DSC PC4820 User manual

1
S e c t i o n 1
The PC4820 is a versatile Dual Card ReaderAccess Control
module which will enable you to meet the most
demanding access control requirements of an installation.
The PC4820 is monitored and programmed via the
PC4010/4020 control panel. Up to 16 PC4820 modules can
be connected to a PC4010/4020 via a 4-conductor Combus,
using standard, unshielded station wire.
Each PC4820 is capable of providing supervision for two
door inputs which may to assigned to any PC4010/4020
zone. Each door contact may be configured for any zone
end of line option which the control panel can provide.
Each of the two PC4820 Access Card Readers can be
programmed to function independently on different
doors, or together controlling access for both sides of one
door.
Control of the access points can be performed using a
variety of equipment. The PC4820 supports four different
types of card readers: the Polaris magnetic strip reader,
the Shadow Prox proximity card reader, the HID proximity
readers, and 26-bit standard Wiegand card readers. The
PC4820 also supports the use of any request to exit device
including the T-REX exit detector.
1.1 PC4820 Access Control Module
Specifications
Two Zone Inputs
• Two programmable supervised zones ( EOLresistors
– value )
• Zones may be programmed as Standard orAuxiliary
delay zone types
• PC4010/4020: up to 16 PC4820 can be added (up to
32 access points)
Non Volatile RAM (internal memory)
• Does not lose any system programming when the
module is powered down.
Low Current Outputs
• Six low current outputs (open collector outputs
switched to ground 25mA max.) :
• Two LED terminals - To the LED input of the
reader
• Two BUZ terminals - To the Buzzer input of the
reader
• Two OUT terminals - Reserved for future use
Regulated Power Supply ( 1.5 Amp max. )
• Electronic shutdown protection of the battery,
auxiliary output, 5 and 12 V reader power supplies,
and lock device power output
• Auxiliary output supply: 12VDC, 125mA Max
• LK1 and LK2 Door Strike power: 12VDC, 250mA Max
• Reader Power 5VDC, 125mA Max
• Reader Power 12VDC, 125mA Max
Reader Technology
• Polaris, Shadow Prox, HID Proximity and 26-bit
Standard Weigand format
Access Card Compatibility
• Polaris POL-C1CN - Polaris Magnetic Cards
• Shadow Prox, Module Numbers:
SH-C1 - Shadow Prox Card
SH-K1 - Shadow Prox Keytag
• HID Proximity:
HID-C1325KSF - Proximity Card
HID-C134KSP - Proximity Keytag
• Weigand - Standard 26 bit formats
Battery
• 12VDC 7.0Ah recommended rechargeable gel-cell
Transformer
• 16.5 VAC, 40VA
Operating Temperature
•2
°C to 40°C (35°F to 110°F) operational Temperature
Range
•90
°non-condensing humidity
Output Voltage
• Output voltage = 13.8VDC (with normal AC and a
fully charged battery). Devices that require power
from the PC4820 should be capable of operation over
the voltage range of 10 to 14VDC.
• 5V Power Supply - Devices connected to the 5V
supply should be capable of operation between 4 and
6V.
Introduction

2
S e c t i o n 2
2.1 Plan Your Installation
When designing a security system with access control it
is best to first lay out the system on paper. This will help
determine the total number of zones, additional expanders,
access control points and other system components that
will be required to complete the installation.
When the location of all points of access are known,
appropriate points may be chosen for access control. When
working from the layout, be sure to locate the PC4820
module so that the wire runs from each door will be as
short as possible.
When deciding the placement of the access points and
module, remember to check the capacitance limit for the
wire you are using for the Combus. Follow the steps
outlined in your PC4010/4020 v3.0 Installation Manual
(Section 2.4 “Capacitance Limits”).
NOTE: Do not run the Combus to the PC4820 in shielded
cable.
2.2 Installation Steps
Once the location of the PC4820 and each access point is
determined, follow the installation steps outlined below.
1 Installation of PC4820 and accessories:
The PC4820 controller cabinet has been designed for
surface mounting. The cabinet is large enough to
accommodate the battery backup supply and the
necessary wiring connections for most applications.
The cabinet should be mounted indoors, in a dry,
secure location providing normal temperature,
humidity levels and access to an earth ground
connection. The location should be easily accessible
for servicing the equipment, and it is recommended
that each PC4820 module be near the doors it controls.
If the PC4820 is within the Access controlled area, keys
for the controlled doors must be made available so
that the PC4820 can be accessed for servicing.
Connect the various devices for each access door
according to the diagram below:
A. Access card readers should be located 107cm (42")
from the floor.
B. Connect door strikes using standard 18-gauge cable.
Recommended door strikes are electric “Continuous
Duty” devices which, when power is cut, will remain
in a locked or “secured” state. When using magnetic
locks, follow local regulations on the use of these
devices.
CAUTION – Local regulations may prohibit “Lock on
Power Failure” if the door is used as a Fire Escape route.
C. Door contact must be hardwired directly to the PC4820.
Wireless or addressable contacts may not be used.
D. Install a T-REX exit detector and door alarm (optional)
inside of the protected area. (See T-REX Installation
Instructions for details on wiring and proper
mounting locations.)
2 Tamper protection
A tamper switch may be installed on the cabinet to
protect it from unauthorized entry. The normally
closed tamper switch is connected to the TAMP and
GND (on right side of the PC4820). If the tamper
switch is not used, the TAMP terminal must be
terminated to any GND terminal with a wire.
3 Connect all inputs, outputs, door locking
devices and card readers
Follow the instructions outlined in the sections
below for installing each type of device.
4 Power requirements
Install a 16-18VAC/40VA transformer outside the
cabinet. Connect the red battery lead to the positive
terminal and the black battery lead to the negative
terminal.
NOTE: Do not apply power until all wiring is complete.
Both the AC and battery connections must be made in
order for the PC4820 to function properly. Connect
the battery before connecting the AC.
2.3 Inputs – POST, ARM and REX
The door inputs are capable of following any type of
supervision. Choose the end of line configuration (Normally
Closed Loops, Single End of Line or Double End of Line)
which you have selected for the rest of the security system.
The POST, ARM and REX inputs are for Auto-arm
postponement, Arming buttons and Request to Exit
devices, respectively. These inputs will only be capable of
Normally Closed Loops or Single End of Line resistors.
When using Double End of Line supervision, these inputs
must only be wired for Single End of Line configuration.
Please see section 3.5 “ZoneAssignment forAccess Doors”
for information on door input zone programming.
POST Inputs
When enabled, this PC4820 input allows postponement of
Autoarm of the PC4010/4020 for the partitions selected in
Installation and Wiring
To PC4820 Access
Control Module (See
Access Control
ModuleWiring
Diagrams for details)
B
CD
A

