EAE RCU2018 User manual

EAE KNX Room Control Unit
Product Manual RCUXXYY
RCU2018
RCU2000
RCU2016
RCU2000
RCU1212
RCU1200
RCU0808
RCU0800
Note: RCUXXYY where XX denotes the number of outputs and YY number of inputs.

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 1 / 80
Index
1 General............................................................................................................................................ 3
1.1 Device Description......................................................................................................................... 3
1.2 Technical Data ............................................................................................................................... 4
1.3 Connection Example...................................................................................................................... 6
1.4 Scale Drawings............................................................................................................................. 10
2 Communication Object Table........................................................................................................ 13
3 Parameters.................................................................................................................................... 15
3.1 General.................................................................................................................................. 15
3.2 Weather alarms..................................................................................................................... 17
3.3 Scene ..................................................................................................................................... 18
3.4 Enable Input a…s ................................................................................................................... 20
3.4.1 a - Switch Sensor ............................................................................................................... 22
3.4.2 a - Switch Dim Sensor........................................................................................................ 25
3.4.3 a - Blind Sensor.................................................................................................................. 26
3.4.4 a - Value/Forced Operation............................................................................................... 29
3.5 Enable Output A…J ................................................................................................................ 32
3.6 Switch .................................................................................................................................... 34
3.6.1 A1 - General....................................................................................................................... 34
3.6.2 A1 - Function ..................................................................................................................... 36
3.6.2.1 A1 - Staircase Function.................................................................................................. 37
3.6.2.2 A1 - External logic.......................................................................................................... 39
3.6.2.3 A1 - Sweep..................................................................................................................... 40
3.6.2.4 A1 - Scene...................................................................................................................... 41
3.7 Blind....................................................................................................................................... 42
3.7.1 A/B –General .................................................................................................................... 42
3.7.2 A/B –Drive Blind................................................................................................................ 44
3.7.3 A/B –Drive Slat.................................................................................................................. 46
3.7.4 A/B –Functions ................................................................................................................. 47
3.7.4.1 A/B –Position/Presets................................................................................................... 48
3.7.4.2 A/B –Weather alarm..................................................................................................... 50
3.7.4.3 A/B –Forced position.................................................................................................... 52
3.7.4.4 A/B –Feedbacks ............................................................................................................ 53
3.7.4.5 A/B –Scene.................................................................................................................... 54

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 2 / 80
3.8 Valve Control......................................................................................................................... 55
3.8.1 A/B –Control Input............................................................................................................ 55
3.8.2 A –Valve General .............................................................................................................. 57
3.8.3 A –Function....................................................................................................................... 59
3.8.4 A –Limit............................................................................................................................. 61
3.9 Fan Coil.................................................................................................................................. 62
3.9.1 Fan ..................................................................................................................................... 62
3.9.2 A/B1 - Status Message....................................................................................................... 64
3.9.3 A/B1 - Automatic Operation.............................................................................................. 66
3.9.4 A/B1 - Direct Mode............................................................................................................ 67
4 Function Chart............................................................................................................................... 68
5 Object Description......................................................................................................................... 69
5.1 General Object Description ................................................................................................... 69
5.2 Input Object Description ....................................................................................................... 70
5.3 Switch Object Description ..................................................................................................... 72
5.4 Blind Object Description........................................................................................................ 74
5.5 Valve Object Description....................................................................................................... 77
5.6 Fan Object Description.......................................................................................................... 78

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 3 / 80
1General
1.1 Device Description
•Room Control Unit RCU Series are designed as an all in one product for different room layouts such as
apartments, hotel rooms, hospitals and residences.
•Room Control Unit covers all requirements of the electrical installation of room applications and offers
following functions in one product.
✓Switching lighting
✓Switching loads
✓Controlling AC/DC blinds
✓Controlling fan coils (2 & 3-point valve)
✓Dry contact inputs
•RCUXXYY has XXx16A relay outputs. These outputs are grouped as 5/4/3/2 independent output
channels for XX = 20/16/12/8 respectively. Each channel can be configured to have different
modes of operation as follows,
•Suitable for switching resistive, capacitive and inductive loads as well as fluorescent lamp loads
according to EN 60 669. A single switch output provides following functions,
➢Staircase
➢External logic
➢Internal logic
➢Priority
➢Threshold
➢Operating hour
➢Sweep
•RCUXXYY has YY independent input channels. A single input channel provides following functions,
➢Switch / push button input
➢Dimmer control
➢Control of shutter/blinds
➢Value sending
➢Scene control
➢Counter for count pulse
•Manual control is possible for each channel through the built-in button panel.
•220V auxiliary power is NOT required.
➢Switching output x4
➢AC Blind x2
➢DC Blind x1
➢2 Point valve x2
➢3 point valve x2

