EbV elektronik CETA 100 User manual

Operating manual
100
Differential temperature control
Version 1308-22
Art. 0450021014
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 1 Donnerstag, 21. Februar 2013 11:46 11

Scope of delivery ...............................................................................................................1
General ................................................................................................................................1
Intended use .....................................................................................................................1
Safety ..................................................................................................................................1
General key functions ...................................................................................................... 2
Version display (when starting) ..................................................................................... 2
Basic display ..................................................................................................................... 2
Function with direct access ............................................................................................3
Sensor resistance values ................................................................................................4
Menu level .........................................................................................................................5
Parameter description .....................................................................................................8
Mounting .......................................................................................................................... 13
Terminal diagram ........................................................................................................... 14
Fault clearance ................................................................................................................15
Declaration of conformity .............................................................................................. 16
Technical Data .................................................................................................................17
Liability ..............................................................................................................................17
Disposal ............................................................................................................................17
© Elektronikbau- und Vertriebs GmbH
Heisterner Weg 8 - 12
D-57299 Burbach
This document may not be reproduced nor disclosed to third parties, particularly competitors, in original
or copy form without our prior explicit consent. The document is subject to our proprietary rights and
copyrights.
Any misuse is an infringement of the German Copyright Law of September 9, 1965, the law against
unfair competition, and the German Civil Code.
Contents
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 2 Donnerstag, 21. Februar 2013 11:46 11

1
Scope of delivery
1. 1x Central unit CETA 100
2. 1x Tank immersion sensor KVT 20/2/6
3. 1x Collector sensor PT1000/6
4. 8x Screw, plate 2,9x19 mm
5. 3x Screw assembly 4x35 mm
6. 3x Plug U6
7. 2 x Cable clamp
General
Systems with heat source and hot water tank are controlled via the differential
temperature control. When the heat source temperature exceeds the tank
temperature by the value set on the controller, the circulation pump is activated
by the control and the heat absorbed in the heat source is transported to the hot
water tank.
Intended use
The unit is manufactured in accordance with state of the art technology and
approved safety regulations. Nevertheless, using the unit can cause danger to the
user or third persons, or damage to the unit and other assets. The unit must be
used exclusively as differential temperature controller.
Safety
All electrical connections, safety measures and protections have to be carried out
by an authorised professional electrician according to the valid standards and VDE-
guidelines, as well as the local regulations. The electrical connection must be a
fixed connection according to VDE 0100.
Hazard symbols in this operating manual
Hazard!
This symbol indicates information that warns of possible safety
risks or severe and fatal injuries!
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 1 Donnerstag, 21. Februar 2013 11:46 11

General key functions
2
1. General key functions
Prog
•Change selected submenus
•Change (parameter) setting
•Save value
+ (Plus) or - (Minus)
•Change parameter
•Change menu item
Esc
•Exit setting
•Keep old value
•Select next higher menu level
Esc-Lang
•Return to basic display
2. Version display (when starting)
3. Basic display
c 100= Type designation
2.1= Version display (due to update it can
differ from example shown)
80.5°C= Temperature heat supplier (e.g.
collector or solid fuel boiler)
44.0°C= Temperature heat storage tank
ΔT1= Display pump function
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 2 Donnerstag, 21. Februar 2013 11:46 11

3
Function with direct access
4. Function with direct access
Manual operation
— Activate by pressing and holding button
— Change pump function via buttons
and
— end function by pressing button
0...1
Controller is in manual mode
Pump function
Function: Manual operation allows manual start-up of the system, e.g. to
perform venting.
0 = The pump ΔT1 is OFF.
1 = The pump ΔT1 runs continuously.
Important!
This function shall only be used by an authorised
professional. Temperatures are not monitored during manual
operation. Faulty operation or unsupervised operation of this
function may result in damages to the heating system.
+
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 3 Donnerstag, 21. Februar 2013 11:46 11