3
Installation and Wiring
the Arm/Disarm mask. To postpone an autoarm, the user
must present their access card (during the autoarm pre-
alert) and activate the device connected to the POST input.
Typically the POST input will be a push button device
mounted next to the access card reader (107cm (42") from
the floor) which is assigned to the partition(s).
The PC4010/4020 will send an Autoarm Abort reporting
code to the monitoring station if the reporting code is
programmed. The autoarm will restart at the end of the
Postpone Arm time (ref # [00020305]) unless the partition
has been manually rearmed. The autoarm may be
postponed as many times as desired.
NOTE: To postpone an autoarm, the user must be
assigned to the partition(s) being armed, and the user’s
access card must have the disarm attribute enabled.
See your PC4010/4020 Instruction Manual for
information on programming access codes and cards.
ARM Inputs
When enabled, this PC4820 input will allow designated
users to arm the selected partitions on the PC4010/4020.
To arm the partition, the user must first ensure that the
partition area(s) to be armed is secure (close all protected
doors and stop movement in areas covered by motion
detectors). The user should present the access card and
activate the device connected to the ARM input. The exit
delay will begin. Typically the ARM input will be
connected to a push button device and should be
mounted next to the access card reader (107cm (42") from
the floor) which is assigned to the partition(s).
NOTE: To arm partitions, the user must be assigned to
the partition(s) being armed, and the user’s access card
must have the arm attribute enabled. See your PC4010/
4020 Instruction Manual for information on
programming access codes and cards.
REX Inputs
A Request to Exit device can be used on the inside of the
secured area to provide a method of unlocking the door
without the need for an access card reader on the inside
of the door. When the REX device is tripped, the door
will unlock. This will also allow the door to be opened
without the door being “Forced open.” Request to exit
devices can be of many different types. Be sure to read
the installation sheets provided with each unit for proper
installation for the REX devices.
2.4 Outputs – LED, BUZ and OUT Terminals
LED Outputs
The LED outputs for Out Door 1 and Out Door 2 are used
for controlling the LED on the access card readers. This
allows the PC4820 to provide visual feedback when the
access card is presented to the reader. Connect the wire
from the reader indicated as LED to the LED terminal of
the selected output.
When using this output to switch an external device, the
negative terminal of the device must be connected to the
LED output terminal. The positive terminal of the external
device must be connected to the AUX+ terminal.
BUZ Outputs
The BUZ outputs for Out Door 1 and Out Door 2 are
used for controlling the buzzer of the access card readers.
This will allow the PC4820 to provide audible feedback
to indicate error conditions. Connect the wire indicated
as buzzer to the BUZ terminal of the selected output.
When using this output to switch an external device, the
negative terminal of the device must be connected to the
BUZ output terminal. The positive terminal of the external
device must be connected to the AUX+ terminal.
OUT Outputs
Reserved for future use.
2.5 Door Locking Devices – LK1 & LK2 Terminals
Connect door locks to LK1 and LK2. Each lock output
can provide up to 250mA at 12VDC. Always check local
regulations concerning the installation of magnetic
locking devices.
The locking device outputs are controlled according to
the installer programmed parameters for allowing access
to, or unlocking the doors according to schedules. These
door locking device outputs can operate DC-powered
locking devices such as electromechanical strikes and can
be configured to operate in fail-safe or fail-secure modes
(normal or reverse action). The typical maximum DC for
each lock output is 250mA.
WARNING: According to local regulations, there may
be strict limitations to installing magnetic locks or
other similar locking devices on doors used for exit.
Be sure to check local regulations before installing any
door locking device.
2.6 Access Card Readers
Each PC4820 module can control two access card readers.
These can be installed on one door to control both entry
and exit, or on two separate doors to control access in
one direction only. Using the proper cable, the readers
may be located up to 150 meters (500 feet) from the
PC4820 module. The access card readers should be
mounted 107cm (42") from the floor.
WARNING: Connecting the Red wire lead (or power
lead) of a 5VDC reader to the 12VDC terminal may
damage the reader. See reader installation procedure
for proper power connection.
Using Two Readers to Control One Door
When using the Two Readers option, the PC4820 can use
both readers to control entry and exit from a single access
control point. Each reader can be programmed to have
its own access levels (allowing the ability to separately
control entry and exit permissions for each door on the
system), and schedules. See section 3.2 “Door Options”
for programming information.
NOTE: When using the Two Reader option, the Door
2 input must be terminated to any COM terminal.
Access Card / Keypad Readers
Access card readers with integrated keypads may be used
with the PC4820. In order to use this reader type, the
user must first present their access card. The LED on the
reader will flash twice every second to indicate to the
user that the reader is waiting for an access code to be
entered. The user will have 15 seconds to enter their access
code. If the code is entered successfully, the door will be
unlocked. The access code entered must be the correct