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 4 / 80
1.2 Technical Data RCUXXYY Series
Type of protection
IP 20
EN 60 529
Safety class
II
EN 61 140
Power supply :
- Voltage
21V… 30V DC, SELV
- Current consumption
≤ 10 mA
External supply
-
-
Connections
- Screw terminals
- Max tightening torque
0,5…3,31 mm² solid and stranded wire
0,5…3,31 mm² stranded wire with
ferrule
0.5 Nm
- KNX
Bus connect terminal
Output
- Number
XX output
- Switching voltage
250 V AC; 50/60 Hz
- Switching current 250 V AC
- Switching current 250 V AC,
capacitive loads
16A / AC 1
16A (200µF)
- Maximum switching power
4000 VA
- Mechanical life
> 1 x 106
Type of load
- Incandescent lamp
4000 W
- Halogen lamp
4000 W
- Inductive loads, transformer
2000 W
- Electronic drivers
1500 W
Type of contact
- Potential-free, bistable
Input
- Number
YY binary inputs
- Scanning voltage
5 V pulsed
- Current
1 mA
- Cable length
< 300 m
Installation
- 35mm mounting rail
EN 60 715
Operating elements
- LED (red) and button
For physical address
Temperature range
- Ambient
-5° C + 45° C
- Storage
-25° C + 55° C
Humidity
- max. air humidity
85 % no moisture condensation
Dimensions
Width W in mm
Width W in units (18 mm modules)
66 x W x 90mm
180 mm
10 modules
Weight
0,65 kg
Box
Plastic, polycarbonate, colour grey
CE
In accordance with the EMC
guideline and low voltage
Application program
Communications
objects
Number of addresses(max)
Number of
assignments(max)
254
255
255
Type of protection
IP 20
EN 60 529
Safety class
II
EN 61 140
Power supply :
- Voltage
21V… 30V DC, SELV
- Current consumption
≤ 10 mA
External supply
-
-
Connections
- Screw terminals
- Max tightening torque
0,5…4 mm² solid and stranded wire
0,5…2,5mm² stranded wire with ferrule
0.8 Nm
- KNX
Bus connect terminal

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 5 / 80
Output
- Number
20 output
- Switching voltage
250 AC; 50/60 Hz
- Switching capacity 250 V AC
16A / AC 1
- Maximum switching power
4000 VA
- Mechanical life
> 1 x 106
Type of contact
- Potential-free, bistable
Input
- Number
18 binary inputs
- Scanning voltage
32 V pulsed
- Current
0.1mA
- Cable length
< 300 m
Installation
- 35mm mounting rail
EN 60 715
Operating elements
- LED (red) and button
For physical address
Temperature range
- Ambient
-5° C + 45° C
- Storage
-25° C + 55° C
Humidity
- max. air humidity
85 % no moisture condensation
Dimensions
Width W in mm
Width W in units (18 mm modules)
66 x W x 90mm
180 mm
10 modules
Weight
0,65 kg
Box
Plastic, polycarbonate, colour grey
CE
In accordance with the EMC
guideline and low voltage
Application program
Communications
objects
Number of addresses(max)
Number of
assignments(max)
254
255
255
NOTE: Device factory default physical address is “15.15.255”.

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 6 / 80
1.3 Connection Example
RCU2018
Connection Example 1
Connection Example 2

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 7 / 80
RCU0808
Connection Example 3
Connection Example 4

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 8 / 80
RCU1212
Connection Diagram 5
Connection Diagram 6

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 9 / 80
RCU1616
Connection Diagram 7
Connection Diagram 8

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 10 / 80
1.3 Scale Drawings RCUXXYY
RCU2018
RCU1616

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 11 / 80
RCU1212
RCU0808

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 12 / 80
Scale Dimensions RCUXXYY