Sensor resistance values
4
5. Sensor resistance values
Depending on temperature:
PT1000 KVT 20
T (°C) R (kOhm) T (°C) R (kOhm)
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
1,155
1,194
1,232
1,271
1,309
1,347
1,385
1,423
1,461
1,498
1,536
1,573
1,611
1,648
1,685
1,722
1,758
1,795
1,832
1,868
1,905
1,941
10
12
14
16
18
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
1,783
1,812
1,840
1,869
1,898
1,928
2,002
2,078
2,155
2,234
2,314
2,395
2,478
2,563
2,648
2,735
2,824
2,914
3,005
3,098
3,192
3,287
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 4 Donnerstag, 21. Februar 2013 11:46 11

5
Menu level
6. Menu level
General menu structure Ceta series
Basic display
Prog
Esc
01
Menu 01
02
Menu 02
+-
27
Calibration
28
Relay test
02:01
Parameter 01
02:02
Parameter 02
02:nn
Last parameter
+-
+-
+
-
+
-
Prog
Select menu level
Select parameters
Esc
Value 1
Prog
Value 2
+-
Value n
+-
Set parameter value
Prog
Return
without
saving
Return
and save
Esc
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 5 Donnerstag, 21. Februar 2013 11:46 11

Menu level
6
Overview of menu level
X1: Only displayed during active heat balancing
X2: Function only in bus connection
X3: Are hidden when activating code 03:09
Basic display
Prog
01
Info
03
System
+-
08
Delta T
27
28
Relay test
03:01
08:01 08:02 08:03
03:03
+-
+-
+-
+
-
08:01
Delta T oper.mode
08:02 08:03
08:09 08:10 08:11
27:01 27:02 27:03
+
-
28:01
-
+
-
+
Prog
ESC
Prog
ESC
Prog
ESC
Prog
ESC
Prog
ESC
X1 X1
ESC
X2 X2 X3
X3
08:19 08:20
Switch-on temperature
thermostat
08:21
Switch-off temperature
thermostat
03:06 X3
Heat capacity Heat balance Pump on/off
Code entry Bus address Automatic
exit time
Switch-on difference Switch-off difference
Burner block
heat generator
Inhibition heat
generator
Heat balance
On/Off
Burner block
temperature
Calibration Calib. sensor F1 Calib. sensor F2 Calib. sensor F3
Relay test output R1
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 6 Donnerstag, 21. Februar 2013 11:46 11

7
Menu level
08:04 08:05 08:06 08:07 08:08
08:04 08:05 08:06 08:07 08:08
08:12 08:13 08:14 08:15
03:09 03:10
03:07 X3 X3
Anti-blocking
prot.pump
08:18
Heat exchange
function
08:22
Reversing the
thermostat
08:23
Frost protection temperature
of solar panel flow sensor
Temperature
heat supplier
Temperature heat
storage tank Return temperature Pump
operating hours Pump starts
Code heating
specialist Reset parameter
Minimum running
time of pump
Min. temp. of
heat supplier
Max. temp. of
heat supplier
Fin.switch-off
temp.heat supplier
Max. temp. of heat
storage tank
Volume flow
HT-medium Density HT-medium Heat capacity
HT-medium Reset counter
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 7 Donnerstag, 21. Februar 2013 11:46 11

Parameter description
8
7. Parameter description
01 Information level
03 Parameter system
Display Designation Description
08:01 Heat capacity Current heat capacity in W X1
08:02 Heat balance Display of cumulative heat energy in kWh X1
08:03 Display pump
function
0: Pump is switched off
1: Pump is switched on
08:04 Temperature
Heat supplier
Sensor temperature of heat supplier (e.g. collector, solid fuel
boiler) at input F3
08:05 Te m p e r a t u re
Heat storage tank
Sensor temperature of heat storage tank at input F1
08:06 Return temperature Sensor temperature of return at input F2, if available.
08:07 Pump operating
hours
Number of pump operating hours
08:08 Pump starts Number of pump starts
Display Designation Description
03:01 Code entry Setting range: 0 … 999
Factory setting: 0
Function:
Show parameters marked with X3 if they are hidden by the
"Code heating specialist" 03:09.
03:03 Bus address Setting range: 21…25 X3
Factory setting: 21
Function:
If more than one CETA 100 or 101 has to be connected via data
bus within a system, each unit must be set to a unique address.
03:06 Automatic exit time Setting range: 0.5 … 10 min X3
Factory setting: 2 min
Function:
When unit is not operated during the set time, the display
returns to basic display.
03:07 Anti-blocking
protection
Setting range: 0 = OFF X3
1 = ON
Factory setting: OFF
Function:
Pump is switched on 20 s daily during extended shutdown
(> 24h) as protection against blocking when function is activated.
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 8 Donnerstag, 21. Februar 2013 11:46 11

