Choosing a location for the humidifier
When selecting a location for the humidifier, consider the following:
t Proximity to duct
Install the humidifier near the air duct system where the
dispersion assembly will be located. The maximum recommended
length for vapor hose connecting a single humidifier to a
dispersion assembly is 10' (3 m). The maximum recommended
developed length for tubing or pipe connecting a single
humidifier to a dispersion assembly is 20' (6 m). See the
dispersion section of this manual for more information about
installing dispersion assemblies.
t &MFWBUJPOPGUIFJOTUBMMFEEJTQFSTJPOBTTFNCMZ
The recommended installation location for the dispersion
assembly is at an elevation higher than the humidifier. However,
if the dispersion assembly must be installed at an elevation
lower than the humidifier, install a drip tee and drain as shown
in Figure 16-1. Before installing a dispersion assembly or
interconnecting piping, review all pitch requirements in the
dispersion section of this manual.
t 3FDPNNFOEFENJOJNVNDMFBSBODFT (see Figure 3-1)
t &MFDUSJDBMDPOOFDUJPOT
Electrical power supply connections are made at the bottom
right panel corner of the electrical enclosure. The system wiring
is inside the cover of the control cabinet. See the field wiring
instructions.
t 4VQQMZXBUFSBOEESBJOQJQJOHDPOOFDUJPOT
Water supply piping connections are made on the bottom right
side of the unit. Drain piping connections are made at the bottom
center of unit. See the field piping illustration and instructions.
t &YUFSJPSXBMMJOTVMBUJPO
Do not install the humidifier on an exterior wall unless that wall
is properly insulated.
Choosing a location for the dispersion assembly and control
devices
See the dispersion section of this manual for recommended
installation locations for the dispersion assembly. See Page 10 for
recommended installation locations for humidistats.
$IPPTJOHBMPDBUJPO
Important:
Install humidifier only in locations that meet
the following temperature and relative
humidity (RH) requirements:
Maximum ambient temperature:
104 °F (40 °C)
Minimum ambient temperature:
41 °F (5 °C)
Maximum ambient humidity:
80% RH (non-condensing)
Note:
To open the humidifier access door, rotate
the screw counter-clockwise ¼ turn. The
door pivots toward the front of the unit
from the bottom of the door. To close the
access door, position screw slot so that it
is horizontal and then push the door shut.
Make sure sides of door go outside the
enclosure.
Figure 3-1:
Recommended minimum clearances
OM-7497
Top: 16"
(400 mm)
Floor: 16"
(400 mm)
Between units: 4"
(100 mm)
Side: 4" (100 mm)
Front: 36"
(914 mm)
XTR_IOM.pdf 5 12/9/2009 1:39:53 PM