4
code for the access card used, otherwise access will not
be granted, even if the code entered is a valid code on the
system. When access is denied to the user due to a wrong/
invalid code being entered, or time has expired waiting
for the access code, the LED on the reader will flash 3 times
every second and the buzzer will give an audible beep 3
times every second to indicate that access was denied.
Reader LED Flash Rates
Most access card readers will have an LED output to
provide visual feedback when the access card is presented
to the reader. The light will flash in different ways to
indicate the following conditions:
LED State Access Condition
Steady Red Door is locked
Steady Green Door is unlocked –
Access granted
Slow flash (state changes The partition that the
every half second) Arm/Disarm mask is
assigned to is armed
Medium Flash (state changes Waiting for a Privileged
three times every second) card to be presented
Fast flash (State change Access denied/Time
four times every second) expired waiting for a
privileged card.
Buzzer Operation
Most access card readers will have a buzzer output to
provide audible feedback. The Buzzer output may be
connected to operate local warning devices for the
following conditions:
• The access controlled door has been forced open.
The buzzer will activate and remain active until the
door has been closed.
• The access controlled door has been left open too
long. The buzzer will activate and remain active
until the door has been closed. The buzzer will pulse
on and off for the last half of the programmed Door
Open Time to indicate that the Door Open Too Long
event is about to occur.
Reader Connection Function PC4820 Terminal
Polaris / Shadow Prox HID
Green Green Data 0 GRN
White White Data 1 WHT
Red Red + VDC or +12VDC +5V or +12V
Black Black Ground GND
Blue Yellow Buzzer Buzz
Brown Brown (Red LED) LED LED
Orange/Yellow Terminals marked as Tamper Switch To PC4010/4020 zone or connected
(Polaris only) Tamper Common in series with the assigned door
& Tamper Select* input on this module (optional)
——— Blue Hold Not used
——— Orange Green LED Not used
——— Violet Return GND
Purple/Grey (POL-2KP only) -------- Independent Switch Can be used for Arm
or Post inputs. See PC4820 Wiring
Diagram for wiring instructions.
* Tamper connection not available on the MiniProx detector
PC4820 Connection Chart
Reader Type Reader Part Numbers Supply Voltage Card Part Numbers
Magnetic Stripe POL-1, POL-1W, POL-2, POL-2KP +5Vdc POL-C1CN
Bar Code BC-201
Proximity:
Shadow Prox SH-1, SH-2, SH-2KP +5Vdc to 14Vdc SH-C1, SK-K1, SH-CMG1,
SH-4, SH-5 +12Vdc SH-CMG2
SH-6, SH-7 +24Vdc to 28Vdc
HID HID-MP5365 - MiniProx +12Vdc HID-1365KSF, HID-1335KSF,
HID-PR5355, HID-PR5355KP - ProxPro +10Vdc to 15Vdc HID-1334KSF, HID-1365KSF,
HID-MX5375 - MaxiProx +14Vdc to 28.5Vdc HID-1385KSF
PC4820 List of Supported Readers and Cards

5
Installation and Wiring
PC4820 Access Control Module Reader Connections
*
NOTE: Only use the +5V power supply when using
Polaris Readers.
✝✝
✝✝
✝
NOTE: Only use the +12V power supply when using the
Shadow Prox Reader.
Polaris Readers (POL-1, POL-2, POL-2KP) Shadow Prox Readers
HID Readers Connecting External Power Supplies
Cabling Specifications
Component Maximum Wire Length Cable Description
Reader 5V 150m (500ft) 3 Pair, #18 AWG, stranded, overall shield
with extra drain conductor
Reader 12V 150m (500ft) 3 Pair, #22 AWG, stranded, overall shield
with extra drain conductor
Inputs (Door, REX, Post, Arm) 300m (1000ft) 2 pair, #22 AWG, twisted pairs
AC Transformer 8m (25ft) 1 pair, #18 AWG Ground 8m (25ft)
1 conductor, #18 AWG, Solid

6
Programming of the PC4820 is performed at the PC4010/
4020 control panel in Installer’s Programming mode.
Refer to Section 4 “How to Program” of the PC4010/4020
Installation Manual for instructions.
The following programming sections must be
programmed for each PC4820 enrolled on the system. To
select a module, enter reference number [0011XX] where
“XX” refers to the PC4820 module number.
The control panel will transfer all necessary information
(access codes, scheduling, etc.) to each PC4820 module
whenever one of the following occurs:
1. the main panel is powered up
2. installer’s mode is exited
3. a PC4820 loses and then restores communication
with the control panel
4. a PC4820 is hardware defaulted
5. a PC4820 is enrolled
6. a downloading session has disconnected.
The data transfer can take up to 2.5 minutes per PC4820
module. When the transfer is completed, all keypads will
beep 16 times. Changes to PC4820 programming will not
take effect until the data transfer is complete.
3.1 Programming Reader Types
Ref # [0011XX00] where XX = PC4820 module #
The PC4820 is capable of supporting different types of access
card readers. The same type of reader must be used on both
doors of an access card module, but different modules may
use different reader types. Enter the 2-digit code for the
reader type you are installing on the selected zone.
00 Polaris 1- Magnetic card reader. 7 Digits with clock
and data.
01 Shadow Prox - Extended range proximity reader
SH5, SH6, SH7, SH-VR 32 Bits.
02 26 Bit Standard Wiegand reader, HID Proximity
readers
The default access card reader type is 00 (Polaris 1).
3.2 Reader Options
Ref # [0011XX01] where XX = module #
This section contains the programming for the selected
PC4820. First, you must select which of the two doors to
program. Use the arrow (< >) keys to scroll to either Door
1 or Door 2 and press the [*] key to select. Aseries of toggle
options will be available for each door. Again, use the
arrow (< >) keys to scroll through each option and press
the [*] key to turn the selected option on or off.
The options available for each door are as follows:
•Lock Reversed: If enabled, power will be applied to
lock the door. The lock will remain closed when idle
and will deactivate when a valid access card is used
to open the door. The programming for this option is
dependent on the type of locking device being used.
Check the installation sheet provided with the locking
device to see what is required for power.
If disabled, power will be applied to unlock the door.
This option is for use with “Fail Secure” devices such
as electronic door strikes. (Default = No)
•Unlock on REX: If enabled, tripping a Request To
Exit device will cause the door to unlock for the
programmed Door Unlock time (see Section 3.4
“Door Times”). If disabled, tripping the Request To
Exit device will not cause the door to unlock.
(Default = Yes)
•Flash When Arm: If enabled, the armed status of the
assigned partition(s) will be indicated by the light on
the reader assigned to the door. The LED will flash
slowly for the duration of the armed period.
NOTE: The partition(s) to which the door’s zone is
assigned must also be selected in the Arm/Disarm Mask
for proper operation of this function.
If disabled, the LED on the access card reader will
not indicate the armed status. (Default = Yes)
•Relock On Arm: If enabled, a Request To Arm will
relock the door when the arm input is activated. If
disabled, a Request to Arm will not relock the door.
(Default = No)
•Lock On Close: If enabled, a door unlocked by an
access card or by a REX device will lock once the
zone is opened and then closed. If disabled, a door
unlocked by an access card or by a REX device will
relock once the zone is opened. (Default = No)
•Code Required: If enabled, a valid access code must
be entered at an adjacent keypad in addition to the
card swipe in order for the door to unlock. If
disabled, no code will be required. (Default = No)
•LED Reversed: If enabled, the normal state of the
LED output on the PC4820 will be an open collector.
If disabled, the output’s normal state will be low.
(Default = No)
•Two Readers: If enabled, both “doors” (card readers)
will be assigned to the same zone. This will allow
the PC4820 to control access both into and out of a
secured area at a single access point. The zone and
partition assignment of both doors on the PC4010/
4020 must be the same. (See section 3.5 “Zone
Assignment for Access Doors” and your PC4010/
4020 Programming Manual for information on zone
and partition programming.)
Any time an access card is presented at one reader
to open the door, the second reader will also allow
access. This will prevent a door forced open event
(both lock outputs will unlock).
Each door can still be programmed to have its own
access levels (allowing the ability to control both
entry and exit permissions for each door on the
system), and schedules.
S e c t i o n 3
Programming the PC4820

