EAE DA110 User manual

Order Number: 48107
EAE KNX DALI Gateway
Product Manual DA110

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 1 / 21
Contents
1. General ................................................................................................................................................ 2
1.1. Device Description........................................................................................................................ 2
1.2. Technical Data .............................................................................................................................. 3
1.3. Connection Example..................................................................................................................... 4
1.4. Operation and Display.................................................................................................................. 4
2. Communication Object Information ................................................................................................... 5
2.1. Communication Object Table....................................................................................................... 5
2.2. Communication Object Descriptions............................................................................................ 6
3. Parameters ........................................................................................................................................ 15
3.1. General ....................................................................................................................................... 15
3.2. Feedback..................................................................................................................................... 17
3.3. Fault Conditions.......................................................................................................................... 19
3.4. DALI Devices (1…64)................................................................................................................... 20
3.4.1. Device 1…64 ........................................................................................................................ 20
3.5. Scenes......................................................................................................................................... 21
3.5.1. Scene 1…16.......................................................................................................................... 21

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 2 / 21
1. General
1.1. Device Description
DA110 KNX-DALI Gateway operates as an interface device between KNX bus and DALI bus. Device can
control 64 DALI devices on a DALI line. This DALI line is powered by internal power supply. DALI
compatible ECGs (electronic control gear) can be controlled individually.
Device features are listed below;
Maximum 64 DALI devices (e.g. electronic ballast, transformer) can be connected to DALI output.
DA110 enables to control 64 DALI devices individually and can store 16 different lighting scenes.
Fault statuses of DALI devices can be monitored by both device based via different communication
objects on the KNX.
Bus voltage fail/return states can be selected on ETS parameters.
Addressing of DALI devices is made via EAE DALI Tool (PC Software). DALI Tool can be downloaded
from website. www.eaetechnology.com.
NOTE: Each channel is uniform. Device factory default physical address is “15.15.255”.