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 13 / 80
2Communication Object Table
The device has 254 communication objects. Overview of all communication objects of the device can
be seen on the following table. Object names will be changed according to channel function as
follows.
Fan coil: Fan A/B1, Fan C/D1, Fan E/F1, Fan G/H1, Fan I/J1 etc.
Valve control: Valve A/B, Valve C/D, Valve E/F, Valve G/H, Valve I/J.
Shutter/Blind DC: Output A/B, Output C/D, Output E/F, Output G/H, Output I/J.
Shutter/Blind AC: Output A, Output B, Output C, Output D, Output E.
Switch: Output A1, Output A2, Output B1, Output B2, Output C1, Output C2 etc.
No
Name
Function
DTP Type
Length
Flags
0
General
In operation
1.002
1 bit
CWT
1
General
Scene 8-bit
18.001
1 byte
CW
2
Blind
Wind alarm
1.005
1 bit
CWTU
3
Blind
Rain alarm
1.005
1 bit
CWTU
4
Blind
Frost alarm
1.005
1 bit
CWTU
5
Input a
Disable
1.003
1 bit
CW
6
Input a
Switch
1.001
1 bit
CWT
Switch –short
1.001
1 bit
CWT
Shutter Up/Down
1.008
1 bit
CT
Value (0,1)
1.001
1 bit
CWT
Value (forced)
2.001
2 bit
CWT
Value [0...255]
5.001
8 bit
CWT
Value [0...65535]
8.001
16 bit
CWT
Value [-32768...32767]
7.001
16 bit
CWT
Value [0...4294967295]
12.001
32 bit
CWT
7
Input a
Switch –long
1.001
1 bit
CWT
Dimming brighter / darker
3.007
4 bit
CT
Shutter stop / lamella
1.007
1 bit
CT
Value (0,1) - long
1.001
1 bit
CT
Value (forced) - long
2.001
1 bit
CT
Value [0...255] - long
5.001
8 bit
CT
Value [0...65535] - long
8.001
16 bit
CT
Value [-32768...32767]
7.001
16 bit
CT
Value [0...4294967295]
12.001
32 bit
CT
8
Input a
Shutter upper limit position
1.002
1 bit
CW
Value (temperature)
14.068
32 bit
CT
9
Input a
Shutter lower limit position
1.002
1 bit
CW
Value (temperature) - long
14.068
32 bit
CT
10…94
Input b … s
Same as “Input a”
95
Output A1
Switch
1.001
1 bit
CW
Output A
Output A/B
Move blind/shutters up-down
1.008
1 bit
CW
Fan A/B1
Fan speed switch
5.010
1 byte
CW
Control input
Control value HEATING
5.001
1 byte
CW

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 14 / 80
96
Output A1
Status Switch
1.001
1 bit
CW
Output A
Output A/B
Slat adjustment/stop up-down
1.007
1 bit
CW
Fan A/B1
Switch speed 1
1.001
1 bit
CW
Control input
Control value COOLING
5.001
1 byte
CW
97
Output A1
Enable staircase function
1.003
1 bit
CRW
Output A
Output A/B
Blind/shutters up-down limited
1.008
1 bit
CW
Enable limitation
1.003
1 bit
CW
Fan A/B1
Switch speed 2
1.001
1 bit
CW
Control input
Toggle Heating/Cooling
1.100
1 bit
CW
98
Output A1
Staircase lighting duration
7.007
2 byte
CRW
Output A
Output A/B
Move to position height 0…255
5.001
1 byte
CW
Fan A/B1
Switch speed 3
1.001
1 bit
CW
Control input
Fault control value
1.005
1 bit
CRT
99
Output A1
Permanent ON
1.001
1 bit
CW
Output A/B
Move slats 0…255
5.001
1 byte
CW
Fan A/B1
Fan speed UP/DOWN
1.007
1 bit
CW
Valve HEATING
Block
1.003
1 bit
CW
100
Output A1
External logic input
1.001
1 bit
CW
Output A
Output A/B
Move to position 1, 2
1.022
1 bit
CW
Fan A/B1
Status fan ON/OFF
1.001
1 bit
CT
Valve HEATING
Forced operation
1.003
1 bit
CW
101
Output A1
Forced positioning
2.001
2 bit
CW
Output A
Output A/B
Move to position 3, 4
1.022
1 bit
CW
Fan A/B1
Status fan speed
5.010
1 byte
CRT
Valve HEATING
Trigger valve purge
1.017
1 bit
CW
102
Output A1
Sweep
1.017
1 bit
CW
Output A
Output A/B
Set position 1, 2
1.022
1 bit
CW
Fan A/B1
Status fan speed 1
1.001
1 bit
CRT
Valve HEATING
Status valve purge
1.003
1 bit
CRT
103
Output A2
Switch
1.001
1 bit
CW
Output A
Output A/B
Set position 3, 4
1.022
1 bit
CW
Fan A/B1
Status fan speed 2
1.001
1 bit
CRT
Valve HEATING
Status valve position
1.001
1 bit
CRT
Status valve position
5.001
1 byte
CRT
104
Output A2
Status Switch
1.001
1 bit
CW
Output A
Output A/B
Trigger reference movement
1.008
1 bit
CW
Fan A/B1
Status fan speed 3
1.001
1 bit
CRT
Valve COOLING
Block
1.003
1 bit
CW
105
Output A2
Enable staircase function
1.003
1 bit
CRW
Output A
Output A/B
Block
1.003
1 bit
CWTU
Fan A/B1
Forced operation
1.003
1 bit
CW
Valve COOLING
Forced operation
1.003
1 bit
CW
106
Output A2
Staircase lighting duration
7.007
2 byte
CRW
Output A
Forced operation 1 bit
1.003
1 bit
CWTU