7
P r o g r a m m i n g t h e P C 4 8 2 0
NOTE: This option can only be enabled for Door 1.
If disabled, doors 1 and 2 will have their own zone
and partition assignments. (Default = No)
3.3 Arming and Disarming with Access Cards
The PC4820 can be set up so that users may arm and
disarm, or postpone the autoarm of any active partition
on the system. To set up partitions to be armed and
disarmed from an access control module, the following
must be programed:
1. The user’s access card must be assigned to the
appropriate partition(s); an access level must be
assigned to the access card; and the access card must
have the arm and or disarm attribute enabled (see
section 3.8 “Programming Access Cards”).
2. The access door must be assigned a PC4010/4020
zone (see section 3.5 “Zone Assignment for Access
Doors”), and the zone must be assigned to the
appropriate partitions (see below).
3. The Arm/Disarm mask must be programmed to
include the partition(s) that are to be armed/
disarmed from that access card reader (see below).
4. The Postpone Arm, Arm Request and Disarm
Request schedules must be programmed with a date
schedule other than [00] (see section 3.6 “Access
Door Schedules”).
HINT: When using the arming/disarming options of the
PC4820, the use of Bell Squawk and a Partition Status
output will allow for clear indication of the armed status
of the partition(s). These options can be enabled/disabled
on each partition (see your PC4010/4020 Installation
Manual for more information on programming partitions).
Arm/Disarm Partition Mask
Ref # [0011XX01YY01] where XX = module #; YY = door #
In this section select the partition(s) which users will be
able to arm and/or disarm when they present the
appropriate access card at the reader for the access door.
NOTE: The zone assigned to the door must be assigned
to the same partitions selected in the Arm/Disarm
Partition Mask (Partition Programming, reference #
[0100XX03], where XX = partition #).
3.4 Door Times
Ref # [0011XX01YY02] where XX = module #; YY = door #
Door Unlock Time
The amount of time that the door will remain unlocked
after a valid access card has been presented is
programmed in this section. This is also the Request To
Exit time period. The default setting is 10 seconds. Valid
entries are from 001-255 seconds.
Door Open Time
This section will program the amount of time an access
door can remain open before a Door Open Too Long event
is generated. After half of the Door Open Time has
expired, the reader buzzer will pulse on and off as a
warning. At the end of the Door Open Time, the buzzer
will sound steady to indicate that the door has been left
open too long. The default setting is 030 seconds. Valid
entries are from 001-255 seconds.
3.5 Zone Assignment for Access Doors
Ref # [0011XX01YY03] where XX = module #; YY = door #
Assign each “door” to a zone on the PC4010/4020. Any
zone from Zone 17 to 128 may be used (Zone 9 to 64 on
the PC4010).
You can use any zone supervision option provided by
the PC4010/4020 for PC4820 zones. The end of line
resistors used for the door inputs are 5600Ωfor the alarm
contact. If you will be using DEOL resistors, the tamper
contact is also 5600Ω.
The door’s zone must be programmed as a Standard
Delay, or an Auxiliary Delay zone (PC4010/4020
programming reference number [0100XX03], where
XX=partition number). See your PC4010/4020 v3.0
Installation Manual, section 5 “Zone Programming”.
3.6 Access Door Schedules
A date schedule can be assigned to each of the following
access door features.Adate schedule will include the start
and end times for each event, the days of the week the
schedule will be active for and any holiday groups the
event will observe.
Date Schedules 00 and 01
If date schedule 00 is programmed, the feature will be
disabled (schedule is never active). If date schedule 01 is
programmed, the feature will be always on (schedule is
always active).
For more information regarding date schedule
programming, please refer to your PC4010/4020 v3.0
Installation Manual, section 14.1 “Date Schedules”.
There are 11 access door features which can be scheduled.
They are as follows:
Postpone Arm Schedule
Ref # [0011XX01YY04] where XX = module #, YY = door #
This schedule will program at what times the auto arming
sequence can be postponed by a user presenting their
access card at the appropriate reader. Only the partitions
to which the door’s zone are assigned and that are
selected in the arm/disarm mask will be affected.
The user’s access card must also be assigned to the
appropriate partitions and have the disarming attribute
enabled for the feature to work correctly. See your
PC4010/4020 Instruction Manual for information on
programming access codes and cards.
The default date schedule is 01.
Arm Request Schedule
Ref # [0011XX01YY05] where XX = module #, YY = door #
This schedule will program when the selected partitions
may be armed by a user presenting their access card at
the appropriate reader. Only the partitions assigned to
the door zone and selected in the arm/disarm mask will
be affected.
The user’s access card must also be assigned to the
appropriate partitions and have the arming attribute
enabled in order for arming to occur. See your PC4010/
4020 Instruction Manual for information on
programming access codes and cards.

