2.5. Switch Setting Menu 1
Use this menu to configure dual pole sensors as multi-level lighting (sequencing)
sensors.
1) Sequences (2-Pole):
Once configured using WIR-3110 with
each press of the override button the
Diversa sensor steps through the
sequence, as per table below:
00 = Both poles off (START)
10 = Primary pole off, secondary pole
on
11 = Both poles on
01 = Primary pole on, secondary pole
off
RPT = Repeat
The first level is activated by the
occupancy signal or switch if it is
set to vacancy.
2) Alternating Primary (2-Pole):
When enabled, the primary pole will
alternate for even lamp wear, every
time occupancy is detected (does
not apply to override button).
3) Disable Mode
The sensor can be disabled by
applying 24VAC from the source on
the Sensor Link wire. This option is
to determine what action is to be
performed.
- OFF
- 10
- 01
- 11
- ––(As-is)