ALA
ALB
ALC
ALD
2
A L 1
AL2
AL3
AL4
AL5
AL6
SBA
IN
H
T
HT
HTD
HOP
HST
TOP
TST
HLL TLL
HHH
SYS
THH
PRG
SEL
23.4
HCETOD
PRG
SEL
23.4
HCETOD
HTX20-FTS-502
dotech,inc
RH : 10~95%RH, 1.2~3.5V
T : NTC5K
RH & TempSensor
+5
V
RH
GND
TH
TH
PRG
SEL
23.4
HCETOD
OUT1
OUT2
HTX20-FTS-502
dotech,inc
RH : 10~95%RH, 1.2~3.5V
T : NTC5K
RH & TempSensor
+5
V
RH
GND
TH
TH
PRG
SEL
23.4
HCETOD
UH2
UL2
St
dF
dF
PV St
dF/2
dF/2
PV
OUT1
OUT2
FX3DH
FX3DH
FX3DH
FX3DH
OUT1
OUT2
OUT1
OUT2
OUT1
OUT2
Set control sensibility of alarm output.
Temperature Setting Group
●The set point is indicated byflickering at every
0.5 secondsintervals and this set point can be
established by using the ▲ key or ▼ key.
After changing set point, it displays the current temp.
●If there’s no input made for a period of 60 seconds during the setting,
thenit returns back to the run mode automatically.
Run Mode
Set output #1 setup value.
Set output #2 setup value.
Display Current Temp.
Push for
3 sec.
Output #1 setup value
Output #2 setup value
Setting 1 Group
Run Mode
Set control sensitivity of control output #1.
Setting Range 0 ~19.9
Display
Current Temp.
Set control function of
control output #1.
Select Control Type #1 Select Control
Type #2
Control Deviation Value #1
ON Delay Time #1
Minimum OFF Time #1
Minimum ON Time #1
Output #1 at Sensor Error
Alarm Deviation Value
Alarm Option
Manual Output Mode Output #1
Push for 3 sec.
No use output function
(Use display mode only.)
Use cooling control only
(Use OVER temperature sensing only.)
Use heating control only
(Use UNDER temperature sensing only.)
DeviationHigh Limit Alarm
Output is ON when the deviation between
PV value and SVvalue is higher than setup
value of deviation temperature.
DeviationLow Limit Alarm
Output is ON when the deviation between
PV value and SVvalue islower than setup
value of deviation temperature.
DeviationHigh & Low Limit Alarm
Output is ON when the deviation between
PV value and SVvalue is higher or lower
than setup value of deviation temperature.
DeviationHigh & Low Limit Reverse Alarm
Output is OFFwhen the deviation between
PV value and SVvalue is higher or lower
than setup value of deviation temperature.
Absolute ValueHigh Limit Alarm
Output is ON when PVvalue is higherthanor
equal asalarmtemperature setup value.
Absolute Value Low Limit Alarm
Output isON when PV value is lower than or
equal asalarmtemperature setup value.
Sensor Open Wire Alarm
Output isON when sensor wire is opened.
No output within Min. OFF time
after control output #1 OFF.
Output after delaying during setting
delay time in case of control
output #1 ON.
Set output #1 when sensor is
disconnected or shorted.
e.g) In case of setting as ON,
output #1 is ON when error occurs.
Maintain ON in spite of OFF
condition during Min. ON time
after ON.
Setup range is 0~99.9
General alarm
Standard alarm operation
without option
Maintain alarm
Maintain output ON after
alarm occurs
Standby alarm
No output at initial operation
(until achieve the 1st setup value)
Execute both ALD & ALC
at the same time
(-R4 Model)
OFF : Output by temp.
ON : Output by
MV1
Output continuously regardless setup
temp. if manual output value is ON
when manual output mode is ON.
Manual Output Value Output #1
(-R4 Model)
Select deviation type #1
e.g)Condition : Cooling mode,
setting temp.10.0
℃
, deviation 1.0
℃
+Deviation control : ON at 11.0
℃
, OFF at 10.0
℃.
±Deviation control : ON at 10.5
℃
, OFF at 9.5
℃.
+ Deviation control
± Deviation control
Max. Setup Value by User
Min. Setup Value by User
Input max. value settable by user
Possible to set until 100.
Input min. value settable by user
Possible to set until 0.
Simple Trouble Check Point
Setting Method of control mode
Use for humidity only
Use for temperature only
Use for humidity and temperature control
(Output1: humidity control, output2: temperature control)
Humidity and temperature are displayed by every
2.5 sec. interval in shifts.
Use for humidity control and temperature display.
Humidity Sensor
Open Wire
Humidity Sensor
Short Circuit
Temperature Sensor
Open Wire
Temperature Sensor
Short Circuit
Minimum range
for Humidity use Minimum range
for Temperature use
Maximum range
for Humidity use
If the stored value is changed randomly, please re-setup after
parameter initialization.
maximum range
for Temperature use
Humidity and temperature are displayed by every
2.5 sec. interval in shifts.
Setup sensor input of setting 2 group.
※ According to user’s setup, FX3DH is able to use humidity only or temperature
only or for both temperature and humidity. Please use after you setup the
parameter of sensor input of setting 2 group.
※ FX3DH controls by measured value which is detected by sensor.
If sensor fault alarm occurred as following, please check wiring with sensor
※ In case of the above-mentioned error, it will be normally operated with cancelling error
status if the reason of error is solved.
In the case of Humidity display,
unit will not be displayed.
Distinguishment between Temperature and Humidity.
In the case of temperature display,
℃ unit is displayed.
Deviation Control(TP mode)
Dehumidification
(Cooling)Control
OUTPUT ON
when TP mode is P when TP mode is PN
OUTPUT ON
Humidification
(Heating)Control
Dehumidification
(Cooling)Control
Humidification
(Heating)Control
OUTPUT ON
OUTPUT ON
When it use for Humidity & Temp. control
(Apply HTX20-FTS-502 Temp. & Humidity sensor)
YELLOW
BLUE
WHITE
BLACK
RED
YELLOW
BLACK
RED
WHITE
BLACK
RED
When it use for Humidity control(Apply HTX20-FTS-502 Humidity sensor)
When it use for temperature control(Apply DPR-TH1-ET Temp. sensor)
※ Set sensor input setting(IN) of setting 2 group to T.
※ Set sensor input setting(IN) of setting 2 group to H.
※ Set sensor input setting(IN) of setting 2 group to H.
※ Set sensor input setting(IN) of setting 2 group to HT.
When it use for Humidity control (Apply HTX3515 Humidity sensor)
Maintain & standby alarm
Push for
3 sec.