8
The default date schedule is 01.
Door Unlock Schedule
Ref # [0011XX01YY06] where XX = module #, YY = door #
This schedule will determine when an access door will
be unlocked. When the door is unlocked, a user will not
require an access card to open the door. The door will
remain unlocked for the duration of the schedule.
Opening the door will not cause a door forced open event.
When the partition(s) to which the door zone is assigned
are armed, the door will automatically lock at the
beginning of the exit delay. If the Door Unlock schedule
becomes active while the partition(s) are armed, the door
will not unlock. However, if the partition is disarmed while
the door unlock schedule is active, the door will unlock,
and will remain unlocked until the scheduled end time.
NOTE: If the door is assigned to more than one
partition, the door will only lock once the last partition
to be armed has begun its exit delay.
The default date schedule is 00 (disabled).
Request To Exit (REX) Schedule
Ref # [0011XX01YY07] where XX = module #, YY = door #
This schedule controls the Unlock on REX option. When
the schedule is active, tripping a Request To Exit device
will cause the door to unlock for the programmed Door
Unlock time (see section 3.5 “Door Times”). If the
schedule is not active, a Request To Exit will not cause
the door to unlock.
The default date schedule is 01.
Second Card Schedule
Ref # [0011XX01YY08] where XX = module #, YY = door #
This schedule will determine when users with the Wait
For Privilege option enabled will require a Privileged user
to grant them access to the area. If the Second Card
Schedule is active, the following will occur:
The user with the Wait For Privilege card presents their
card first. The LED on the card reader will flash slowly
for 10 seconds. If during this time a Privileged card is
used, the door will be unlocked. Only privileged cards
are capable of allowing access to the system. If a non-
privileged card is used, the door will not be unlocked
and a log will be made to the buffer. This feature is used
for monitoring the access of users on the system.
The default date schedule is 00 (disabled).
Disarm Request Schedule
Ref # [0011XX01YY09] where XX = module #, YY = door #
This schedule will program the times when the selected
partitions may be disarmed by a user presenting their
access card at the appropriate reader. Only partitions
which have the door’s zone assigned to them, and that
are selected in the arm/disarm mask will be affected.
To disarm the partition(s), the user must present their
access card and open the door. The partition(s) will be
disarmed if the Disarm Request schedule is active. If the
user presents their card is outside of the Disarm Request
schedule time window, the door will be unlocked but
the partition(s) will not be disarmed when the door is
opened. The user must then enter their access code at a
keypad to disarm the partition(s).
NOTE: To disarm a partition or enter a partition which
is armed, the user must be assigned to the partition,
and the user’s disarm attribute must be enabled in
access code and card programming. See your PC4010/
4020 Instruction Manual for information on
programming access codes and cards.
The default date schedule is 00 (disabled).
Code Schedule
Ref # [0011XX01YY11] where XX = module #, YY = door #
When this schedule is active, the door will not unlock
until the card is presented AND a valid access code is
entered on the keypad. When the schedule is inactive,
the door will unlock when an access card is presented.
If Schedule [00] is programmed into this section, the door
will be unlocked by an access card only when the
partition(s) the door is assigned to are disarmed. When
the partitions are armed, an access code will also be
required.
NOTE: The Code Required option must be enabled in
order for this feature to work.
The default date schedule is 01.
Forced Open Schedule
Ref # [0011XX01YY12] where XX = module #, YY = door #
When this schedule is active and a door is opened without
tripping a REX device, a Door Forced Open event will be
logged to the event buffer and transmitted to central
station. When the schedule is inactive and a door is forced
open, the event will be logged, but not transmitted.
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).
Forced Open Bell Schedule
Ref # [0011XX01YY13] where XX = module #, YY = door #
When this schedule is active and a door is opened without
tripping a REX device, the partition(s) the door is assigned
to will go into alarm. The alarm will be on until the bell
cut-off time expires, or until an access code is entered to
silence the alarm.
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).
Open Too Long Schedule
Ref # [0011XX01YY14] where XX = module #, YY = door #
When the schedule is active and the assigned door is left
open past the Door Open time, an Open Too Long event
will be logged to the event buffer and transmitted. When
the schedule is inactive and the door is left open past the
Door Open time, the event will be logged but not
transmitted. The Door Open time is default set at 30
seconds but can be changed (see Section 3.4 “Door
Times”).

9
P r o g r a m m i n g t h e P C 4 8 2 0
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).
Open Too Long Bell Schedule
Ref # [0011XX01YY15] where XX = module #, YY = door #
When the schedule is active and the assigned door is left
open past the Door Open time, the partition(s) the door is
assigned to will go into alarm. The alarm will remain on
until the bell cut-off time expires, or until an access code is
entered to silence the alarm. The Door Open time is set at
30 seconds by default, but can be changed (see Section 3.4
“Door Times”).
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).
3.7 Access Level
Ref # [0011XX01YY10] where XX = module #, YY = door #
Access levels allow specific users to have access to areas
of the system at various times of the day. Each door can
have multiple access levels assigned to it. Each access
level will follow one date schedule.
There are 63 access levels for each door. To program access
levels, select an access level number (02-63) and then enter
the schedule number that the access level will follow.
Access cards programmed with access level 01 always
have access to all doors. Access levels 02 - 63 will be
recognized by the card reader during the windows
provided by the assigned date schedule.
Date Schedules 00 and 01
Access levels programmed with date schedule 01 will
always be recognized by the door. Access levels
programmed with date schedule 00 will never be
recognized by the door. In order to disable an access level
for a door, assign the access level to Date Schedule 00.
By default all access levels are assigned to Date Schedule
00 (disabled).
3.8 Programming Access Cards
In order for an access card to function on the PC4820 the
card must first be programmed into the PC4010/4020.
This is done through user programming (enter
[*][5][system master code] or [supervisory code]). See
your PC4010/4020 Instruction Manual for more
information on programming access codes and cards.

