napájecího napětí. Následný zkratový proud proudící
tímto zařízením může způsobit jeho poškození.
Věnujte pozornost správnému zapojení!
Obvod Obvod
Výstup
0V/GND
Výstup
0V/GND
Napájení napětí
st 24V~ 0V
ss 15-36V = GND
st 24V~ 0V
ss 15-36V = GND
Obvod
Výstup
0V/GND
Napájení napětí


GAERASGARD®KLQ - SD
/
KLQ - W
Rev. 2020 - V34
Patented quality product (patent no. DE 10 2014 010 719.1)
Maintenance-free duct sensor
AERASGARD
®
KLQ-SD
with active output, automatic calibration (fixed), in a compact plastic housing with snap-on lid,
for determining the air quality in three VOC sensitivity levels (low/medium/high). The measuring transducer converts the measured values into a
standard signal of 0 -10 V.
Maintenance-free duct sensor
AERASGARD
®
KLQ-W
with active/switching output, automatic calibration (can be deactivated), in a compact plastic
housing with quick-locking screws, for determining the air quality in three VOC sensitivity levels (low/medium/high). The measuring transducer
converts the measured values into a standard signal of 0 -10 V or 4...20 mA (switchable).
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The air quality is detected by a
VOC sensor
(mixed gas sensor for volatile organic substances). This sensor determines the loading of the room air
due to contaminated gases such as cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions from building components,
etc. With regard to the expected air contamination, low, medium or high VOC sensitivity can be selected.
TECHNICAL DATA
Power supply: 24 V AC ⁄ DC (± 10%)
Power consumption:
< 1.5 W ⁄ 24 V DC typical;
< 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
Sensor: VOC sensor (metal oxide) (VOC = volatile organic compounds), with manual calibration (via zero button),
KLQ - SD
with automatic calibration (fixed)
KLQ -W
with automatic calibration (can be deactivated via DIP switches)
Measuring range: 0...100 % air quality; referred to calibrating gas;
multi-range switching
(selectable via DIP switches)
VOC sensibility low, medium, high
Output: (0V = clean air, 10V = polluted air)
KLQ - SD
0 -10 V (fixed)
KLQ - W
0 -10 V
or
4...20 mA, working resistance <800 Ω
(selectable via DIP switches), with offset potentiometer (± 10 % of the measuring range)
Relay output:
KLQ - SD
without changeover contact
KLQ - W
with potential-free
changeover contact
(24 V / 1 A), switchpoint adjustable
Measuring accuracy:
typical
± 20 % of final value (referred to calibrating gas)
Service life: > 60 months (under normal load conditions),
depending on the type of loading and gas concentration
Gas exchange: by diffusion
Warm-up time: approx. 1 hour
Response time: approx. 1 minute, minimum flow rate 0.3 m / s (air)
Ambient temperature: –10...+60°C
Electrical connection: 0.14 - 1.5 mm2, via terminals
Housing: plastic, UV-stabilised, material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016),
KLQ - SD
with snap-on lid,
KLQ -W
with quick-locking screws
(slotted ⁄ Phillips head combination)
Housing dimensions: 72 x 64 x 37.8 mm (Tyr 1/Tyr 01 without display)
Cable connection:
cable gland
, plastic (M 16x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm)
Protective tube:
PLEUROFORM
TM,
material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, vmax = 30 m/s (air)
Process connection: by mounting flange, plastic (included in the scope of delivery)
Protection class: III (according to EN 60 730)
Protection type:
KLQ - SD IP 54
(according to EN 60 529)
*
Housing tested, TÜV SÜD, Report No. 713160960A (Tyr 01)
KLQ- W IP 65
(according to EN 60 529)
*
Housing tested, TÜV SÜD, Report No. 713139052 (Tyr 1)
*
Housing in the built-in state (permeable PLEUROFORM: IP 30)
Standards: CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
AERASGARD
®
KLQ - SD
Duct air quality sensor and measuring transducer, Standard
AERASGARD
®
KLQ - W
Duct air quality sensor and measuring transducer, Premium
Type ⁄ WG02 Measuring Range
VOC
Output
VOC
Equipment
Item No.
KLQ - SD
(fixed)
IP 54
KLQ-SD-U 0...100 % 0 -10 V
–
9501-3170-1001-200D1
KLQ - W
(switchable)
IP 65
KLQ-W 0...100 % 0 -10 V ⁄
4...20 mA
changeover contact 9501-3150-7301-200D1
Note: This unit
must not
be used as safety-relevant device!

