
2
CDS Humidifier RL Series
90-2579
• If using registers and diffusers, the total open area must
be at least 453 in2(0.3m3), which is the equivalent
area to a 24 inch (610 mm) round.
• When locating registers and diffusers be aware of the
following;
• Relative to other dehumidifier inlets/outlets – must
be a minimum 10 feet (3 m) apart and do not direct
toward one another.
• Relative to HVAC diffusers – ensure minimum 10
foot (3 m) distance from other HVAC diffusers.
• For agriculture applications – do not directly vent
onto plants.
• Ensure that the ductwork is supported within 2 feet
(0.6 m) of inlet and outlet of the dehumidifier. Consult
building codes and standards for duct support
requirements beyond 2 feet (0.6 m) of the dehumidifier.
DUCT SIZING AND ROUTING
• Inlet and outlet collars fit 24" (610 mm) round duct.
• Unit performance decreases as airflow decreases,
the shortest possible duct lengths with minimal bends
should be used.
• Do not exceed 1,000 feet (305 m) of metal duct or
750 feet (229 m) of flex duct.
• Max static pressure is 0.6" w.c. (149 Pa).
• Install the dehumidifier in location where filter door,
service access panel, compressor side panel, and
user interface are accessible, see the Dehumidifier
Installation and Operating Instructions for more details.
• Do not install a bend in the ductwork within 2 feet
(0.6 m) of the dehumidifier inlet or outlet.
• When selecting duct material, it is preferred to use
metal ducting to maintain airflow. If flex duct is to be
used, ensure it is extended out as much as possible
to limit disruptions to the airflow. Note:Use only
insulated ducting when the inlet side of the duct work
is located outside of the conditioned space. In some
instances when the dehumidifier is placed outside of
the conditioned space, the cabinet of the dehumidifier
may also need to be insulated to prevent condensation
formation on the exterior of the unit.
• Do not duct more than one dehumidifier together. See
Figure 2-1.
Table 2-1:
Equivalent length of bends
45° bend 5 feet (1.5 m)
90° bend 10 feet (3.0 m)
180° bend 30 feet (9.1 m)
FIGURE 2-1: DO NOT DUCT MORE THAN ONE DEHUMIDIFIER
TOGETHER