manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eaton
  6. •
  7. Portable Generator
  8. •
  9. Eaton IQM3PPM User manual

Eaton IQM3PPM User manual

Three-Phase Power Module
Style IQM3PPM (66C2113) IL17568
Eective January, 2000
THE MODULE
The Three-Phase Power Module (IQM3PPM) is
designed for use with the IQA6400/IQA6600 (66d2045)
and DP4000 (66d2040) meters in three-phase
applications from 100Vac to 600Vac.
In applications using either the IQA6400/IQA6600 or the
DP4000/DP4100, supply power can be drawn directly
from the three-phase line-to-line voltage.
The IQM3PPM may also be used in certain applications
of the IQA6000/6200 (2d82302) or DP4000/DP4100
(4d13110) where the NEU terminal is grounded. These
applications include three-wire applications and
applications with potential transformers (PT’s). In either
of these acceptable retrof it applications, the NEU to
GND potential at the meter terminals is zero.
INSTALLATION
This device is designed to be installed, operated, and
maintained by adequately trained personnel. These
instructions do not cover all details, variations, or
combinations of the equipment, its storage, delivery,
installation, checkout, safe operation, or maintenance.
Care must be exercised to comply with local, state, and
national regulations, as well as safety practices, for this
class of equipment.
REMOVE ALL POWER FROM (DE-ENERGIZE) THE
DEVICE TO WHICH THE POWER MODULE IS BEING
ATTACHED OR WIRED; OTHERWISE, SERIOUS OR
FATAL PERSONAL INJURY AND EQUIPMENT
DAMAGE MAY RESULT.
REMOVING EXISTING POWER MODULE
Disconnect all power to the existing meter, including
power to any relay contacts of the device. Clearly mark
all wire connections. Then, disconnect all wires from the
existing power module. Refer to Fig. 2 and your meter’s
technical manual.
Unscrew the plug lock assembly on the ribbon cable
from the meter chassis and remove the cable from the
power module connector. Carefully remove the two
shoulder screws that secure the power module to the
chassis.
BE PREPARED TO SUPPORT THE POWER MODULE
ONCE THE SCREWS HAVE BEEN REMOVED.
MOUNTING TO IQ ANALYZER OR DP4000
Place the Three-Phase Power Module in its mounting
position on the rear of the meter chassis, in the same
position as the one removed. Replace the two shoulder
screws to secure the IQM3PPM. Reconnect all wires to
the IQM3PPM and meter - tighten all screws.
Fig. 1 Three-Phase Power Module
CAUTION
CAUTION
I.L. 17568
Effective January, 2000
Page 2
REMOTE MOUNTING OF THE IQM3PPM
In those cases where it is necessary to mount the
IQM3PPM separately from the chassis, be sure that:
(1) The location allows for a cable connection
between the meter chassis and the IQM3PPM by means
of a 45-inch extension cable (IQA45CABLE).
(2) The IQM3PPM physical dimensions are shown
in Fig. 2 below.
To mount the IQM3PPM, use the module as a drilling
template at the new location. The two #8-32 screws can
be used to remount the module in holes that are properly
drilled and tapped.
Reconnect all wires to the IQM3PPM and meter —
tighten all screws.
Fig. 2 Power Module Physical Dimensions and Mounting Holes
I.L. 17568
Effective January, 2000
Page 3
OPERATION CHECK
Verify that the NEU terminal is used. In three-wire
applications or applications with PT’s, the NEU terminal
must be tied to ground. Otherwise, wire NEU to the
power system’s neutral.
Apply ac line power to the meter. The front display of
meter should become operational within 2 seconds at
480 Vac or within 8 seconds at 120 Vac. If the device is
not powered, remove power and check the wiring
diagrams and device connections.
Restore ac line power to the meter and check readings
on the unit. If the readings do not check out, or an alarm
condition occurs, consult the instruction manual or call
Eaton Customer Support.
MAINTENANCE
This industrial type control is designed to be installed,
operated, and maintained by adequately trained
personnel. These instructions do not cover all details,
variations, or combinations of the equipment, its storage,
delivery, installation, checkout, safe operation, or
maintenance. Care must be exercised to comply with
local, state, and national regulations, as well as safety
practices, for this class of equipment.
There are no user serviceable parts on the Separate
Source Power Module. While there is a 0.25A fuse
within the module, its failure would indicate other
problems that require repair. The user should not
attempt servicing this equipment. Please contact your
local Eaton representative or Eaton Customer Support.
I.L. 17568
Page 4
Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2011 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. IL17568
December, 2011
PowerChain Management is a registered
trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.

This manual suits for next models

1

Other Eaton Portable Generator manuals

Eaton DV2-A10B Operating instructions

Eaton

Eaton DV2-A10B Operating instructions

Eaton RPM-3U User manual

Eaton

Eaton RPM-3U User manual

Eaton 8 kW Air-cooled User manual

Eaton

Eaton 8 kW Air-cooled User manual

Popular Portable Generator manuals by other brands

Powermate Coleman PMC606500 user manual

Powermate

Powermate Coleman PMC606500 user manual

Generac Portable Products 1575-0 owner's manual

Generac Portable Products

Generac Portable Products 1575-0 owner's manual

Simplicity 990220 Operator's manual

Simplicity

Simplicity 990220 Operator's manual

Rato R2200 Service manual

Rato

Rato R2200 Service manual

Nature Power 40500 user manual

Nature Power

Nature Power 40500 user manual

Domnick Hunter Maxigas Series Service guide

Domnick Hunter

Domnick Hunter Maxigas Series Service guide

Generac Power Systems 45kW owner's manual

Generac Power Systems

Generac Power Systems 45kW owner's manual

Winco 25PTOS-3 Installation and operator's manual

Winco

Winco 25PTOS-3 Installation and operator's manual

VICI DBS MISTRAL user manual

VICI DBS

VICI DBS MISTRAL user manual

SDMO Diesel 15000 TE Instruction and maintenance manual

SDMO

SDMO Diesel 15000 TE Instruction and maintenance manual

Clarke IG2000D Operation & maintenance instructions

Clarke

Clarke IG2000D Operation & maintenance instructions

Powerspot NANO manual

Powerspot

Powerspot NANO manual

Dometic TEC29 EV AUS operating manual

Dometic

Dometic TEC29 EV AUS operating manual

Champion Global Power Equipment 100891 Operator's manual

Champion Global Power Equipment

Champion Global Power Equipment 100891 Operator's manual

North Star M165601P.5 owner's manual

North Star

North Star M165601P.5 owner's manual

RIDGID RD903600 Series Operator's manual

RIDGID

RIDGID RD903600 Series Operator's manual

Leviton 83A00 installation manual

Leviton

Leviton 83A00 installation manual

MULTIQUIP Power WHISPERWATT DCA400SSI Parts and operation manual

MULTIQUIP

MULTIQUIP Power WHISPERWATT DCA400SSI Parts and operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.