10
S e c t i o n 4
Diagnostics
4.1 Hardware Reset
On occasion, it may be necessary to perform a reset of the
PC4820 to factory default programming. To perform a
hardware reset of the PC4820, the following steps must
be performed:
1. Power down the PC4010/4020 by removing both AC
and battery power from the control panel.
2. Power down the PC4820 modules by removing both
AC and battery power from the units.
3. Remove all connections from the following PC4820
terminals; OUT (for OUT DOOR 1), Door (for
INPUTS DOOR 1) and AUX+.
4. On the selected PC4820, connect a short from the
terminals marked as OUT (for OUT DOOR 1) and
Door (for INPUTS DOOR 1). Next connect a 5600 ohm
resistor from the Door input to the AUX+ terminal.
5. Restore AC power to the PC4820 module(s).
6. Wait for 10 seconds then remove AC power to the
PC4820 module(s).
7. Remove the connections made in Step 4.
8. Any terminal connections removed in Step 3 can now
be reconnected.
9. Restore AC and battery power to the PC4820
module(s)
10. Restore AC and battery power to the PC4010/4020
control panel.
The PC4820 will now indicate to the PC4010/4020 that a
hardware default has been performed and the PC4010/
4020 will retransmit all programming information back
to the PC4820 modules. All keypads on the system will
beep quickly 16 times to indicate that the programmed
information has been sent to the PC4820.
Be sure to remove all connections involved in the hardware
default procedure when the hardware default has been
completed.
NOTE: When performing a hardware or software
default of the PC4010/4020 be sure to also perform a
hardware default on the PC4820. This will insure that
all unwanted programming has been removed from
the module.
4.2 Diagnostics via VTAL LED (L1)
The VTAL LED (located on the right hand side of the circuit
board) of the PC4820 is capable of providing diagnostics
information for various conditions that may appear on
the module.
• Steady flash (once per second) indicates normal
operation.
• Fast flash indicates that communication to the
PC4010/4020 has been lost (Combus fault).
• On steady (1/2 second) indicates data is being
received from an access card reader.

PC4820 Programming Worksheet
Record your PC4820 module programming information here. Make one copy of this sheet for each PC4820 you will install.
[0011] PC4820 Options NOTE: XX = module #; YY = door #
[0011XX] PC4820 Module Number:
[0011XX00] Reader Type Default: 00
[0011XX01YY]Select Door Number: Door 01 Door 02
[0011XX01YY00] Toggle Options: Default Default
Lock Reversed? N N
Unlock on REX? Y Y
Flash When Arm? Y Y
Relock on Arm? N N
Lock on Close? N N
Code Required? N N
LED Reversed? N N
Two Readers? N N
[0011XX01YY01] Arm/Disarm Mask:
Partition: 1 2 3 4 5678 12345678
NNNNNNNN NNNNNNNN
[0011XX01YY02] Door Times:
Door Unlock Time 010 010
Door Open Time 030 030
[0011XX01YY03] Zone Assignment 000 000
[0011XX01YY04] Postpone Arm Schedule 01 01
[0011XX01YY05] Arm Request Schedule 01 01
[0011XX01YY06] Door Unlock Schedule 00 00
[0011XX01YY07] REX Schedule 01 01
[0011XX01YY08] Second Card Schedule 00 00
[0011XX01YY09] Disarm Request Schedule 00 00
[0011XX01YY10] Access Level (enter 02 - 63) Default (all levels): [00]
Access Schedule Access Schedule Access Schedule Access Schedule Access Schedule Access Schedule
Level Number Level Number Level Number Level Number Level Number Level Number
02 23 44 02 23 44
03 24 45 03 24 45
04 25 46 04 25 46
05 26 47 05 26 47
06 27 48 06 27 48
07 28 49 07 28 49
08 29 50 08 29 50
09 30 51 09 30 51
10 31 52 10 31 52
11 32 53 11 32 53
12 33 54 12 33 54
13 34 55 13 34 55
14 35 56 14 35 56
15 36 57 15 36 57
16 37 58 16 37 58
17 38 59 17 38 59
18 39 60 18 39 60
19 40 61 19 40 61
20 41 62 20 41 62
21 42 63 21 42 63
22 43 22 43
Default Default
[0011XX01YY11] Code Schedule 01 01
[0011XX01YY12] Forced Open Sched. 00 00
[0011XX01YY13] Forced Open Bell 00 00
[0011XX01YY14] Open Too Long Schedule 00 00
[0011XX01YY15] Open Too Long Bell 00 00
I
______I
______
I
I
___________I
I
___________I
I
___________I
I
___________I
I
___________I
I
___________I
I
___________I
I
___________I
I
_________I
_________I
_________I
_________I
_________I
_________I
_________I
_________I
I
______I
______I
______
I
I
______I
______I
______
I
I
______I
______I
______
I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
___________I
I
___________I
I
___________I
I
___________I
I
___________I
I
___________I
I
___________I
I
______I
______I
______ I
I
______I
______I
______ I
I
______I
______I
______ I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
______I
______I
I
_________I
_________I
_________I
_________I
_________I
_________I
_________I
_________I

Security Products
TM
©1998 Digital Security Controls Ltd.
1645 Flint Road, Downsview, Ontario, Canada M3J 2J6
(416) 665-8460 • Fax (416) 665-7498 • 1-800-387-3630
Printed in Canada 29002622 R0

PC4820 v1.2 • Installation Manual
WARNING: This manual contains information on limitations
regarding product use and function and information on the
limitations as to liability of the manufacturer. The entire manual
should be carefully read.