GInstallation and Commissioning
Rev. 2020 - V34
ATTENTION!
There is no universally uniform standard, which could be applied to a
VOC sensor
(Volatile Organic Compounds). The monitored air contains a large
number of substances to which the sensor responds, and gas mixtures are adjusted. Therefore this sensor does not act selectively, but rather
reflects the overall air quality. In principle, one also cannot state precisely what is "bad air" or what is "good air" because this is a purely subjective
sensation.
The gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air
surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay. It is essential to choose an installation
location for the device in which the air stream flows around the sensor. Otherwise the gas exchange may be considerably delayed or prevented.
Automatic calibration of air quality (default)
The automatic background logic is a self-calibrating mechanism that is suitable
for use in applications in which the air quality regularly drops to fresh air level.
This should typically occur during times in which the rooms are unoccupied.
The sensor reaches its normal accuracy after 24 hours of continuous operation
in an environment that has been subjected to a fresh air supply.
The deviation errors remain minimal if the sensor is exposed to fresh air at least
4 times within 28 days. The device needs continuous operating cycles of more than
24 hours to operate correctly.
Manual calibration of air quality
After connecting the device, ensure continuous operation for at least 2 hours
using air defined as "normal" air quality.
Manual calibration can be started by pressing the button position,
irrespective of the DIP 3 -switch.
The calibration procedure is started by pressing the "ZERO" button
(for approx. five seconds). This is signalled via the flashing LED.
Then calibration takes place. During this phase, the LED is continuously active
and a 600 second countdown runs.
Putting in operation
After switching on the device, a self-test and tempering period follows.
This process takes around 30 - 50 minutes, depending on the ambient conditions.
It is imperative to perform manual calibration once this process is completed.
Switching point setting
A switching point between 10 % and 95 % of the measuring range can be selected
using the SET potentiometer.
A potential-free changeover contact is available as a switch output.
Offset
The VOC measured value can be adjusted subsequently using the offset
potentiometer. The adjusting range is ± 10 % of the measuring range.
DIP switches
KLQ - W
VOC sensitivity DIP 1 DIP 2
LOW OFF OFF
MEDIUM (default)
O N
OFF
HIGH OFF
O N
VOC automatic zero point DIP 3
deactivated OFF
activated (default)
O N
Output DIP 4
Voltage 0 -10 V (default) OFF
Current 4...20 mA
O N
DIP switches
KLQ - SD
VOC sensitivity DIP 1 DIP 2
LOW OFF OFF
MEDIUM (default)
O N
OFF
HIGH OFF
O N

GGeneral notes
– This device may only be used in non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element.
– The voltage output is short-circuit proof.
– Applying overvoltage will destroy the device.
– In case of pollution, we recommend cleaning and recalibration in the factory.
– The device operating range covers 10...95 % relative humidity respectively 0...+50 °C.
Outside of that range, mismeasurements or increased deviations will occur.
– If this device is operated beyond the specified range, all warranty claims are forfeited.
Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In additionIn addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
– Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device
(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided,
and EMC directives are to be observed.
–
This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and
the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
– No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed and commissioned by authorised specialists.
– The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid.
Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement
of our products.
– In case of any modifications made by the user, all warranty claims are forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.
Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
– Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,
or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
– Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.
Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an
initial manual adjustment on-site during commissioning and subsequently at regular intervals.
Commissioning is mandatory and may only be performed by qualified personnel!
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded !
Connecting scheme
Parallel operation
Connecting scheme
Individual operation
Circuitry Circuitry
Output
0V/GND
Output
0V/GND
Power supply
AC 24V~ 0V
DC 15-36V = GND
Circuitry
Output
0V/GND
Power supply
AC 24V~ 0V
DC 15-36V = GND
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier also allows operating 0 - 10 V devices on
AC supply voltage.
The output signal is to be tapped by a measuring instrument. Output
voltage is measured her against zero potential (OV) of the input voltage!
When this device is operated on
DC supply voltage
, the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB – or GND for
ground wire!
When several devices are supplied by one 24 V
AC voltage supply
, it is to
be ensured that all ”positive“ operating voltage input terminals (+) of the
field devices are connected with each other and all ”negative“ operating
voltage input terminals (–) (= reference potential) are connected together
(in-phase connection of field devices). All outputs of field devices must be
referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!

{
G
AERASGARD
®
KLQ- SD
©
Copyright by S+S Regeltechnik GmbH
Zákaz částečného či úplného kopírování bez svolení S+S Regeltechnik GmbH.
Reprint in full or in parts requires permission from S+S Regeltechnik GmbH.
Chyby a technické změny vyhrazeny. Všechny údaje odpovídají stavu znalostí k datu zveřejnění. Slouží pouze k informaci o našich produktech a možnostech
jejich použití, nezaručují však určité vlastnosti produktu. Jelikož produkty mohou být nasazovány za nejrůznějších podmínek a zatížení, které nemůžeme ovlivnit,
musí zákazník nebo uživatel vždy provést korekci pro konkrétní případ aplikace. Respektujte vlastnická práva. Bezchybnou kvalitu zaručujeme v rámci našich
Všeobecných obchodních podmínek.
Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about
our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range
of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property
rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.
Výrobce ⁄ Manufacturer:
S+S Regeltechnik GmbH, Pirnaer Str. 20,
90411 Nürnberg ⁄ Germany
Tel. +49 911 51947-0, Fax +49 911
51947-70, mail@SplusS.de, www.SplusS.de

AERASGARD
®
KLQ- W
AERASGARD
®
KLQ- SD
{
G
This manual suits for next models
1
Table of contents
Other domat Accessories manuals