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 15 / 80
Output A/B
Forced operation 2 bit
2.002
2 bit
CW
Fan A/B1
Automatic ON/OFF
1.003
1 bit
CW
Valve COOLING
Trigger valve purge
1.017
1 bit
CW
107
Output A2
Permanent ON
1.001
1 bit
CW
Output A
Output A/B
Status height 0…255
5.001
1 byte
CRT
Fan A/B1
Status automatic
1.003
1 bit
CW
Valve COOLING
Status valve purge
1.003
1 bit
CRT
108
Output A2
External logic input
1.001
1 bit
CW
Output A
Output A/B
Status slat 0…255
5.001
1 byte
CRT
Valve COOLING
Status valve position
1.001
1 bit
CRT
Status valve position
5.001
1 byte
CRT
109
Output A2
Forced positioning
2.001
2 bit
CW
Output A
Output A/B
Status upper end position
1.011
1 bit
CRT
110
Output A2
Sweep
1.017
1 bit
CW
Output A
Output A/B
Status lower end position
1.011
1 bit
CRT
111…254
Output B1…U2
Output C/D…
Output T/U
Same as “Output A1” for switch
Same as “Output A/B” for blind
3Parameters
3.1 General
Enable manual operation
disable
*enable

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 16 / 80
This parameter can be used to enable/disable manual control. If manual operation is enabled,
connected load can be controlled via the corresponding channel button on the device.
▪Set the parameter to “enable”
This selection is used to enable manual operation.
▪Set the parameter to “disable”
This selection is used to disable manual operation.
Reset manual operation to KNX operation
*via push button
automatically and via push button
This parameter determines how long manual operation remains activated.
Time for automatic reset
in s[10…6000]
10…*300…6000
Manual operation remains activated until the adjusted time is up or deactivated by button manually.
Device alive operation active
*no
yes
This object is used to report that device is still alive and connected to KNX line. (Heartbeat) If alive
telegram is not received, device may be defective or KNX cable can be disconnected. If parameter is
selected "yes", following parameters come up.
In operation bit
0
*1
Telegram value can be selected as “1” or “0”.
In operation send interval
1…*300…65535
Telegram value is sent cyclically according to time interval.
Transmission delay [2…255s] after bus
voltage return
*2…255
The parameter defines the behaviour of the actuator at a bus power return. The transmission delay
time determines the period between bus voltage recovery and the point after which telegrams can
be sent.
Telegram limit active
*no
yes
Telegrams which are sent by the gateway can be limited with this parameter. If “yes” is selected,
following parameters come up.
Telegram limit period
50ms…*10s…1dk
The limit period can be selected via telegram limit period parameter.
Max. number of transmitted telegram
1…*20…255
Maximum number of telegrams can be sent freely within a period.
NOTE: If the value of the object cannot be sent in the time of a period. The object is buffered for the
next period time. The buffered object will be updated if the object value is updated.

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 17 / 80
Activate scene
*no
yes
If parameter is selected “yes”, “Scenes” section will be visible in parameter titles.
Weather alarm function
enable
*disable
If the parameter is selected “yes”, “Weather Alarm”section will be visible in parameter titles. You
can find weather alarm information under the “Weather Alarm” section.
3.2 Weather alarms
Order of priority for weather alarms
*1.Wind 2.Rain 3.Frost
1.Wind 2.Frost 3.Rain
1.Rain 2.Wind 3.Frost
1.Rain 2.Frost 3.Wind
1.Frost 2.Wind 3.Rain
1.Frost 2.Rain 3.Wind
If an alarm is triggered, the drives move into a safe position and stay in safe position until the event is
over. You can select the priority of the weather alarm. This parameter is applied for all blind/shutter
channels which are enabled for weather protection function. If more than one weather alarms occur
simultaneously, then only the alarm with highest priority will be activated. The other lower priority
alarms are carried out after highest priority alarm is completed.
Wind alarm
*disable
enable
This parameter activates the wind alarm. If the parameter selected “enable”, “Monitoring period for
wind alarm in s [0…1000]” parameter will be visible.