9
Parameter description
08 Parameter Delta-T
03:09 Code heating
specialist
Setting range: 0 … 999
Factory setting: 0
Function:
Hide parameters marked with X3.
03:10 Total reset Reset to factory settings
Display Designation Description
08:01 Control mode Setting range: 0…3
Factory setting: 1
Function:
0 = OFF
1 = Delta-T without return flow sensor
2 = Delta-T with return flow sensor F2
3 = Thermostat function F1
08:02 Switch-on difference Setting range: (Switch-off differential + 3K) … 30K
Factory setting: 10K
Function:
If temperate difference between sensors of heat supplier F3 and
heat storage tank F1 is greater than set value, the pump
switches on.
08:03 Switch-off difference Setting range: 2K … (Switch-on differential - 3K)
Factory setting: 5K
Function:
If temperate difference between sensors of heat supplier F3 and
heat storage tank F1 is less than set value, the pump switches
off.
08:04 Minimum running
time of pump
Setting range: OFF (----)
0.5 … 60 min
Factory setting: 3 min
Function:
Minimum switch-on time of pump per start.
08:05 Minimum
temperature heat
supplier
Setting range: OFF (----)
5 … 80 °C
Factory setting: OFF
Function:
Irrespective of switching differentials, the pump switches on
only after the sensor of heat supplier F3 has exceeded the set
value.
Note: The set minimum temperature has a fixed switching
hysteresis of 10K.
Display Designation Description
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 9 Donnerstag, 21. Februar 2013 11:46 11

Parameter description
10
08:06 Maximum
temperature heat
supplier
Setting range: OFF (----), 30 … 110 °C
Factory setting: 90°C
Function:
Irrespective of switching differentials, the pump performs a
forced switch on after the sensor of heat supplier F3 has
exceeded the set value.
08:07 Final switch-off
temperature of heat
supplier
Setting range: OFF (----), 70 … 210 °C
Factory setting: OFF
Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat supplier F3 has
exceeded the set value.
08:08 Maximum
temperature heat
storage tank
Setting range: OFF (----), 50 … 110 °C
Factory setting: 75°C
Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat storage tank F1 has
exceeded the set value. This switch-off takes priority over
functions 08:07 and 08:06.
08:09 Burner block
Heat generator
Setting range: 0 ... 2 X2
Factory setting: 1
Function: 0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
08:10 Temporary
interruption of heat
generator
Setting range: OFF (----) ... 24h X2
Factory setting: OFF
Function:
After burner block is active, the heat generator is also blocked for
the duration of the set time.
08:11 Activation of heat
balance
Setting range: OFF (----) X3
1 = Heat balancing via sensor on F2
Factory setting: 1
Function:
The settings of parameters 08:12 to 08:14 are only active if the
heat balance function has been switched on via this parameter.
08:12 Volume flow HT-
medium
Setting range: 0.0 … 30 l/min
Factory setting: 0.0 l/min
Function:
Here the volume flow is set in litre/minute when calculating flow
rate, according to respective pump capacity.
Display Designation Description
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 10 Donnerstag, 21. Februar 2013 11:46 11