Product Manual DA110
EAE KNX DALI Gateway DA110 R3.0
©EAE Technology www.eaetechnology.com Page 3 / 21
1.2. Technical Data
Type of protection
IP 20
EN 60529
Safety class
II
EN 61140
KNX supply(4)
Voltage
Current consumption
21 - 30V DC, SELV
< 10mA
Mains supply(6)
Voltage
Power consumption
Current consumption
85 - 300V AC @ 50-60Hz
Max. 8W
100mA @ 85V AC
DALI supply(5)
Voltage
Current
16V DC typical
Max. 120mA
Connections
Screw terminals
Max tightening torque
KNX terminal
0,05 - 2,5mm² solid wire
0,03 - 1,5mm² stranded wire
0.5Nm
Red - grey bus connect terminal
Output
Number of DALI devices
Cable lengths
Max. 64
1.5 mm2
Max. 300 m
0.75 mm2
Max. 150 m
0.5 mm2
Max. 100 m
Installation
35mm mounting rail
EN 60715
Operating elements
Programming LED and button
Green LED
Yellow LED
Red LED
Manual button
Test button
Physical address localization
Power OK
Initialization active (fast blink)
A DALI device fault present (slow blink)
DALI line power failure (constant on)
No Mains connection (constant on)
Manual operation active
Activate the manual control over test button
Switch-dim DALI output (when Manual Mode is active)
Temperature range
Ambient
Storage
-5°C +45°C
-25°C +55°C
Humidity
Max. air humidity
95% no moisture condensation
Dimensions
Width W in mm
Width W in units
70 x W x 91mm
69mm
4 modules (18mm modules)
Box
Plastic, polycarbonate, colour grey
CE
In accordance with the EMC guideline and low voltage directives.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 4 / 21
1.3. Connection Example
Connection Example of DA110
1.4. Operation and Display
Power OK LED (7):
OFF : KNX bus failure.
ON : KNX bus connected.
DALI Status LED (8):
OFF : No problem.
ON : DALI line failure. Possible causes; mains supply failure, DALI line is short-circuit, mains
power is connected to DALI line.
Slow Blink : A DALI device fault is present. (Lamp fault, ballast fault …)
Fast Blink : Initialization is active.
Manual LED (9) :Lights up when manual control is activated by pressing manual button.
Manual Button (10):Activate/Deactivate manual control. (Press the manual button for 3 seconds to
activate. Press shortly to deactivate manual control.)
Note: KNX commands cannot operated when manual control is activated.
Test Button (11) :If manual operation is activated, short press sends broadcast on/off command and
long press sends broadcast dim up/down command to DALI line. (Commands are sent in sequent.)
Programming LED and Button (3):Physical address localization.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 5 / 21
2. Communication Object Information
2.1. Communication Object Table
Overview of all communication objects of the device application can be seen on the following table.
No Function Name DPT Length Flags
0
In operation
General
1.002
1 Bit
CT
1
Enable manual operation
General
1.003
1 Bit
CRW
2
New devices addressing
General
1.003
1 Bit
CW
3
Field capture
General
1.003
1 Bit
CW
4
Request all statuses
General
1.003
1 Bit
CW
5
Device status
Feedback
Non-DPT
3 Bytes
CWT
6
Coded status switch
Feedback
Non-DPT
2 Bytes
CWT
7
Coded status brightness value
Feedback
Non-DPT
2 Bytes
CWT
8
Coded faults
Feedback
237.600
2 Bytes
CWT
9
DALI line fault
Feedback
1.005
1 Bit
CRT
10
Mains connection fault
Feedback
1.005
1 Bit
CRT
11
Lamp fault
Feedback
1.005
1 Bit
CRT
12
Device fault
Feedback
1.005
1 Bit
CRT
13
Mains power failure status
Feedback
1.005
1 Bit
CRT
14
Scene 8-bit
Scene
17.001
1 Byte
CW
15
0=Scene 1, 1=Scene 2
Scene
1.022
1 Bit
CW
16
0=Scene 3, 1=Scene 4
Scene
1.022
1 Bit
CW
17
0=Scene 5, 1=Scene 6
Scene
1.022
1 Bit
CW
18
0=Scene 7, 1=Scene 8
Scene
1.022
1 Bit
CW
19
0=Scene 9, 1=Scene 10
Scene
1.022
1 Bit
CW
20
0=Scene 11, 1=Scene 12
Scene
1.022
1 Bit
CW
21
0=Scene 13, 1=Scene 14
Scene
1.022
1 Bit
CW
22
0=Scene 15, 1=Scene 16
Scene
1.022
1 Bit
CW
23
Broadcast Switch
Broadcast
1.001
1 Bit
CWU
24
Broadcast Set brightness value
Broadcast
5.001
1 Byte
CWU
25
Broadcast Relative dimming
Broadcast
3.007
4 Bit
CW
26…215
Switch
Dali Device 1…64 1.001 1 Bit
CWU
Switch/Status
CWTU
Switch/Status
CRWU
Switch/Status
CRWTU
27…216
Set brightness value
Dali Device 1…64 5.001 1 Byte
CWU
Set brightness value/Status
CWTU
Set brightness value/Status
CRWU
Set brightness value/Status
CRWTU
28…217
Relative dimming
Dali Device 1…64
3.007
4 Bit
CW

