DUCH CAM888 User manual

DCH Users Manual
U
CONTENT
I Preface 1
1.1 Notices when open the cases 2
1.2 Install environment 2
1.3 Warning of installment 3
1.4 Attention of connection design 3
II Function And Specification 4
2.1 Function list 4
2.2 Specification Table 4
III Installation and connection 5
3.1 Installation dimensions 5
3.2 Parts connection diagram 6
3.3 Terminal board description 7
3.4 Interface circuit 8
3.5 Sensor dimension 8
IV System Interface 9
4.1 ATP Function Guide 9
4.2 ATP Action Timing Diagram 10
4.3 Wiring example 10
V Parameter Setting 12
5.1 Key specification 12
5.2 Digital display 12
5.3 Enter setting 12
5.4 Cam parameter setting 13
5.5 System parameter setting 15
5.5.1 System menu entrance 15
5.5.2 System parameter setting table is as following 16
5.5.3 Description of system menus 16
5.5.4 Rotary direction setting 16
5.5.5 Controller 180°calibrate 16
5.5.6 Counts setting 17
5.5.7 Other parameter of controller 17
5.5.8 The production count arriving function 17
VI Protection and alarm 18
6.1 Protection And Alarm Instruction 18
6.2 Protection and trouble codes 18
1
I Preface
Thank you for your using of CAM888 cam controller, here after is called controller, which is
produced by DUCH automatic technology CO., Ltd. The controller adopts the newest
technology. And our company has the completely independent intellectual property. Besides, it is
the national invention patent product. The characteristics are as following:
zLeading technology
☆It uses the high speed microprocessor, the large-scale field programmable chip and the
entire digital high accuracy high speed control.
☆Gear change system: Intelligent calculate of stopping at top dead end.
☆It is dynamic indicating for cam angle setting, which is more human nature.
zHigh performance
☆The displayed precision of angle measurement may amount to ±0.1°.
☆braking test has 2 channels outputs . programmable scissors cam has 6
channels outputs. Production value has 1channel output.system normal
indication has 1 channel output. Totally 16 channels output.
Before using the controller please read the manual carefully Make sure it is used correctly
and then it will display its high performance. Moreover, this manual is an appendix which is sent
with the controller. Please take care of it after you have used it. So that it will work when you
repair and maintain the controller.
1.1 Notices when open the cases
When open the case, please confirm the following items carefully.
◇If there is any damage during the delivery.
◇Check if the rating value on name plate is the same with your requirement. Make sure the
accessories are whole.
◇Any question please contact us or the supplier.
1.2 Install environment
◇The height is no more than1000m;When it is over1000m, it will reduce the capability of
the controller because of the thin air.
◇Environment temperature:-10℃~+40℃Environment humidity:No more than 50% at
40℃. No more than 90% below 20℃.
◇When the installation base allowable vibration is 10~150HZ, its maximum vibration
acceleration should be no more than 5m/s².
◇Power supply:DC24V1A.
2

