Add and Remove Devices
(NB: only required if adding a new thermostat. All items in the Wish 1, 2 & 3 packs are pre-bound)
To manually connect a miGenie thermostat, insert the batteries into the thermostat and wait for “Bind?” to be
displayed, press ( ) to select. You will also need to enter the binding process on the miGenie Controller, by entering
the Advanced Settings menu, then the Zone settings and selec t the Device manager option. In this screen select
the Add thermostat option to complete the binding process. To remove a miGenie Thermostat enter the Device
manager option in the miGenie controller using the same sequence detailed above. The option will now display
Remove Thermostat, selec t this option and the thermostat will be removed from the system.
To manually connect a miGenie gateway, press and hold the button on the rear of the gateway for more than 5
seconds, the LED will repeatedly flash red-yellow-green. You will also need to enter the binding process on the
miGenie Controller, by entering the Advanced Settings menu, then System settings, then Internet options. In this
screen select the Add gateway option to complete the binding process. To remove a miGenie Gateway enter the
Internet options menu in the miGenie controller using the same sequence detailed above. The menu will display
Remove gateway, select this option and the gateway will be removed from the system.
Technical Data
Step 7: Connection Charts
Step 8: Advanced Settings
Step 8: Advanced Settings
→
→
Feature Description Factory Pre-Set
Device manager Add, replace or remove RF room thermostats Pre-bound
Signal strength Displays the signal strength of the selected zone, if a miGenie thermostat is connec ted to the zone
Channel settings (within
Zone settings)
Customise the application type and associated control settings for zones following this
application type
Application type Selecting the application type pre-configures
the available zone information
Zone 1: Heating:
Zone 2: Hot Water
Zone 3: Heating
Zone 4: Unused
Control type
*Heating zones only
Select TPI or TP.
TPI = Use if the house usually reaches setpoint in ≤ 1 hour.
TP = Use if the house usually reaches setpoint in ≥ 1 hour.
TPI
Cycle rate (only when
control type is TPI or TP)
Select 3 cph (c ycles per hour), 6 cph or 12 cph 6 cph
Frost temperature Disable frost protection or set between 3-10°C 5°C
Valve protection The output will be activated for the specified time (in minutes). This
will happen weekly, related to the last ac tion of the output. Select 0
to 10 minutes.
0 mins (Off)
Feature Description Factory Pre-Set
Advanced settings ! CAUTION! These settings should only be modified by a qualified person. They can influence the
safety and the proper functioning of the system
System settings These are set tings applicable to the system controller unit, global set tings
for bound nodes and internet connection settings
Backlight miGenie controller options are:
On with timeout, Always on, Always off
miGenie thermostat options are:
On with timeout, always off
On with timeout
Lock settings Enable or disable the screen lock for the miGenie controller. To lock:
enter a 3 digit code for protection. To unlock: enter the 3 digit code
000
Master code 401
Product Information View product details for devices in the system e.g. part number, firmware version, etc.
Signal strength Informs about the current signal strength of the products connected to the system
Internet options Sub-menu relating to the connec tion of an internet gateway – enables
a gateway to be added, replaced or removed with an indication of signal strength.
System reset Will reset all settings to factor y pre-sets
Zone settings Customise each zone according to personal preferences
These are set ting which will be applied to a connected thermostat
Select zone Select the zone for the following actions
Rename zone To rename an existing zone Heating, H Water, LivRoom
Edit schedule Update the schedule for the zone
Zone setup Contains detailed zone setup values – see below for descriptions
Minimum
temperature
The minimum set temperature that can be set
for the zone
5°C
Maximum
temperature
The maximum set temperature that can be set
for the zone
30°C
Eco
temperature
Temperature used for energy saving events
e.g. during the night
16°C
Comfort
temperature
Temperature used for comfort events
e.g. during the day
21°C
Offset
temperature
Adjust the displayed temperature to personal needs 0°C
! IMPORTANT:
Always switch off the mains before removing
the miGenie Controller – and never fit it to a live
wall-plate!
→
Arrowed numbers relate to the junction box.
* Consult boiler handbook for details of pump
overrun wiring.
Make the wiring connections, as above, for the
appropriate system. For surface wiring, snap out the
cable entry strip on the bottom edge of the wall-plate.
miGenie controllers are double-insulated and need
no ear th connection, but an earthing continuity (loop)
terminal is provided for convenience.
After wiring, clip on the unit and tighten the securing
screws. Check the mains input has a 3A fuse, and switch
on the mains.
Biflo system: Model T724R Twinzone system: Model T724R
From the Home screen, select
Settings, then Advanced settings
as shown.
From here you can edit the assigned zones, rename them if required
and check the Signal strength.
→
→
→→ →
→
→
→
→
Client Schneider Electric File Name 6490211_E Artwork.pdf
Artworker -
Proof Stage PRINT
Finished Size 420x297mm
Creative Director N/A Artwork % 100%
Modification Date 18/02/17Bleed 3mm
miGenie Controller miGenie Controller
3 Zone system: Model T744R
miGenie Controller
Select a name from the list or
select 'Custom zone name' to
create a new zone name.
miGenie controller miGenie thermostat miGenie gateway
Power Supply 230V a.c. +10% -10% 50Hz 2 X 1.5V IEC LR6(AA) alkaline
batteries
5V d.c. 1A USB Micro-B
Switch Rating 2 (1) A 230V a.c. each switch N/A
Wiring Fixed wiring only, to comply with
current IET regulations (BS7671)
No wiring required
Battery life N/A 2 years typical N/A
Ambient Temperature
Operating: 0º to 45ºC (miGenie controller 3 / 4 channel 0º to 40ºC)
Storage: -20ºC to 55ºC
Ambient humidity
(non condensing)
Operating 25% to 90%
Storage 15% to 95%
Temperature Range 5 ºC - 30 ºC N/A
Control Accuracy <0.6ºC at 4º / hour N/A
Timing resolution 1 minute N/A
Temperature resolution 0.5°C N/A
Ball Pressure Test
Temperature
75ºC
Pollution Degree 2
Energy Class IV = 2% (Acc. EU 811/2013, 812/2013, 813/2013, 814/2013) N/A
Software Class A
Software Version
Maximum Radiated Power
Without Mains Power Display: blank; Time: always kept
Program times: always preser ved N/A
Rated Impulse Voltage 2.5kV
Radio Frequency
N/A
868.3MHz (Bi-directional communication)
Radio Signal Range 30m typically. The range may be affected by the composition / density and the number
of walls between the miGenie products
Mounting Industry standard wall plate Wall bracket or table stand Table top
Relevant EC Directives: 2014/53/EUREDDirective
2013/56/EU Battery Directive
2011/65/EU RoHS Directive
Applied Standards: EN60730-1; EN60730-2-7; EN60730-2-9
EN 300 220-2; EN 301 489-3
Hereby, Schneider Electric Controls UK LTD, declares that this miGenie Wireless Packs is in compliance with the
essential requirements and other relevant provisions of RED-DIRECTIVE 2014/53/EU. Declaration of conformity
can be downloaded on: www.draytoncontrols.co.uk
6712076 6712077
6712075
+11dBm (12.6mW)