out of phase. This would reverse the test results. To correct this, remove the motor assembly and move the damper linkage
180 degrees. Re-install the motor assembly.) If this procedure is not correct, test for 24 volts at terminals “1” & “2” at
the Damper. (Constant non-controlling 24 volts ac) Then test for 24 volts at Damper terminals “1” & “4”. (Controlling
24 volts on a call open) Voltage readings at the Panel Terminals “1”, “2” and “4” should match readings on corresponding
Damper Terminals. If the voltages are not present at the damper but are on the panel, a break in the wiring is indicated.
If the test voltages are not present at the panel call DuroZone Technical Support.
4. Cool Mode Test Procedure.
A. Leave the Thermostats for Zones #2 and #3 in the “OFF” position. Put the Zone #1 Thermostat into the “COOL” mode,
Fan in “AUTO” and adjust the temperature setting above room temperature (not calling for cooling). This should energize
(LED indicators on) relays O1 (K2) and Valve (K12). If this is correct, proceed to step B. If relays O1 (K2) and Valve
(K12) do not energize, test for 24 volts at “C” & “O” on the Zone #1 Terminal Strip (TB2). If there is no voltage read-
ing, check the wiring and the thermostat for proper operation. If the voltage is present call DuroZone Technical Support.
B. Set the temperature on the Zone #1 Thermostat below the room temperature (calling for cooling). Relays O1 (K2), Valve
(K12), Z1 (K8) and CAC (K11) should be energized and the Heat Pump Cooling should activate. (Some thermostats
may have a time delay for short cycle protection) The Zone #1 Damper(s) should stay open and the Dampers for Zones
#2 and #3 should close. Relays Z1 (K8) and CAC (K11) should both be energized. If either or both are not energized,
test for 24 volts on the Zone #1 Terminal Strip (TB2) at “C” & “Y” for the Z1 (K8) Relay and “C” & “G” for the CAC
(K11) Relay.
If there are no voltages present, check the Wiring and the Thermostat for proper operation. If 24 volts ac is present call
DuroZone Technical Support.
If relays O1 (K2), Z1 (K8), Valve (K12) and CAC (K11) are energized and the Heat Pump Cooling does not activate,
test for 24 volts at “C” & “Y”, “C” & “G” and “C” & “O” on the Equipment Terminal Strip (TB1). If 24 volts is pres-
ent, check the Wiring and the Heat Pump for proper operation. If no voltage is present at any one of these terminals call
DuroZone Technical Support.
(Note: The Zone #1 Thermostat is the mode (“HEAT” or “COOL”) selector. Zone #2 and Zone #3 will
only function in the same system mode as Zone #1.)
C. The Zone #1 Thermostat should be in the “COOL” mode, and not calling for cooling. Put the Zone #2 Thermostat in
the “COOL” mode and not calling for cooling. Relays O1 (K2), Valve (K12) and O2 (K3) should be energized. If all the
relays are energized proceed to step D. If Relay O2 (K3) is not energized test for 24 volts ac at “C” & “O” of the Zone
#2 Terminal Strip (TB3). If 24 volts is not present, check the Wiring and the Zone #2 Thermostat for proper operation.
If the voltage is present and Relay O2 (K3) is not energized, call DuroZone Technical Support.
D. The Zone #1 Thermostat should be in the “COOL” mode, and not calling for cooling. Set only Zone #2 Thermostat to
call for cooling. Relays O1 (K2), O2 (K3), Valve (K12) and Z2 (K9) should be energized and the Heat Pump Cooling
should activate. The Zone #2 Damper(s) should open and the Dampers for Zones #1 and #3 should close. If the Relays,
Dampers and Heat Pump operate correctly, proceed to step E. If Relay Z2 (K9) is not energized, test for 24 volts at “C”
& “Y” of the Zone #2 Terminal Strip (TB3). If the voltage is not present check the Wiring and the Zone #2 Thermostat
for proper operation. If the voltage is present and Relay Z2 (K9) is not energized, call DuroZone Technical Support.
E. The Zone #1 Thermostat should be in the “COOL” mode and not calling for cooling. Turn the Zone #2 Thermostat “OFF”
and set the Zone #3 Thermostat to the “COOL” mode, but not calling for cooling. The relays O1 (K2), Valve (K12)
and O3 (K4) should be energized. If the relays are energized, proceed to step F. If relay O3 (K4) is not energized, test
for 24 volts at “C” & “O” of the Zone #3 Terminal Strip (TB4). If the voltage is not present, check the Wiring and the
Zone #3 Thermostat for proper operation. If the voltage is present and Relay O3 (K4) is not energized, call DuroZone
Technical Support.
F. The Zone #1Thermostat should be in the “COOL” mode, and not calling for cooling. Set only the Zone #3 Thermostat
to call for cooling. Relays O1 (K2), O3 (K4), Valve (K12) and Z3 (K10) should be energized and the Heat Pump Cool-
ing should activate. The Zone #3 Damper(s) should open and the Dampers for Zone #1 and Zone #2 should close. If
the Relays, Dampers and Heat Pump operate correctly, proceed to the “Heat Mode Test Procedure”. If relay Z3 is not
energized, test for 24 volts at “C” & “Y” of the Zone #3 Terminal Strip (TB4).
If the voltage is not present, check the Wiring and the Zone #3 Thermostat for proper operation. If the voltage is present
and Relay Z3 (K10) is not energized, call DuroZone Technical Support.
DuroZone JTZ-HP WIRING INSTRUCTIONS PAGE 7