DCH Users Manual
U
◇Install a circuit breaker or protecting instrument in the exterior circuit. For safety, the
controller should be fixedly mounted, and the cable should be put in the pipe.
1.3 Warning of installment
◇Never install it on combustible devices. Never put the combustible things beside it. Never
install it in the surrounding which has volatile gas, dust, point-blank sunshine, high
temperature or humidity. Never drop any metal into the controller.
◇Do not disassemble or install the present control by yourself, please reach for the
professional engineer.
◇Please make sure the power line in well condition. If it is damaged or pressed by heavier
goods, it might cause electricity leakage or fire accident.
◇Please make sure the controller is fixedly mounted in the assembly hole to prevent
damage.
◇Keep the control a suitable distance from other instrument.
◇Install a masking means to isolate static electricity, noise signals, magnetic field or
radiation to prevent operation failure.
1.4 Attention of connection design
◇We suggest that you use the DC24V/1A power source. Separate the input & output power
supply from system power supply.
◇Do not put the controller to earth at the same point with motor and transducer. You should
put it in another line. Please ensure that the controller and the press are well earthed.
◇Please install filters at heavy load terminal and inductive terminal to avoid the controller
from being jammed. Please add resistance and capacitance devices to AC contactor and
solenoid valve. The resistance takes 22Ω/2W, the capacitance takes 0.1μF/3KV. Install the
absorb equipment at the side near the contactor coil or the valve coil.
◇The controller cable should as short as possible. Do not put it together with the high
pressure electricity. If it is difficult for you please use metal hose to separate them and put
the AC and DC to earth dividually.
Attention: Putting the sensor wire to earth is extremely important. Please ensure that the
shielded wire of sensor connect wire is well earthed.
3
II Function And Specification
2.1 Function list
SPM/Angle Display: Continuous mode, showing the value of SPM when SPM>8,
otherwise showing the angle. Other mode, showing the angle.
Production value display: 6 digits. The max. is 999999.
★Brake signal:2 ways redundancy output.
Top point locate:Automatically compensate the warp when positioning the Top
dead end Point.
Cam Setting:Programmable cam output 6 channels; Programmable cam
output 6 channels.
Production value has 1 channel output.
Bottom Dead Point(180°) Setting.
Forwards/Backwards running of the Angle Sensor Setting.
★Protection Function:locked protection,power off protection.
Software lock protection for system parameter
System unusual alarm.
Communication: Standard RS-485 bus communication connection
2.2Specification Table
Item Specification
Power Supply DC: 10~30V, 1A
OperationTemperature 0~40℃
Keeping Temperature -20~70℃30~85%
Angle Display 0~359º
Angle Setting 0~359º
Stroke 0~800 stroke/minute (360P/R)
Angle Sensor 1°
Indicating lamp Angle position indicating lamp 36
Display Angle/Speed(*1channel with 3 orders)
Counter(*1 channel with 6 orders)
Setting Key 4 micro switch keys(up, down, put in, enter)
Cam Output 0~359º, programmable scissors cam outputs are 6 channels,
programmable cam outputs are 9 channels.
Cam input 4 channels,DC24V±10%, ,Max. input current 5mA or dry
connect point input.
Output 16channels, collector through way output, max. fill current is
100mA
4

DCH Users Manual
UIII Installation and connection
3.1 Installation dimensions
Outline dimension :
Hole dimension:
5
3.2 Parts connection diagram
Caution:
1. Make sure the voltage and the poles.
2. Make sure the plug inserted into the socket totally and in correct way. Leave the wire
a suitable length for disassembly.
3. To avoid the controller being interfered, please eliminate the noise at heavy load and
the inductance loading terminal.
6

DCH Users Manual
U
3.3 Terminal board description:
7
3.4 Interface circuit
3.5 Sensor dimension
8
NO Name Index
F01 Cutting cam output 1
F02 Cutting cam output 2
F03 Cutting cam output 3
F04 Cutting cam output 4
F05 Cutting cam output 5
F06 Cutting cam output (production count
reaches output)
6
F07 Cam output 7
F08 Cam output 8
F09 Cam output 9
F10 Cam output 10
F11 Cam output 11
F12 Cam output 12
FC Production value output 13
RD Normal Indication Signal System 14
BR1 Brake signal 1 15
BR2 Brake signal 2 16
24V +24V power supply terminal 18
0V 0V power supply terminal 19
I1 System reset 20
I2 ATP 21
I3 Running 22

DCH Users Manual
UIV System Interface
4.1ATP(Automatic positioning the Top dead end Point) Action Timing Diagram
9
4.2ATP(Automatic positioning the Top dead end point) Wiring example:
4.3ATP(Automatic positioning the Top dead end Point)
ATP Function Guide
a. IN2 ON(Inch----ATP Function Disable(OUT2 ON)
b. IN2 OFF IN3 ON (Single Mode)
c. IN2 ON=>OFF, IN3 ON(Continues Mode )------
ATP Function Enable(ATP CAM arrive,OUT2 ON=>OFF ,Wait for IN3 OFF,
OUT2 OFF=>ON
10

