Display Messages
In normal operation the probe temperature selected by P5 will be displayed.
The following messages can also appear :
- Err Memory reading error.
- ErP1, ErP2, ErP3 Probe1 , 2 or 3 error
- Eri Internal parameter error. In this case, enter the standard configuration,
as it is indicated in “To record a standard configuration”.
- ALH High temperature alarm.
- ALL Low temperature alarm.
- ALE External alarm.
- AEH High temperature and external alarm.
- AEL Low temperature and external alarm.
- ooo Open probe.
- - - - Short-circuited probe.
- DON Defrosting activated.
- DOF Defrosting de-activated or cannot be done.
- CON Continuous cold cycle activated.
- COF Continuous cold cycle de-activated or cannot be done.
- -d- Thermostat on defrosting.
To view the probe not chosen by P5, press SET+UP
The display blinks when there is an error recording a parameter in memory or
when awaiting confirmation of a value.
Operation in Error Case
If the ambient probe fails, the thermostat will connect the compressor
according to parameters c2 and c3, being able to perform defrosting and
continuous cold cycles.
If the memory fails the thermostat will connect the compressor ON for 5
minutes and OFF for 5 minutes, not being able to perform defrosting or
continuous cold cycles.
Buzzer Operation
If there is a memory error, probe error, temperature alarm (high or low),
external alarm or door open alarm, the internal buzzer sounds.
The buzzer can be muted pressing any key.
Two Compressors Operation
In this case, when the thermostat demands cold (Sd1 >= Set+r0) the first
compressor to be connected is the compressor with less running hours, and
after c6 seconds, the second compressor is also connected. When the
thermostat begins to cool, and Sd1<Set+r0/2 is reached, the second
compressor stops, and the first one continues. The second will be stopped
when Sd1<Set. Nevertheless, if before stopping the first compressor, Sd1 >=
Set+r0, the second compressor starts running again.
HACCP
If this option is activated, the thermostat registers up to 5 alarms of the types
Hight, Low, and blackout. These alarms can be seen in the menu Registry of
Alarms (HAC). To acced to this menu, proceed as for the parameters menu.
The first value that appears is the number of registered alarms. Afterwards,
for each alarm (if it has existed), the value of the temperature and the time of
the alarm. For the disconnection alarm, the temperature when returning the
connection is registered, as well as the time until the correct values are
reached. (Probe<Set+A1-A0)
When the elapsed time is showed it will appear xxd (days).Pressing UP xxH
(Hours) will be shown, and pressing UP again, xxn (Minutes) will be
displayed. When located over a temperature of alarm or time, pressing
UP+DOWN during 2 seconds, both recorded data of the alarm (time and
temperature value) are deleted.
In the Ald menu, and pressing UP+DOWN keys during 2 seconds, all the
recorded data of alarms are deleted.
Front Operation
Set Point Setup
- Press key SET. The Set label appears.
- Press SET again. Current set point value appears blinking.
- Press UP or DOWN to increase or decrease the value.
- Press SET to confirm the new value.
- Press SET and DOWN to exit
Time programming
- Press key SET. The Set label appears.
- Press UP or DOWN to go to Hour or Minute
- Press SET to see the value.
- With UP and DOWN set the desired new value.
- Press SET for 8 seconds, Pro will appear on the display once the
time has been correctly programmed
- Press SET + DOWN to quit or wait for 1 minute (keyboard timeout).
Parameter programming
- The parameters are grouped in the menus COM, DEF, PRO, ALA,
INI
- Press SET for 8 seconds. Value 00 appears blinking.
- Set the code with UP and DOWN (it is set to 00 from factory).
- Press SET to confirm the code. If it is right, the label of the first
menu will appear.
- With UP and DOWN go to the desired menu.
- Press SET, the label of the first parameter of menu will appear.
- With UP and DOWN go to the desired parameter label of the list of
parameters.
- Press SET to see the value.
- With UP and DOWN set the desired new value.
- Press SET to confirm it and exit to the parameter label.
-Press SET + DOWN to go to menu list.
-Press SET + DOWN to quit programming or wait 1 minute
(keyboard timeout).
To record a standard configuration
-Access to parameter H0 as explained in Parameter programming.
- Choose desired configuration.
For series KLT13I-Dx: H0 is set to 0
For series KLT23I-Dx: H0 is set to 1
For series KLT33I-Dx: H0 is set to 2
For series KLT33I-Dx: H0 is set to 3
- Press SET for 8 seconds, and the thermostat will be reset.