LIMITED WARRANTY
Digital Security Controls Ltd. warrants the original purchaser that for a period of twelve
months from the date of purchase, the product shall be free of defects in materials and
workmanship under normal use. During the warranty period, Digital Security Controls
Ltd. shall, at its option, repair or replace any defective product upon return of the product
to its factory, at no charge for labour and materials. Any replacement and/or repaired
parts are warranted for the remainder of the original warranty or ninety (90) days, which-
ever is longer. The original owner must promptly notify Digital Security Controls Ltd. in
writing that there is defect in material or workmanship, such written notice to be received
in all events prior to expiration of the warranty period.
International Warranty
The warranty for international customers is the same as for any customer within Canada
and the United States, with the exception that Digital Security Controls Ltd. shall not be
responsible for any customs fees, taxes, or VAT that may be due.
Warranty Procedure
To obtain service under this warranty, please return the item(s) in question to the point of
purchase. All authorized distributors and dealers have a warranty program. Anyone re-
turning goods to Digital Security Controls Ltd. must first obtain an authorization num-
ber. Digital Security Controls Ltd. will not accept any shipment whatsoever for which
prior authorization has not been obtained.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relating to normal use. It
does not cover:
• damage incurred in shipping or handling;
• damage caused by disaster such as fire, flood, wind, earthquake or lightning;
• damage due to causes beyond the control of Digital Security Controls Ltd. such as
excessive voltage, mechanical shock or water damage;
• damage caused by unauthorized attachment, alterations, modifications or foreign objects;
• damage caused by peripherals (unless such peripherals were supplied by Digital Secu-
rity Controls Ltd.);
• defects caused by failure to provide a suitable installation environment for the prod-
ucts;
• damage caused by use of the products for purposes other than those for which it was
designed;
• damage from improper maintenance;
• damage arising out of any other abuse, mishandling or improper application of the
products.
Digital Security Controls Ltd.’s liability for failure to repair the product under this war-
ranty after a reasonable number of attempts will be limited to a replacement of the prod-
uct, as the exclusive remedy for breach of warranty. Under no circumstances shall Digital
Security Controls Ltd. be liable for any special, incidental, or consequential damages
based upon breach of warranty, breach of contract, negligence, strict liability, or any
other legal theory. Such damages include, but are not limited to, loss of profits, loss of
the product or any associated equipment, cost of capital, cost of substitute or replace-
ment equipment, facilities or services, down time, purchaser’s time, the claims of third
parties, including customers, and injury to property.
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in lieu of any and all other
warranties, whether expressed or implied (including all implied warranties of mer-
chantability or fitness for a particular purpose) And of all other obligations or li-
abilities on the part of Digital Security Controls Ltd. Digital Security Controls Ltd.
neither assumes nor authorizes any other person purporting to act on its behalf to
modify or to change this warranty, nor to assume for it any other warranty or liabil-
ity concerning this product.
This disclaimer of warranties and limited warranty are governed by the laws of the
province of Ontario, Canada.
WARNING: Digital Security Controls Ltd. recommends that the entire system be com-
pletely tested on a regular basis. However, despite frequent testing, and due to, but not
limited to, criminal tampering or electrical disruption, it is possible for this product to
fail to perform as expected.
Installer’s Lockout
Any products returned to DSC which have the Installer’s Lockout option enabled and
exhibit no other problems will be subject to a service charge.
Out of Warranty Repairs
Digital Security Controls Ltd. will at its option repair or replace out-of-warranty prod-
ucts which are returned to its factory according to the following conditions. Anyone
returning goods to Digital Security Controls Ltd. must first obtain an authorization num-
ber. Digital Security Controls Ltd. will not accept any shipment whatsoever for which
prior authorization has not been obtained.
Products which Digital Security Controls Ltd. determines to be repairable will be repaired
and returned. A set fee which Digital Security Controls Ltd. has predetermined and which
may be revised from time to time, will be charged for each unit repaired.
Products which Digital Security Controls Ltd. determines not to be repairable will be
replaced by the nearest equivalent product available at that time. The current market
price of the replacement product will be charged for each replacement unit.
WARNING Please Read Carefully
Note to Installers
This warning contains vital information. As the only individual in contact with system users, it is your
responsibility to bring each item in this warning to the attention of the users of this system.
System Failures
This system has been carefully designed to be as effective as possible. There are circumstances, how-
ever, involving fire, burglary, or other types of emergencies where it may not provide protection. Any
alarm system of any type may be compromised deliberately or may fail to operate as expected for a
variety of reasons. Some but not all of these reasons may be:
■■
■■
■Inadequate Installation
A security system must be installed properly in order to provide adequate protection. Every installation
should be evaluated by a security professional to ensure that all access points and areas are covered.
Locks and latches on windows and doors must be secure and operate as intended. Windows, doors,
walls, ceilings and other building materials must be of sufficient strength and construction to provide
the level of protection expected. A reevaluation must be done during and after any construction activity.
An evaluation by the fire and/or police department is highly recommended if this service is available.
■■
■■
■Criminal Knowledge
This system contains security features which were known to be effective at the time of manufacture. It
is possible for persons with criminal intent to develop techniques which reduce the effectiveness of
these features. It is important that a security system be reviewed periodically to ensure that its features
remain effective and that it be updated or replaced if it is found that it does not provide the protection
expected.
■■
■■
■Access by Intruders
Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection
by moving through an area of insufficient coverage, disconnect a warning device, or interfere with or
prevent the proper operation of the system.
■■
■■
■Power Failure
Control units, intrusion detectors, smoke detectors and many other security devices require an adequate
power supply for proper operation. If a device operates from batteries, it is possible for the batteries to fail.
Even if the batteries have not failed, they must be charged, in good condition and installed correctly. If a
device operates only by AC power, any interruption, however brief, will render that device inoperative
while it does not have power. Power interruptions of any length are often accompanied by voltage fluctua-
tions which may damage electronic equipment such as a security system. After a power interruption has
occurred, immediately conduct a complete system test to ensure that the system operates as intended.
■■
■■
■Failure of Replaceable Batteries
This system’s wireless transmitters have been designed to provide several years of battery life under normal
conditions. The expected battery life is a function of the device environment, usage and type. Ambient
conditions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the
expected battery life. While each transmitting device has a low battery monitor which identifies when the
batteries need to be replaced, this monitor may fail to operate as expected. Regular testing and maintenance
will keep the system in good operating condition.
■■
■■
■Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver under all circumstances which could include metal objects placed on or
near the radio path or deliberate jamming or other inadvertent radio signal interference.
■■
■■
■System Users
A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary
physical disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is
important that all system users be trained in the correct operation of the alarm system and that they
know how to respond when the system indicates an alarm.
■■
■■
■Smoke Detectors
Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of
reasons, some of which follow. The smoke detectors may have been improperly installed or positioned.
Smoke may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roofs,
or on the other side of closed doors. Smoke detectors may not detect smoke from fires on another level of
the residence or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot
sense all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by
carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage
of flammable materials, overloaded electrical circuits, children playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances when there is insufficient
warning to allow all occupants to escape in time to avoid injury or death.
■■
■■
■Motion Detectors
Motion detectors can only detect motion within the designated areas as shown in their respective installa-
tion instructions. They cannot discriminate between intruders and intended occupants. Motion detectors
do not provide volumetric area protection. They have multiple beams of detection and motion can only be
detected in unobstructed areas covered by these beams. They cannot detect motion which occurs behind
walls, ceilings, floor, closed doors, glass partitions, glass doors or windows. Any type of tampering whether
intentional or unintentional such as masking, painting, or spraying of any material on the lenses, mirrors,
windows or any other part of the detection system will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in temperature. However their effective-
ness can be reduced when the ambient temperature rises near or above body temperature or if there are
intentional or unintentional sources of heat in or near the detection area. Some of these heat sources
could be heaters, radiators, stoves, barbeques, fireplaces, sunlight, steam vents, lighting and so on.
■■
■■
■Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if
there is an intervening wall or door. If warning devices are located on a different level of the residence or
premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices may be
interfered with by other noise sources such as stereos, radios, televisions, air conditioners or other appliances,
or passing traffic. Audible warning devices, however loud, may not be heard by a hearing-impaired person.
■■
■■
■Telephone Lines
If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of
time. Also an intruder may cut the telephone line or defeat its operation by more sophisticated means
which may be difficult to detect.
■■
■■
■Insufficient Time
There may be circumstances when the system will operate as intended, yet the occupants will not be
protected from the emergency due to their inability to respond to the warnings in a timely manner. If the
system is monitored, the response may not occur in time to protect the occupants or their belongings.
■■
■■
■Component Failure
Although every effort has been made to make this system as reliable as possible, the system may fail to
function as intended due to the failure of a component.
■■
■■
■Inadequate Testing
Most problems that would prevent an alarm system from operating as intended can be found by regular
testing and maintenance. The complete system should be tested weekly and immediately after a break-
in, an attempted break-in, a fire, a storm, an earthquake, an accident, or any kind of construction
activity inside or outside the premises. The testing should include all sensing devices, keypads, con-
soles, alarm indicating devices and any other operational devices that are part of the system.
■■
■■
■Security and Insurance
Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm
system also is not a substitute for property owners, renters, or other occupants to act prudently to prevent
or minimize the harmful effects of an emergency situation.

