4
INSTALLATION
connections are made at the lower right rear corner of
the unit.
When mounting on a stud wall, locate studs and
position mounting bracket in place so that each of the
two holes will center on a stud. Mark hole locations
and pre-drill 6 mm diameter pilot holes. Secure
bracket to wall with lag bolts provided. The hole in the
back of the cabinet above the plumbing opening is for
a lag bolt into the wall to secure the cabinet on the
hanging bracket.
For hollow block or poured concrete wall mounting,
position mounting bracket in place and mark the
second hole from each end. Drill appropriate pilot hole
for two 10 mm toggle bolts or two 10 mm machine bolt
lead anchors. Secure bracket in place.
When the HUMIDI-TECH humidifier is in final opera-
tion, the panel access keys should be removed and
secured in a different place.
Examples of Mounting the Dispersion Tube
Figure 4-1: Mounted Horizontally in Duct
38 mm Vapor Hose
(50 mm for VM25)
Vapor hose and dispersion tube should be pitched back to the humidifier with a
gradual slope of 165 mm/m (minimum). VM34 must use a multiple tube steam
dispersion system.
OM-228
Figure 4-2: Mounted Horizontally in Duct and
Lower Than HUMIDI-TECH Unit
Tee
OM-229
75 mm to 125 mm
(150 mm to 300 mm for
VM 25 and VM 34)
This is not recommended on VM10, VM12, VM16, VM25, and VM34.
IMPORTANT NOTES: When duct is located more than 3 metres away from unit,
vapor hose is not recommended; 40 mm minimum I.D. hard pipe should be used
instead. VM34 must use a multiple tube steam dispersion system.
OM-230
A water seal must be located in drain line as shown to maintain steam pressure.
VM34 must use a multiple tube steam dispersion system.
Locating and Mounting the HUMIDI-TECH®
Humidifier
The HUMIDI-TECH humidifier is designed to hang on
a wall, and should be installed in a space located near
an air duct system.
Consider the following when selecting the location of
the humidifier:
• Convenient access to duct
• Electrical and plumbing connections
• Required clearances
The mounting location should provide a minimum
clearance of 90 cm to the front and 60 cm to the right
side of the unit. This clearance is required for removing
the evaporating chamber and accessing electrical
compartment.
Electrical power supply, water make-up piping and
drain piping must also be considered. These service
Figure 4-3: Mounted Vertically (Optional)
150 mm
min.