DCH Users Manual
U
4.3.3 PLC program list
LD X003 LD X001
OUT Y002 OR MO
LDI X001 AND Y000
OUT TO K3 AND X006
LDI X004 OUT MO
AND X000 LD X006
OUT T1 K3 ANI MO
LDI X004 OR X004
OR X005 ANI X005
OR X006 OUT Y001
AND Y006 END
LD X000
ANI T1
ORB
AND X002
AND X010
ANI TO
OUT YO 11
V Parameter Setting
5.1 Key specification
Operationpanelfunctiontable
Item Name Function
Increase/Up Menu up or numerical value increase. When adjust
the numerical value, keep pressing it to make the
value increase quickly.
Reduce/Down Menu down or numerical value reduce. When
adjust the numerical value, keep pressing it to
make the value reduce quickly.
Enter/Shift Press this key to enter the menu. When adjust the
content,press it to shift.
Confirm/Exit Exit the setting or exit the submenu.
Keep pressing the key for more than 4 seconds to
reset the counter.
5.2 Digital display
The quaternion illuminant digital monitor upside is used to display the stroke/angle value:
In continuous mode, it displays stroke when the stroke is more than 20 times/minute, otherwise
it displays angle value. In other working modes it displays angle value. When it displays angle
value, the left indicating lamp A turns on and the right indicating lamp S extinguishes. When it
display stroke, the left indicating lamp A extinguishes and the right indicating lamp S turns on.
The hexad illuminant digital monitor downside is used to display the work count.
When braking test is over, the quaternion illuminant digital monitor upside displays braking
angle. The hexad illuminant digital monitor downside displays braking time.
In setting state the illuminant digital monitor displays multiple information the user needs.
The flashing point is the parameter focus. It indicates the position which cursor located.
5.3 Enter setting
When the device is free ( equipment in idle condition),press and together for
12

DCH Users Manual
U
more than 3 seconds to make the controller enters into setting status. Here, the digital
monitor will flash. Then press or to select the menu. Press to enter into the
submenu.
5.4 Cam parameter setting
Cutting Cam parameter setting:
Code Description Unit Range Default
On Angle Degree 0~359 0
Off Angle Degree 0~359 135
F01
Scissors Counter Times 2-6000 0
On Angle Degree 0~359 0
Off Angle Degree 0~359 135
…
Scissors Counter Times 2-6000 0
On Angle Degree 0~359 0
Off Angle Degree 0~359 135
F06
Scissors Counter Times ------ 0
F07-F12 Cam parameter setting:
Code Description Unit Range Default
On Angle Degree 0~359 0
F07
Off Angle Degree 0~359 135
On Angle Degree 0~359 0
…
Off Angle Degree 0~359 135
On Angle Degree 0~359 0
F12
Off Angle Degree 0~359 135
FC Production value Times 0-999999 0
13
Cam parameter setting steps::
1
Enter setting status. Press or
to select the cam code
which will be set.
2
Press to enter the
submenu. Here item name in
submenu flashing, press or
to select the item which
will be adjusted.
3
Press to enter the
adjustment. Here item content
in submenu flashing, press
or to select the parameter
which will be adjusted.
4
Press to exit the parameter
adjustment. Back to submenu
and repress to back to
main menu. Select other cam.
Repeat step2、3.
5
Parameter setting finished.
Press to exit the setting.
System saves the data
automatically.
or setting steps take the scissors cam F05 as example. F05 parameter:Start Angle =270°
EndAngle =90°
Scissors Count=15
a. When the device is free ( equipment in idle condition),press and together for
more than 3 seconds to make the controller enters into setting status. Here, the digital monitor
will flash. Than press to select F05. Press to enter into the submenu.
b. Now the submenu starting angle value at right side will flash. Press or to adjust
the parameter. Keep pressing it for a long time the value will change quickly. When it gets to
270, press to back to submenu.
14

