STORK TRONIC ST129-JA1TA.10 User manual

ST129-JA1TA.10
Temperature controller
Order number 900321.003
Wiring diagram
Product description
The controller ST129-JA1TA.10 is intended for the assembly on DIN rail, which allows easy in-
stallation in the switch gear cabinet. It was specifically developed for direct switching at high per-
formances. Given the high maximum electric load of 16A (ohm) and 6A (inductive) it can operate
without cut-out relay in many cases. The controller is supplied with 230V AC and has 4 keys.
Sensor: Pt100, PTC
Range: dependent on the type of sensor
Housing size(L x W x H): 106 x 95 x 60mm
Installation: Clip-on mounting on DIN-Rail 35 x 7.5mm
Connector: screw terminal
1

2

SOFTWARE .10
Adjustment options
Key 1: UP
Pressing this key you can increase the parameter or parameter value or scroll the
parameter list.
Key 2: DOWN
Pressing this key you can decrease the parameter or parameter value or scroll the
parameter list. At alarm the buzzer function can be switched off with this key.
Key 4: SET
While SET key is pressed, the setpoint is indicated.
In addition, the SET key is used for setting parameters
Key 5: Standby
Switching the controller on or off.
First control level:
Parameter setting of the control setpoint
If none of the keys is pressed, the display indicates the actual value of the temperature. Pressing
the SET key, the setpoint shows on the display.
If the setpoint is to be changed, the SET key is to be kept pressed while adjusting the setpoint with
the keys UP and DOWN.
Please note that the setpoint can only be changed within the set setpoint limits.
With appropriate parameter settings (see A85, A86) a second setpoint S1’ can be activated with a
special key A or B (if available).
The setpoint S1’ can be adjusted in the same way. If setpoint S1’ is activated it is indicated and
relevant for the control.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
S1
Setpoint
P4...P5
0.0°C
S1‘
Setpoint S1’ (relative)
Setpoint S1’ (absolute)
-99...+99.9 K if A33=1
P4...P5, if A33=2
0.0°C/K

Second control level (P parameters):
Setting of control parameters
Simultaneously pressing the UP and DOWN key for at least 4 seconds opens a parameter list
containing control parameters.
With the UP and DOWN keys the list can be scrolled in both directions.
Pressing the SET key will give you the value of the respective parameter. Pressing also the UP or
DOWN key at the same time the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
P0
Actual measuring value
-
-
P2
Hysteresis contact K1
0.1... 99.9 K
1.0 K
P4
Control range limitation –
minimum setpoint
-99°C...P5
-99°C
P5
Control range limitation –
maximum setpoint
P4...999°C
999°C
P6
Actual value correction
-20.0...+20.0 K
0.0 K
P19
Key-lock
0: no key-lock
1: key-lock
0
P30
Lower alarm value
-99 ... 999°C/K
-99°C
P31
Upper alarm value
-99 ... 999°C/K
100°C
P32
Hysteresis alarm circuit
0.1... 99.9 K
1.0 K
d0
Defrosting interval
1...99 hours
0: no defrosting
8 h
d2
Defrosting temperature
-99 …999 °C
10.0 °C
d3
Defrosting time limit
1…99 min
0: without time limit
30 min

Parameter description:
P2: Hysteresis contact K1
The hysteresis can be set symmetrically or one-sided at the setpoint (see A40, A41).
At one-sided setting, the hysteresis works downward with heating contact and upward with cooling
contact. At symmetrical hysteresis, half of the hysteresis’ value is effective below and half of the
value above the switching point (see fig. 1 and 2).
Fig. 1: Heating controller, one-sided hysteresis Fig. 2: Cooling controller, symmetrical
hysteresis
P4: Control range limitation – minimum setpoint
P5: Control range limitation – maximum setpoint
The adjustment range of the setpoint can be limited in both directions. This is to prevent the end
user of a unit from setting inadmissible or dangerous setpoints.
P6: Actual value correction
This parameter allows the correction of actual value deviations caused for example by sensor
tolerances or extremely long sensor lines. The regulation measure value is increased or decreased
by the here adjusted value.
P19: Key-lock
The key-lock allows blocking of the control keys. In locked condition parameter adjustments with
keys is not possible. At the attempt to adjust the parameters despite key-lock the message "==="
appears in the display.
P30: Lower alarm value
P31: Upper alarm value
The exit alarm is a boundary alarm or a range alarm with symmetrical hysteresis (see parameter
P32). Both at the boundary alarm and the range alarm, limit values can be relative, i.e. going along
with the setpoint, or absolute, i.e. independent of the setpoint. At boundary alarm the hysteresis
works one-sided inwardly, and at range alarm outwardly.
P32: Hysteresis alarm circuit
Hysteresis is set one-sided at the adjusted limit value. It becomes effective depending on alarm
definition.
d0: Defrosting interval
The "defrosting interval" defines the time, after which a defrosting process is started. After each
defrosting start, this time is reset and runs the next interval.

d2: Defrosting temperature limit
This permits to terminate defrosting when the adjusted desired temperature value is reached. The
defrosting time set with "d3" nevertheless runs at the same time, i.e. it functions as safety net to
terminate the defrosting process in case the defrosting temperature is not reached.
d3: Defrosting time limit
After the here set time the defrosting process is terminated.