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 6 / 21
2.2. Communication Object Descriptions
No
Function
Name
DPT
Length
Flags
0
In operation
General
1.002
1 bit
CT
This object is used to report that device is still alive and connected to the KNX line by sending cyclic 1 bit
telegrams. If a telegram is not received, device may be defective or KNX cable would be intercepted.
-Object will be activated if “Device alive operation active” parameter in the General tab is selected as
“enable”.
-Telegram type (ON or OFF) can be selected via “In operation bit” parameter in General parameters tab.
-Cyclic period of transmitted telegrams can be selected via “In operation send interval” parameter in General
parameters tab.
1
Enable manual operation
General
1.003
1 bit
CRW
This object is used for enabling or disabling the manual operation button located on the device. If the manual
operation disabled, manually switching or dimming of the connected DALI devices is not possible.
Furthermore, the status of manual operation can be read via this communication object.
-Value of the object will be “1” after an ETS download if the "Enable manual operation" parameter in General
tab is selected as 'enable'. Value will be “0” if parameter is selected as “no”.
(value “1” = manual operation enable, value “0” = manual operation disable)
2
New devices addressing
General
1.010
1 bit
CW
This object is used to start adressing the all DALI devices randomly. If there is even addressed devices before,
they will be re-addressed again. Please send “enable(1)” to this group object to start this function.
3
Field capture
General
1.010
1 bit
CW
This object is used to read and save all DALI devices to DA110 device which can be found by scan. Un-
addressed devices will be addressed and conflicted addresses will be resolved. Please send “enable(1)” to this
group object to start this function.
NOTE: If statuses are wrong or zero please perform this operation.
4
Request all statues
General
1.010
1 bit
CW
This object is used to read all status by triggering this object when needed. Status information will be sent via
Coded objects (if activated) and via Switch/Status or Set brightness value/Status object(if activated). Please
send “enable(1)” to this group object to start this function.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 7 / 21
No
Function
Name
DPT
Length
Flags
5
Device status
Feedback
Non-DPT
3 bytes
CWT
This communication object is used for getting all current faults and states of a DALI device in one
comprehensive telegram. In order to make a read request, a write should be made
to object with
read/response bit is set.
Object consists of three bytes. Higher two bytes of telegram contains all fault and state data and lowest byte
contains DALI address of subjected device and information of whether telegram is a status request or sent
status.
-Object will be activated if “Enable “Device status” object” parameter in Feedback tab is selected as “enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
Bit numbers and data which they represented is explained below;
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte
Bit Field
Description
1
Bit 0 - 5
DALI device address [0 - 63]
Bit 6
Reserved and should be '0'
Bit 7
Read or response flag: '1' = read, '0' = response
2
Bit 8
Device offline flag: '1' = offline, '0' = online
Bit 9
Device malfunction flag: '1' = failure '0' = no failure
Bit 10
Lamp failure flag: '1' = failure, '0' = no failure
Bit 11
Reserved and should be '0'
Bit 12
Reserved and should be '0'
Bit 13
Reserved and should be '0'
Bit 14
Reserved and should be '0'
Bit 15
Reserved and should be '0'
3
Bit 16
Reserved and should be '0'
Bit 17
Reserved and should be '0'
Bit 18
Reserved and should be '0'
Bit 19
Short circuit flag: '1' = failure, '0' = no failure (LED only)
Bit 20
Open circuit flag: '1' = failure, '0' = no failure (LED only)
Bit 21
Current protector active flag: '1' = failure, '0' = no failure (LED only)
Bit 22
Thermal shutdown flag: '1' = failure, '0' = no failure (LED only)
Bit 23
Reserved

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 8 / 21
No
Function
Name
DPT
Length
Flags
6
Coded status switch
Feedback
Non-DPT
2 byte
CWT
This object is used to get switch status of a DALI group or an individual DALI ballast/driver. In order to make a
read request, a write should be made to object with read/response bit is set.
Object consists of two bytes. High byte of telegram contains switch status and low byte contains DALI address
of subjected device or group number, information of whether telegram is a status request or sent status and
information of whether a device or a group is selected.
-Object will be activated if “Enable “Coded status switch” object” parameter in Feedback tab is selected as
“enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
Bit numbers and data which they represented is explained below;
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte
Bit Field
Description
1
Bit 0 - 5
DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6
Individual device or group flag: '1' = device address, '0' = group number
Bit 7
Read or response flag: '1' = read, '0' = response
2
Bit 8
Switch status: '1' = ON, '0' = OFF (DPT 1.001)
Bit 9 - 15
Reserved

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 9 / 21
No
Function
Name
DPT
Length
Flags
7
Coded status brightness value
Feedback
Non-DPT
2 byte
CWT
This object is used to get brightness value of a DALI group or an individual DALI ballast/driver. In order to make
a read request, a write should be made to object with read/response bit is set.
Object consists of two bytes. High byte of telegram contains brightness value and low byte contains DALI
address of subjected device or group number, information of whether telegram is a status request or sent
status and information of whether a device or a group is selected.
-Object will be activated if “Enable “Coded status brightness value” object” parameter in Feedback tab is
selected as “enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
Bit numbers and data which they represented is explained below;
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte
Bit Field
Description
1
Bit 0 - 5
DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6
Individual device or group flag: '0' = device address, '1' = group number
Bit 7
Read or response flag: '1' = read, '0' = response
2
Bit 8 - 15
Brightness value [0 - 255] (DPT 5.001)