11
Parameter description
08:13 Density HT-medium Setting range: 0.8 … 1.2 kg/l
Factory setting: 1.05 kg/l
Function:
Using this parameter, the density of the heat transfer medium is
entered in kilogramme per litre, according to manufacturer's data.
08:14 Heat capacity HT-
medium
Setting range: 2.0 … 5.0 kJ/kgK
Factory setting: 3.6 kJ/kgK
Function:
This setting value is used to enter the specific heat capacity of
the heat transfer medium according to manufacturer's
information.
08:15 Reset counter Setting range: 0 = no reset, 1 = reset counter
Factory setting: 0
Function:
When value is changed to 1 and confirmed, all counters (heat
balance, operating hours and starts) are
reset.
08:18 Heat exchange
difference
Setting range: OFF (----), 5 ... 50K
Factory setting: OFF
Function:
If the F1 temperature is higher than 08:08 and the F3
temperature below 40°C, the pump will be switched on until the
F1 is lowered to the set difference below 08:08.
08:19 Burner block
temperature
Setting range: OFF (----), 5 ... 80 °C
Factory setting: OFF
Function:
Additionally or alternatively to 08:09, an F1 temperature can be
set whereby the burner block will be activated (via data bus).
When the temperature sinks below the value of 08:19 by 5K, it
will be deactivated.
08:20 Switch-on
temperature
thermostat
Setting range: 5 °C ... (switch-off temperature -3K)
Factory setting: 30 °C
Function:
If F1 sinks below the setting range, the pump switches on.
08:21 Switch-off
temperature
thermostat
Setting range: (switch-on temperature +3K) ... 120 °C
Factory setting: 90 °C
Function:
If F1 exceeds the set value, the pump switches off.
08:22 Reversing the
thermostat
Setting range: 0, 1
Factory setting: 0
Function:
reverts the pump function. 0 = closer, 1 = opener
Display Designation Description
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 11 Donnerstag, 21. Februar 2013 11:46 11

Parameter description
12
27 Sensor calibration
08:23 Frost protection
temperature of solar
panel flow sensor
Setting range: OFF, -15 °C ... 10 °C
Factory setting: OFF
Function:
When the solar panel temperature is below the set value, the
solar loading pump will be switched on, and it will be switched
off when the solar panel temperature exceeds the set value by
+2.5K.
Display Designation Description
27:01 Calibration F1 Setting range: -5K … +5K
Factory setting: 0K
Function: Correction of measured sensor value on
Input heat storage tank F1
27:02 Calibration F2 See 27:01 on input return F2
27:03 Calibration F3 See 27:01 on input heat supplier F3
Display Designation Description
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 12 Donnerstag, 21. Februar 2013 11:46 11

13
Mounting
28 Relay test
8. Mounting
Drilling pattern for wall fastening
Rail mount
Display Designation Description
28:01 Test pump output Setting range: -0 = OFF
1 = ON
Factory setting: 0
Function:
By changing the value, the output switches on and off (test
function), independent of function.
Hazard!
Installation must be performed only by an authorised
professional electrician! Ensure that unit is de-energised before
opening it!
1. Remove terminal area cover from
casing.
2. For mounting, first put a screw
into the wall.
3. Hang controller into the opening.
4. Use controller as template for the
other screw holes.
1. Insert mounting feet into rail
mount opening.
2. Lock hook in place by pushing
down.
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 13 Donnerstag, 21. Februar 2013 11:46 11

Terminal diagram
14
9. Terminal diagram
Hazard!
Connection must be performed only by an authorised
professional electrician! Ensure that unit is de-energised before
opening it!
230V connections Low voltage connections
L=Phase 230V mains
1=L1 (230V) pump connection
Connections without function
Connections without function
N=Neutral 230V mains, pump
Connections without function
=Ground connection
Bus connections for networking (see parameter 03:03)
Connections without function
Connections without function
F1=Sensor heat storage tank Delta-T (KVT20)
F2=Sensor return flow Delta-T (KVT20), (option)
F3=Sensor heat supplier Delta-T (PT1000)
Connections without function
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 14 Donnerstag, 21. Februar 2013 11:46 11