Third control level, (A parameters):
Setting of control parameters
Access to the third control level is granted when selecting the last P-parameter on the second
control level. Continue to press the UP key for approximately 10 seconds until “PA” appears.
Continue to press the UP key and additionally press the DOWN key for about 4 seconds and the
first A-parameter of the third control level is indicated.
With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET key will
give you the value of the respective parameter. By pressing the UP or DOWN key at the same time
the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by
simultaneously pressing the UP and DOWN key for approx. 4 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A1
Switch mode contact K1 0: heating contact
1: cooling contact
2: function alarm K1
0
A3
Function of contact K1 at
sensor error
0: relay off
1: relay on
0
A8
Display mode
(all parameter indications are
presented in 0.1°K)
0: integrals
1: decimals in 0.5°C
2: decimals in 0.1°C
1
A19
Parameter lock
0: no lock
1: A-parameter locked
2: A- and P-parameter locked
0
A30
Function alarm exit
0:Boundary alarm, relative
1:Boundary alarm, absolute
2:Range alarm, relative
3:Range alarm, absolute
4:Boundary alarm, relative,
inverted alarm contact
5:Boundary alarm, absolute,
inverted alarm contact
6:Range alarm, relative,
inverted alarm contact
7:Range alarm, absolute,
inverted alarm contact
0
A31
Special function at boundary or
range alarm
0:no special function
1:flashing display
2:buzzer
3:flashing display and buzzer
4:like 3, buzzer can be cancelled
5:like 4, buzzer restarts after 10 min.
6:like 4, buzzer restarts after 30 min
0
A32
Setpoint display
0: display shows actual value
1: display shows setpoint S1 (S1‘)
0
A33
Type of setpoint S1‘
0: not activated
1: relative to setpoint S1
2: absolute (freely adjustable)
0
A40
Hysteresis mode contact K1
0: symmetrically
1: one-sided
1

Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A50
Minimum action time
contact K1 ”On”
0…600 sec.
0 sec.
A51
Minimum action time
contact K1 ”Off”
0…600 sec.
0 sec.
A54
Delay after “Power-on”
0…600 sec.
0 sec.
A56
Alarm suppression after
"Power-On"
0…60 min.
0 min.
A60
Sensor type
11: Pt100 2-wire
21: PTC
22: Pt1000 2-wire
11
A70
Software filter
1: inactive
2…32: average value with 2…32
measuring values
4
A80
Temperature scale and display
when in Standby-Mode
0: Fahrenheit (“AUS”)
1: Celsius (“AUS”)
2: Fahrenheit (“OFF”)
3: Celsius (“OFF”)
1
A85
Function key A
(if available)
0:no function
1:indicate actual value (if A32=1)
2:activate setpoint S1‘ (if A33>0)
0
A86
Function key B
(if available)
0:no function
1:indicate actual value (if A32=1)
2:activate setpoint S1‘ (if A33>0)
0
A87
Function standby key
0:no function
1:controller On/Off (Standby), same
condition after connecting mains
2: like 1, always off after connecting
mains
3: like 1, always on after connecting
mains
1
A88
Delay for standby ON
0.1 ... 3.0 sec.
0.1 sec.
A89
Delay for standby OFF
0.1 ... 3.0 sec.
0.1 sec.
Pro
Program version
-
-

Parameter description:
The following values can change the equipment characteristics
and are therefore to be set with utmost care.
A1: Switch mode contact K1
The switch mode for the relay, i.e. cooling or heating function, can be programmed independently
at works. Heating function means that the contact opens as soon as the setpoint is reached, thus
power interruption. At cooling function the contact closes, if the actual value is above the required
setpoint. (see fig. 1 + 2)
A3: Function of contact K1 at sensor error
At sensor error the relay falls back into the condition pre-set here. If there is a data-loss in
parameter memory (display indicates “EP”) both contacts K1 and K2 are switched off.
A8: Display mode
The value can be indicated in integrals or with decimals in 0.5°K or 0.1°K. At indication in 0.5°K the
value is rounded up or down. In general, all parameter indications are presented in 0.1°K.
A19: Parameter lock
This parameter enables locking of each parameter level. If third level is locked, only parameter A19
may be changed.
A30: Function alarm exit
The alarm exit evaluates an upper and a lower limit value (see parameters P30 and P31), whereas
a selection is possible as to whether the alarm is active if the temperature lies within these two
limits, or whether the alarm is released if the temperature lies beyond them. In the case of sensor
error, the alarm is activated independently of this adjustment (see fig. 3 – 4 at parameters P30/31).
A31: Special function at boundary or range alarm
Here can be selected whether, in the case of an alarm, the indication to flash and/or the buzzer is
to start. Sensor alarm (display F1L or F1H) is indicated independently thereof by flashing display
and the buzzer.
A32: Setpoint display
A32=0 indicates the actual value, A32=1 statically indicates the setpoint S1 or S1’ in the display.
Therefore, the current actual value can only be indicated with parameter P0.
A33: Adjustment of setpoint S1‘ (not available on all types of controllers)
By closing switching input E1, setpoint S1 can be switched to a setpoint S1’. Setpoint S1’ can be
either relative to setpoint S1 or an independent, freely adjustable, control setting.
The setpoint S1’ can only be accessed if input E1 is closed. The setpoint S1’ can only be activated,
if the external input is configured for setpoint change-over (parameter A81=2).
A40: Hysteresis mode contact K1
These parameters allow selection as to whether the hysteresis value which is adjustable with P32,
is set symmetrically or one-sided at the respective switching point. At symmetrical hysteresis, half
of the hysteresis’ value is effective below and half of the value above the switching point. The one-
sided hysteresis works downward with heating contact and upward with cooling contact (see fig. 1
+ 2).