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 10 / 21
No
Function
Name
DPT
Length
Flags
8 Coded faults Feedback 237.600 2 byte CWT
This object is used to get fault data of a DALI group or an individual DALI device. In order to make a read
request, a write should be made to object with read/response bit is set.
Object consists of two bytes. High byte of telegram contains fault data and low byte contains DALI address of
subjected device or group number, information of whether telegram is a status request or sent status and
information of whether a device or a group is selected.
-Object will be activated if “Enable “Coded faults” object” parameter in Feedback tab is selected as “enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
Bit numbers and data which they represented is explained below;
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte
Bit Field
Description
1
Bit 0 - 5
DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6
Individual device or group flag: '1' = device address, '0' = group number
Bit 7
Read or response flag: '1' = read, '0' = response
2
Bit 8
Device is offline or malfunction flag: '1' = failure '0' = no failure
Bit 9
Lamp failure flag: '1' = failure '0' = no failure
Bit 10
Reserved
Bit 11 - 15
Reserved

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 11 / 21
No
Function
Name
DPT
Length
Flags
9
DALI line fault
Feedback
1.005
1 bit
CRT
This object is used for reporting DALI gateway supply fault. Possible causes of the fault are no mains
connection to gateway supply terminal, power supply malfunction or short circuiting DALI line more than
100ms.
-Object will be activated if “Enable “Fault gateway supply” object” parameter in Feedback tab is selected as
“enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = gateway supply works properly, value “1” = gateway supply fault)
10
Mains connection fault
Feedback
1.005
1 bit
CRT
This object is used for reporting DALI gateway mains connection fault. Possible causes of the fault are no mains
connection to gateway supply terminal.
-Object will be activated if “Enable “Mains connection fault” object” parameter in Feedback tab is selected
as “enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = gateway supply works properly, value “1” = Mains connection fault)
11
Lamp fault
Feedback
1.005
1 bit
CRT
This object is used for reporting whether there is any device that has a fault lamp is present or not.
-Object will be activated if “Enable “Lamp fault” object” parameter in Feedback tab is selected as “enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = no fault lamp, value “1” = at least one of the DALI devices has a lamp fault)
12
Device fault
Feedback
1.005
1 bit
CRT
This object is used for reporting whether there is any offline or malfunctioned ballast/driver is present or not.
-Object will be activated if “Enable “Device fault” object” parameter in Feedback tab is selected as “enable”.
-Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = no ballast/driver fault, value “1” = at least one of the DALI ballasts/drivers is offline or
malfunctions)

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 12 / 21
No
Function
Name
DPT
Length
Flags
13
Mains power failure status
Feedback
1.005
1 bit
CRT
This object is used for reporting a misconnection of mains to the DALI line.
-Object will be activated if “Enable “Fault mains connected” object” parameter in Feedback tab is selected
as “enable”.
-Feedback will be sent only after a request if "transmit mode" parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
(value “0” = no misconnection, value “1” = mains connected to DALI line)
NOTE:
Overvoltage sense circuitry on the DALI line is triggered on voltages above 40V. So any voltage
above 40V is considered as mains.
14
Scene 8 bit
Scene
17.001
1 byte
CW
This object is used to recall up to 16 scenes that are available on the gateway device.
-Object is always enabled.
-Even devices which is not shown on ETS parameters can be controlled via scenes properly.
NOTE: Scene save function is not available.
Bit numbers and data which they represented is explained below;
7
6
5
4
3
2
1
0
Byte
Bit Field
Description
1
Bit 0 - 3
Scene number - 1 [0 – 15 for scenes 1 - 16]
Bit 4 - 7
Reserved and should be 0
Example of recall byte codes for scenes;
Scene
Recall
Scene
Recall
Hexadecimal
Decimal
Hexadecimal
Decimal
1
0x00
0
9
0x08
8
2
0x01
1
10
0x09
9
3
0x02
2
11
0x0A
10
4
0x03
3
12
0x0B
11
5
0x04
4
13
0x0C
12
6
0x05
5
14
0x0D
13
7
0x06
6
15
0x0E
14
8
0x07
7
16
0x0F
15