DCH Users Manual
U
c. By now the starting angle(oN) in submenu start to flash. Press or to select the
item. Adjust it until the end angle(oF) flashes. Press to enter the adjustment. Now the
starting angle value at right side will flash. Press or to adjust the parameter. Keep
pressing it for a long time the value will change quickly. When it gets to 90, press to back to
submenu.
d. At this time the submenu flashes. Press or to enter the item. Adjust it until the
scissors count (N) flashes. Then press to enter the adjustment. Now the starting angle value
at right side will flash. Press or to adjust the parameter. Keep pressing it for a long time
the value will change quickly. When it gets to 15, press to back to submenu.
e. Under the submenu, press to back to the main menu. Press the key once more it will
exit the setting process. At last the system will save the data automatically. The setting is over.
Remind: When you adjust the starting angle the circumferential 36 indicating lamp will
display the cam range which you want to adjust. It is more intuitionistic.
5.4.2 Production count reaches prarameter setting
a. In the system menu FC is production count item .
b. Input the FC setting menu, press change the value ,and then press and
regulation of the value. After setting ,press to exit the setting. System saves the data
automatically.
5.5 System parameter setting
The system parameter is important for controller work. Do not change it unless the system
needs to be debugged. The system parameter is equipped with the password protection.
5.5.1 System menu entrance
a. When the device is in idle condition,press and together for more than 3
15
seconds to make the controller enters into setting status.
b. Now the quaternion digital monitor upside will flash. Press or to select the
menu. Choose P01 and press to enter it.
c. Input the system password by or . Press to return to the main menu.
d. Press or to select the menu. Item P02-P12 will appear.
Caution:password = 777.
5.5.2 System parameter setting table is as following:
5.5.3 Description of system menus:
In the system menu P02-P03 is modifiable parameter item while P11-P12 is read-only
item. The settable parameter item is used to set the parameter or system state. The read-only
item is merely used to observe the related parameter of the controller.
5.5.4 Rotary direction setting
When install the controller, if you find that the crank rotary direction is inconsistent from
the controller indicating direction please reset the direction value in menu P02.
The method is as following:
a. Use the same steps as 5.5.1 to enter the system menu
b. Now the quaternion digital monitor upside will flash. Press or to select the
menu. Choose P02 and press to enter it.
c. Use or to select 0 or 1.Attention: if you find that the crank rotary direction is
inconsistent from the controller indicating direction please select 0 while the original value is 1
and select 1 while it is 0.
d. Press to back to the main menu. Press the key once more it will exit the setting
process. At last the system will save the data automatically. The setting is over.
5.5.5 Controller 180°calibrate
It adopts absolute value rotary transducer. Because the mounting position of transducer
does not correspond to crank shaft position completely, they need to be calibrated. The angle is
180°.
16
Cod
e Description Unit Range Default
P02 Rotary direction setting 0~1 0
P03 180°calibration 0~359
P11 Electricity times on controller Read-only
P12 Controller software edition number Read-only

DCH Users Manual
U
The method is as following:
a. Put the press in inch mode, then adjust the slide to the lowest point(180°).
b. Use the same steps as 5.5.1 to enter the system menu.
c. Now the quaternion digital monitor upside will flash. Press or to select the
menu. Choose P03 and press to enter it.
d. It displays 180 and flashes. Press to stop it from flashing.
e. Press to back to the main menu. Press the key once more it will exit the setting
process. At last the system will save the data automatically. The setting is over.
5.5.6 Counts setting
Count the work of counter-point perspective, the system is set to 135 degrees (can be
customized)
5.5.7 Other parameter of controller
P11-P12 is read-only. Adjust it to the corresponding menu. It displays the data. You can not
change it.
P11------- Electricity times on controller, which used to estimate the time controller has
worked.
P12------- Controller software edition number
The method is as following:
a. Use the same steps as 5.5.1 to enter the system menu
b. Now the quaternion digital monitor upside will flash. Press or to select the
menu. Choose P11 to P12 the digital displayer will display the corresponding data.
c. Press to exit the setting.
5.5.8 The production count arriving function
1. The system menu of the F06 function for the production of the second count of options to
reach a maximum count value is 999999;
2. When the count reaches the production of F06 to set a value of "0" when the count reaches
the production is turned off; F06 setting does not affect the way that the output is "cutting the
output cam."
3. When the set count reaches the value of the production of F06 is not "0" when the count
reaches the production function of opening, F06 channel into a count to reach the output.
4. F06 to set the menu items into the system, with key switch counts the number of bits, and
then adjust the count, or key, set up, press to confirm and exit automatically saved.
5. Count arrived, in the last ending point (0 degrees), the output signal, F06 channel, a long
bright light, blinking count, the system stops working, press reset button cleared and re-start
work; work halfway through the count is cleared , its function will be back to work.
17
VI Protection and alarm
6.1 ProtectionAndAlarm Instruction
The controller will shut off system ‘Ready’ signal and output ‘Stop’ signal when it
inspects the unusual. System will display the corresponding unusual code.
6.2Protection and trouble codes:
Caution:When it alarms, please eliminate the troubles at first and then eliminate the
alarm.
Press enter key or input the alarm reset signal to eliminate the alarm.
Code Description Unusual Reason
Eliminate
Method
E01 Main Memory
Unusual Power、Chip Replace
controller
E02 Sub Memory
Unusual Power、Chip Replace
controller
E03 CPU Unusual CPU Chip Replace
E05 Brake Out Put
Unusual
Brake Circuit,
Redundancy
Protection
Replace
controller
E06 Sensor Unusual
Wiring Unusual
or Damaged
Check rotary
transducer
E08 RS485 Wiring Unusual Check
E09 RS485 Wiring Unusual
18
Table of contents