A50: Minimum action time contact K1 ”On”
A51: Minimum action time contact K1 ”Off”
These parameters permit a delay in switching on/off the relay in order to reduce the switching
frequency. The adjusted time sets the entire minimum time period for a switching-on or switching-
off phase.
A54: Delay after “Power-on”
This parameter allows a switching-on delay of relays after switching-on the mains voltage. This
delay corresponds with the time set here.
A56: Alarm suppression after "Power-On"
This parameter allows a switching-on delay of the alarm contact after switching on the mains
voltage or setpoint change-over. This delay corresponds with the time set here.
A60: Sensor type
These parameter permits selection of the sensor type, if the needed hardware prerequisites are
available.
A70: Software filter
With several measuring values, it is possible to obtain an average value. This parameter can
determine by how many measured values an average value is to be formed. If a sensor with a very
fast reaction to external influences is used, an average value ensures a calm signal process.
A80: Temperature scale
Indication can be switched between Fahrenheit and Celsius. At conversion, the parameters and
setpoints maintain their numerical value and adjustment range. (Example: A controller with the
desired value of 0°C is switched to Fahrenheit. The new desired value is then interpreted as 0°F,
which corresponds to a temperature of -18°C).
NOTE: Indication limits with °F can be smaller than the actual measuring range!
A85 Function key A
A86 Function key B
0: no function
1: actual value will be indicated if A32=1, otherwise no function
2: Setpoint S1 is switched to setpoint S1’ (see A33)
A87: Function standby key
The following functions are available:
0: the respective key has no function
1: the controller is switched to standby mode
A88: Delay for Standby ON
A89: Delay for Standby OFF
For switching the controller on and off, a delay for the Standby key can be defined here.

Status messages
Message
Cause
Error elimination
“AUS” or “OFF”
Standby modus, no regulation
Switch on with standby key
F1L
Sensor error,
short-circuit at sensor F1
Check sensor
F1H
Sensor error,
open-circuit at sensor F1
Check sensor
_ _ _
Key-lock active
Change parameter P19 or A19
display flashes
Temperature alarm at too high or too
low temperature (if activated) see A31
Buzzer
Temperature alarm at too high or too
low temperature (if activated) see A31
The buzzer function can be switched
off with the DOWN-key
EP, display
flashes
Data loss at parameter memory
(Contacts K1 and K2 are switched off)
If error cannot be eliminated by
switching on/off, the controller must be
repaired

Order No.: 900321.001
Technical data of ST129-JA1TA.10
Measuring input
F1: Resistance sensor PTC, Pt100 or Pt1000, 2-wire connection
Measuring range: Pt100 -80°C...+400 °C
Pt1000 -99°C...+350°C
PTC -50°C...+150 °C
Measuring accuracy of the controller at 25°C: +/-0.5K und +/-0.5% of measuring range
Outputs
K1: Relay, normally-open contact, 30(6)A 250V~,
permanent current max. 16(6)A, limited by connectors and/or conductive strips
Display
One 3-digit LED-Display, height 13 mm, colour red
1 LED, diameter 3mm, colour red, for status display of K1
Power supply
230V~ 50/60 Hz, power consumption max. 5 VA
Connectors
screw terminal
X1: 3 pole, spacing 5.0 mm, for cable up to 2.5 mm²
X2: 4 pole, spacing 5.0 mm, for cable up to 2.5 mm²
Ambient conditions:
Storage temperature: -20...+70°C
Operating temperature: 0...+55°C
Relative humidity: max. 75% without dew
Weight
ca. 300 g, without sensor
Enclosure
Front IP00
Installation data
Unit is to be installed on a DIN rail 35mm x 7.5mm
Hounsing size: L 106 mm x W 95 mm x H 60mm
This manual suits for next models
1
Other STORK TRONIC Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

T&D
T&D RTR-501 user manual

aci
aci WH2630A Installation & operation instructions

Full Gauge Controls
Full Gauge Controls Evolution MT-514 E quick start guide

SCI
SCI ERV-24-SUPER owner's manual

Siemens
Siemens RVL470 Basic documentation

Vaillant
Vaillant VRC 400 Operating and OPERATING AND INSTALLATION Manual