Table of Contents
Introduction 1
1.1 PC4820 Access Control Module Specifications ...................................................................................................................1
Installation and Wiring 2
2.1 Plan Your Installation .............................................................................................................................................................. 2
2.2 Installation Steps ...................................................................................................................................................................... 2
2.3 Inputs – POST, ARM and REX ............................................................................................................................................... 2
2.4 Outputs – LED, BUZ and OUT Terminals .......................................................................................................................... 3
2.5 Door Locking Devices – LK1 & LK2 Terminals ...................................................................................................................3
2.6 Access Card Readers ............................................................................................................................................................... 3
PC4820 Connection Chart............................................................................................................................................................... 4
PC4820 List of Supported Readers and Cards ............................................................................................................................4
Cabling Specifications ..................................................................................................................................................................... 5
PC4820 Access Control Module Reader Connections ................................................................................................................ 5
Programming the PC4820 6
3.1 Programming Reader Types ................................................................................................................................................... 6
3.2 Reader Options ......................................................................................................................................................................... 6
3.3 Arming and Disarming with Access Cards ......................................................................................................................... 6
3.4 Door Times ................................................................................................................................................................................ 7
3.5 Zone Assignment for Access Doors ...................................................................................................................................... 7
3.6 Access Door Schedules............................................................................................................................................................ 7
3.7 Access Level .............................................................................................................................................................................. 9
3.8 Programming Access Cards ..................................................................................................................................................... 9
Diagnostics 10
4.1 Hardware Reset ...................................................................................................................................................................... 10
4.2 Diagnostics via VTAL LED (L1)........................................................................................................................................... 10
PC4820 Programming Worksheet 11
Limited Warranty 14
PC4820 Access Control Module Wiring Diagram 16
i
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your authority to use this equipment.
This equipment generates and uses radio frequency energy and if not installed and used properly, in strict accordance with the manufacturer’s instructions,
may cause interference to radio and television reception. It has been type tested and found to comply with the limits for Class B device in accordance with
the specifications in Subpart “B” of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in any residential
installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to television
or radio reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
•Re-orient the receiving antenna
•Relocate the alarm control with respect to the receiver
•Move the alarm control away from the receiver
•Connect the alarm control into a different outlet so that alarm control and receiver are on different circuits.
If necessary,the usershould consultthe dealer oran experiencedradio/television technicianfor additional suggestions.The user mayfind thefollowing booklet
prepared by the FCC helpful: “How to Identify and Resolve Radio/Television Interference Problems”. This booklet is available from the U.S. Government
Printing Office, Washington, D.C. 20402, Stock # 004-000-00345-4.

• Battery and AC Connections
• Combus Connections
PC4820 Access Control Module
W i r i n g D i a g r a m
• Lock device and Reader Connections
• Typical Zone Circuits
ii
Table of contents