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 13 / 21
No
Function
Name
DPT
Length
Flags
15
0=Scene 1, 1=Scene 2
Scene
1.022
1 bit
CW
This object is used for recalling scene 1 or scene 2.
(value “0” = recall scene 1, value “1” = recall scene 2
16…22
0=Scene 3…15, 1=Scene 4…16 same as before
23
Broadcast Switch
Broadcast
1.001
1 bit
CWU
This object is used to switch all connected DALI ballasts on or off. You can configure broadcast switched on
brightness value, using “Brightness value when switch on” parameter.
24
Broadcast Set brightness value
Broadcast
5.001
1 byte
CWU
This object is used to set the brightness value of all connected DALI ballasts.
25
Broadcast Relative dimming
Broadcast
3.007
4 bit
CW
This object is used to dim all connected DALI ballast. The brightness value is changed in the defined direction
with the parameterized speed.
C
Increase or decrease the brightness
0 = Decrease
1 = Increase
Step-Code
The amount of intervals into which the
range of 0 % … 100 % is subdivided or the
break indication.
- 001b…111b: Step
Number of interval = (2)(−1)
- 000b : Break
GENERAL NOTE(Broadcast Control):
Broadcast control objects are not dependent to Individual control group objects. Thus, individually controlled
device statuses will not be taking into account for Broadcast control group objects.
If Broadcast Relative Dim group object is willing to used, Broadcast Switch or Broadcast Absolute Dim control
is required.
If Broadcast control applied firstly, status values will be taking into account for individual control group
objects.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 14 / 21
No
Function
Name
DPT
Length
Flags
41
Switch
Dali Device 1…64 1.001 1 bit
CWU
Switch/Status (after change)
CWTU
Switch/Status (after request)
CRWU
Switch/Status (after change or request)
CRWTU
This object is used to switch DALI device 1…64 ON or OFF.
44
Group 1, Brightness value
Dali Device 1…64 5.001 1 byte
CWU
Set brightness value/Status (after change)
CWTU
Set brightness value/Status (after request)
CRWU
Set brightness value/Status (after change or request)
CRWTU
This object is used to set DALI Device 1…64 brightness value (%0…%100).
46
Group 1, Relative dimming
Dali Device 1…64
3.007
4 bit
CW
This object is used to dimming group 1. The brightness value is changed in the defined direction with the
parameterized speed.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 15 / 21
3. Parameters
“Parameters” chapter describes ETS parameters of the device. Please find detailed descriptions of
objects in 2.2 Communication Object Descriptions. Default parameters are written in bold letters.
3.1. General
Enable manual Operation
*enable
no
Parameter determines whether lightings can be controlled manually or not by push button on DALI Gateway.
If parameter is selected “enable”; manual operation will be possible. (For manual control: Hold down manual
button for 3 seconds than press test button consecutively.)
Device alive beacon
enable
*disable
This object is used to report that device is still alive and connected to KNX line. (Heartbeat) If alive telegram
is not received, device may be defective or KNX cable can be disconnected. If parameter is selected “enable”,
following parameters come up.
In operation value
*true
false
Telegram value can be selected as “1” or “0”.
Operation send interval [sec] 1…*300…65535
Telegram value is sent cyclically according to time interval.
Telegram limit function
enable
*disable
Telegrams which are sent by the gateway can be limited with this parameter. If “enable” is selected, following
parameters come up.
Telegram limit period 50ms…*100ms…1min
The limit period can be selected via telegram limit period parameter.
Max. number of transmitted telegrams
within a period
*1…255
Maximum number of telegrams can be sent freely within a period.
Minimum brightness value limit
*no limit, %5(13)…%90(230)
This parameter defines the minimum brightness value of DALI devices. All DALI devices take this value as
undermost brightness value and cannot accept lower brightness values.
Maximum brightness value limit
*no limit, %95(242)…%10(26)
This parameter defines the maximum brightness value of DALI devices. All DALI devices take this value as
upper limit brightness value and cannot accept higher values.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 16 / 21