15
Fault clearance
10. Fault clearance
To allow an accurate diagnosis in case of malfunction, the unit is equipped with
a fault display system. The faults are shown on the basic display of the unit in
form of an error code:
Fault overview:
A corresponding fault code is shown alternately in the lower display:
0---°C = Sensor heat supplier (e.g. collector or
solid fuel boiler) has interruption
1---°C = Sensor heat storage tank has short
circuit
1---°C = Sensor heat supplier (e.g. collector or
solid fuel boiler) has short circuit
0---°C = Sensor heat storage tank has
interruption
Fault code Cause Repair
0--- Sensor F1, F2 or F3 interruption Check cable and plug connection; repair
if necessary
1--- Sensor F1, F2 or F3 short circuit Replace sensor
Fault Cause Repair
Display text not visible No power, defective fuse in unit Check cable and plug connection; repair
if necessary; replace fuse
Fault Cause Repair
11-0 Interruption sensor F1 Check cable and plug connection;
replace if necessary
11-1 Short circuit sensor F1 Replace tank sensor
12-0 Interruption sensor F2 See 11-0
12-1 Short circuit sensor F2 See 11-1
13-0 Interruption sensor F3 See 11-0
13-1 Short circuit sensor F3 See 11-1
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 15 Donnerstag, 21. Februar 2013 11:46 11

Declaration of conformity
16
11. Declaration of conformity
Elektronikbau- und Vertriebs- GmbH
Heisternerweg 8-12, 57299 Burbach
EC Declaration of Conformity
Product identification: Heating controller
Type designation: CETA 100
Manufacturer:
EbV Elektronikbau- und Vertriebs-GmbH
Heisternerweg 8-12
57299 Burbach
The product described is in full compliance with the following European directives:
89/336/EEC
„Council directive on the approximation of the laws of the member states
relating to Electromagnetic Compatibility“
73/23/EEC
„Council directive on the approximation of the laws of the member states
relating to electrical equipment designed for use within certain voltage
limits" (low voltage directive)
Compliance of the designated product with the rules of the directive is proven by complete
adherence to the following standards:
EMV: Requirements for household appliances, electric tools and similar devices
DIN EN 55014-1:2003 Part1: Transient emission
DIN EN 55014-2:2002 Part 2: Immunity
EMV: Limit values
DIN EN 61000-3-2:2002 Part 3-2: Limit values for harmonic current emissions
DIN EN 61000-3-3:2002 Part 3-3: Limitation of voltage fluctuations and flicker
Automatic electrical controls for household use and similar applications
DIN EN 60730-1:2002 Part 1: General requirements
DIN EN 60730-2-9:2004 Part 2: Particular requirements for temperature sensing controls
We declare that the described product - as independent device - is in conformity with the standards,
directives and/or technical specifications listed above.
EbV Elektronikbau- und
Vertriebs-GmbH
Burbach, 20.02.2009 _________________________________
Wolfgang Höse
Managing Director
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 16 Donnerstag, 21. Februar 2013 11:46 11

17
Technical Data
12. Technical Data
13. Liability
Our general terms and conditions of business are generally applicable. Any liability
claims based on failure to observe operating manual as well as safety instructions
contained therein, are excluded. Subject to technical modifications.
14. Disposal
Dispose of all replaced parts, and eventually the controller itself, in an
environmentally sound manner in compliance with applicable statutory
regulations of the corresponding country.
Power supply voltage: 230V +6%/ -10%
Rated frequency: 50...60Hz
Power input: max. 2.1VA
Fuse: 6.3A
Output relay contact load: 2 (2)A
Ambient temperature: -10...+50°C
Storage temperature: -25...+80°C
Degree of protection: IP 30
Protection class according to EN 60730: II
CE compliance: 89/336/EEC
Casing dimensions: 145.5 x 161 x 48 mm (W x H x D)
Casing material: ABS V0
Weight: 420g
Mains connection technology: Screw terminals 1.5 mm
2
Sensor connection technology: Screw terminals 1.0 mm
2
Company stamp:
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 17 Donnerstag, 21. Februar 2013 11:46 11
Table of contents
Other EbV elektronik Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Pittway
Pittway System Sensor 5251RP Installation and maintenance instructions

BAPI
BAPI BAPI-Stat 4 X-Combo operating instructions

Watlow
Watlow SD Series user manual

Carbolite Gero
Carbolite Gero Eurotherm 2216 operating instructions

Pentair Pool Products
Pentair Pool Products 6800 installation instructions

Ecolink
Ecolink ClearSky CS-502 installation guide