Installation
1JQJOH
4VQQMZXBUFSBOEESBJO
Figure 14-1:
Drain piping detail
OM-7591
* Hose clamp and black rubber hose ship with each
humidifier; they can also be ordered from DRI-STEEM.
See Table 59-1.
Important: Thoroughly flush the
supply water piping to remove pipe residue
and stagnant water before connecting piping
to the humidifier. Pipe residue and stagnant
water in the water supply piping can cause
foaming, preventing the humidifier from
reaching the required steam capacity.
WARNING
Hot drain pipes
Drain piping surface may be hot. Touching
or contact with hot pipe may cause severe
personal injury.
Black rubber hose*
3/4" (DN20) I.D.
Open drain
1" (25 mm)
air gap
Pitch 1/8"/ft (1%) toward drain
Hose clamp*
To drain
Supply water piping
Use only copper for supply water piping; do not use rubber or
plastic. The standard supply water connection before the fill valve is
a 1/4" FIP strainer.
Note: The supply water connection size is 3/8"BSP [DN10] in Europe.
In cases where water hammer may be a possibility, consider
installing a shock arrestor. Water pressure must be 25 to 80 psi
(175 to 550 kPa).
Drain piping
Drain piping must be code-approved, 3/4" (DN 20) ID material
rated for 212 °F (100°C) minimum.
The drain cup has an integral grounding plate and requires a field-
installed 1" (25 mm) air gap to a drain funnel to prevent conduction
of electricity in the drain line.
The XT Series humidifier features user-selectable drain water
tempering. When drain water tempering is selected, the humidifier
tempers drain water by opening the fill valve whenever the drain
valve is energized, which automatically cools drain water before it
enters the drain. Drain water tempering is intended to keep water
entering the drain line no hotter than 140°F (60°C). Manually
energizing the drain valve when the supply water is shut off can
allow 212 °F (100 °C) water to enter the drain line.
Observe following precautions when selecting and installing drain
piping to ensure personal safety and material integrity:
t 8IFOVTJOHDPQQFSPSPUIFSNFUBMMJDESBJOQJQJOHHSPVOEUIF
drain piping to the earth ground lug in the XT Series humidifier.
The earth ground lug is shown in Figures 54-1 and 56-1.
t $IMPSJOBUFEQPMZWJOZMDIMPSJEF$17$QJQJOHJTBOPONFUBMMJD
alternative for drain piping. It is rated up to 212°F (100°C) for
intermittent-use, low-pressure applications.
The connection size for the steam cylinder drain is 1" (DN25) hose.
Do not reduce this connection size.
If drainage by gravity is not possible, use a reservoir pump rated for
212 °F (100 °C) water.
A drain hose is provided to function as the flexible connection from
the drain cup to the field-installed open drain. See Figure 14-1.