Allow switch on via brightness value
*yes
no
Allow switch off via brightness value
*yes
no
Allow switch on via relative dimming
*yes
no
Allow switch off via relative dimming
*yes
no
“Switch on” and “Switch off” conditions can be defined for brightness value and relative dimming commands
separately. If these parameters are selected “no”, then it is not possible to switch “on” or “off” the lighting
fixtures via brightness value (1 byte) or relative dimming (4 bit) objects of the group.
Fade time
(switch, brightness value and dim commands)
jump to…1 s…90 s
These parameter defines the fade time for switch, brightness value and relative dimming commands per
device.
Brightness value when switch on
Last switch on value, 5% (13) …*100% (255)
This parameter defines the brightness value when a “switch on” command is received over Switch
communication object.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 17 / 21
3.2. Feedback
Enable “DALI line fault” object
enable
*disable
Parameter enables “Fault gateway supply” object. This object is used for reporting DALI gateway supply fault.
Possible causes of the fault are no mains connection to gateway supply terminal, power supply malfunction
or short circuiting DALI line more than 100ms. Please check 2.2 Communication Object Descriptions for
detailed object information.
Enable “Mains connection fault” object
enable
*disable
Parameter enables “Fault mains connected” object. This object is used for reporting a misconnection of mains
to the DALI line.
Enable “Lamp fault” object
enable
*disable
Parameter enables “Fault lamp” object. This object is used for reporting whether there is any device that has
a fault lamp is present or not.
Enable “Device fault” object
enable
*disable
Parameter enables “Fault ballast” object. This object is used for reporting whether there is any offline or
malfunctioned ballast/driver is present or not.
Enable “Device status” object
enable
*disable
Parameter enables “Device status” object. This communication object is used for getting all current faults and
states of a DALI device in one comprehensive telegram.
Enable “Coded status switch” object
enable
*disable
Parameter enables “Coded status switch” object. This object is used to get switch status of a DALI group or an
individual DALI ballast/driver.
Enable “Coded status brightness value” object
enable
*disable
Parameter enables “Coded status brightness” object. This object is used to get brightness value of a DALI
group or an individual DALI ballast/driver.
Enable “Coded faults” object
enable
*disable
Parameter enables “Coded faults” object. This object is used to get fault data of a DALI group or an individual
DALI device.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 18 / 21
Enable “Mains power failure status” object
enable
*disable
Parameter enables “Main power failure status” object. This object is used for reporting a no mains connection
applied to the mains line of DA110 device.
Transmit mode description is the same for all parameters in Feedback tab. But selections can be made
independently for each parameter.
Transmit mode
*after request
after change
after request or change
“After request” option only response to a read request to status object. “After change” mode always sends
the status of object when changed. If both selected, object will send the status with a change and response
to read requests.

Product Manual DA110
EAE KNX DALI Gateway DA110 R2.0
©EAE Technology www.eaetechnology.com Page 19 / 21
3.3. Fault Conditions
Lamp values on power on
0 %(0)…100 %(255)
*value before power off
Parameter defines the brightness value of ballasts when power on.
Lamp values on DALI voltage failure
0 %(0)…100 %(255)
*no change
Parameter defines the brightness value of ballasts on DALI line voltage loss.
Lamp values on DALI voltage recovery
0 %(0)…100 %(255)
*no change
Parameter defines the brightness value of ballasts on DALI voltage return.
Lamp values on KNX voltage failure
0 %(0)…100 %(255)
*no change
Parameter defines the brightness value of ballasts on KNX line voltage loss.
Lamp values on KNX voltage recovery
(gateway reset)
0 %(0)…100 %(255)
*no change
Parameter defines the brightness value of ballasts on KNX voltage return.
Table of contents