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 18 / 80
Monitoring period for wind alarm in s
[0…1000]
*0…1000
The telegram of the active weather station is monitored cyclically. The actuator waits for a telegram
from the weather station within the cycle time. If the telegram is not received within this monitoring
period time, actuator assumes that the weather station is broken or bus line is damaged and the
blind moves into the parameterized position.
▪0: If “0” is selected cyclically monitoring is deactivated. If the alarm telegram value is “1”,
weather alarm is activated.
Rain alarm
*disable
enable
This parameter activates the rain alarm. If the parameter selected “enable”, “Monitoring period for
rain alarm in s [0…1000]” parameter is visible.
Monitoring period for rain alarm in s
[0…1000]
*0…1000
The telegram of the active weather station is monitored cyclically. The actuator waits for a telegram
from the weather station within the cycle time. If the telegram is not received within this monitoring
period time, actuator assumes that the weather station is broken or bus line is damaged and the
blind moves into the parameterized position.
▪0: If “0” is selected cyclically monitoring is deactivated. If the alarm telegram value is “1”,
weather alarm is activated.
Frost alarm
*disable
enable
This parameter activates the frost alarm. If the parameter selected “enable”, “Monitoring period for
frost alarm in s [0…1000]” parameter is visible.
Monitoring period for frost alarm in s
[0…1000]
*0…1000
The telegram of the active weather station is monitored cyclically. The actuator waits for a telegram
from the weather station within the cycle time. If the telegram is not received within this monitoring
period time, actuator assumes that the weather station is broken or bus line is damaged and the
blind moves into the parameterized position.
40: If “0” is selected cyclically monitoring is deactivated. If the alarm telegram value is “1”,
weather alarm is activated.
4.1 Scene
The scene function of the switch actuator has an 8 bit scene object. You can define for each 64 scene
with parameter window. 8 independent values can be stored for each relay or each blind. The scene
can be specified that the relay OFF (open contact), or ON (close contact) its state for switch function.
If you use the blind, you can configure the blind height and slat position. You can save height position
for blind also slat-opening angle as scene values.

Product Manual RCUXXYY
EAE KNX Room Control Unit RCUXXYY PM R1.0
©EAE Technology www.eaetechnology.com Page 19 / 80
When the actuator receives a telegram that retrieves a scene address;
i. The output group is configured as a blind, the drive is moved into the saved position and slats
are turned.
ii. The output group is configured as a switch, the actuator evaluate the transmitted scene
address and switches the output to the stored scene value.
A scene is activated when it receives its scene number at the scene object. The storing of the current
channel values is carried out using the scene object.
For example;
Scene
recall
save
Hex.
Des.
Hex.
Des.
1
0x00
0
0x80
128
2
0x01
1
0x81
129
3
0x02
2
0x82
130
4
0x03
3
0x83
131
5
0x04
4
0x84
132
6
0x05
5
0x85
133
7
0x06
6
0x86
134
8
0x07
7
0x87
135
9
0x08
8
0x88
136
10
0x09
9
0x89
137
11
0x0A
10
0x8A
138
…
…
…
…
…
63
0x3E
62
0xE2
190
64
0x3F
63
0xE3
191
Overwrite scene on download
no
*yes
This parameter is selected the reaction of the scene set.
▪Set the parameter to “no”;
During storage of a scene, the scene values are stored in the device. If you want to protect
your scene in the device, you are selected “no”.
▪Set the parameter to “yes”;
The original ETS parameter values can be reload into the device during ETS download
operation.
1…64 scene number (0 = no assignment)
*0…64
This parameter is used to following parameter belongs to which scene. 0 meaning following
parameters are not belong to any scene.
Blind position value
in %[100]
*0…100
Slat position value
*0…100
This manual suits for next models
6
Table of contents
Popular Control Unit manuals by other brands

PMFoundations
PMFoundations Dual VCA Assembly guide

Burkert
Burkert 5470 operating instructions

Sparkfun Electronics
Sparkfun Electronics AD8232 HOOK-UP GUIDE

CALEFFI
CALEFFI 146 Series Installation and commissioning manual

schmersal
schmersal AES 9107 operating instructions

Bola
Bola E 683-18 operating instructions

Lenze
Lenze ECSDS Series Mounting instructions

Blonder tongue
Blonder tongue HDE-8C DIN SERIES user manual

Graco
Graco PrecisionFlo 233678 Instructions-parts list

VideoSys
VideoSys IDU-E user manual

Scott Edwards Electronics
Scott Edwards Electronics BPP-420 user manual

Hoft & Wessel
Hoft & Wessel HW 86010 Integration manual