-Press SET + DOWN to quit or wait for 1 minute (keyboard timeout).
Manual Defrost.
Pressing UP key for 8 seconds defrost is activated. Repeating the
operation is deactivated.
Continuous cold cycle.
Pressing DOWN key for 8 seconds a continuous cold cycle begins.
Repeating the operation the cycle finalizes.
Setting keyboard code to zero
The keyboard code can be programmed to zero by turning off the
controller, and turning it on again, while the key SET is pressed.
Alarm validation
An active alarm can be validated (the alarm output will be turned off)
pressing the SET and DOWN keys simultaneously.
Led Indications
Out: It indicates Compressor connected. It blinks when a
continuous cold cycle has to be initiated and has to wait until the
minimum compressor stoppage time is over.
Def: It indicates defrosting is activated.
Fan: It indicates ventilator is connected.
Alarm: It indicates an error or alarm. It blinks when the alarm is
validated by the user
ON OFF Thermostat
Pressing the keys SET+DOWN for 8 seconds the thermostat will
turn-on or turn-off
If we have a relay setup as light, pressing keys UP+DOWN for 3
seconds the thermostat will turn-on or turn-off the light
The cycles of defrosting can be performed counting total time (d14=
rt) or counting the time only when the compressor is connected
(d14= ct). When (d14= rt) and (d8 24.0 ) First defrosting of day is
made at the hour d3 And the others with the cycle given by d8.
When (d14= ct) or (d8 24.0 ) the cycle is only performed by d8 .
Hour/Minutes Parameters H-M
It is a way to show hours and minutes in 3 digits
The two first digits are the hours and the third the tens of minutes.
E.g. 2.4 2 hours 40 minutes
8.0 8 hours 0 minutes
10.3 10 hours 30 minutes
COMPRESSOR
c2 = ON time of fault cycle, when ambient probe is broken
c3 = OFF time of fault cycle, when ambient probe is broken
Minimum time between two connections of the compressor
ON OFF Light
Defrosting Cycles
<
>=
Parameter description
(CON)
SET = Work set point.
Temperature we wish to maintain the machine. Variable between r1
and r2.
r0 = Differential.
When ambient probe temperature >= Set+r0 Compressor ON
When ambient probe temperature <= Set Compressor OFF
r6 = Fan operation on regulation.
Off = Fan does not connect on regulation.
On = Fan is always connected on regulation.
Con= Fan linked to compressor start-up.
(Fan ON if allowed by the temperature given by F0)
F0 = Fan temperature limit.
Direct mode. Relay selected as FAN
Fan OFF on regulation when probe temperature setup in d12
is >= F0.
Fan ON on regulation, when temperature is =< F0 -A0.
Reverse mode. Relay selected as FAI
Fan OFF on regulation when probe temperature setup in d12
is < F0.
Fan ON on regulation, when temperature is >= F0 +A0.
F1 = Stop compressor and Fan if door opened.
No = The fan and compressor do not stop on regulation and
continuous cycle when opening the door.
Yes = The fan and compressor stop on regulation and
continuous cycle when opening the door.
Con = The compressor stop but the fan do not stop on
regulation and continuous cycle when opening the door.
Fan = The fan stop but the compressor do not stop on
regulation and continuous cycle when opening the door.
c0 = Minimum compressor stop time
Minimum time since compressor stops until it is starts again.
c1 = Continuous cycle time.
Duration of a continuous cold cycle.
c4 = Minimum time of working of the compressor
Minimum time since compressor starts until it stops.
c5 =
Minimum time since compressor starts until it starts again.
c6 = Delay Time 2 Compressor
Time since compressor 1 is connected until compressor 2 is
connected, if it is necessary to connect it and if H9=Con
List of parameters
Con Description Units Range Factory
Set Set point Degrees r1 to r2 3.0
r0 Differential or hysteresis Degrees 0,1 to 20 1.0
r1 Minimum value for set point Degrees -99,9 to r2 -50.0
r2 Maximum value for set point Degrees r1 to 302 150
r6 Fan operation Range off /on /con con
F0 Fan stoppage temperature Degrees -99.9 to 302 28.0
F1 Stop compressor & Fan with Option no/yes/Con/Fan yes
door open
c0 Minimum compressor stoppage time Minutes 0 to 240 1
c1 Continuous cycle time h - m 0.0 to 18 1.0
c2 ON time of fault cycle Minutes 0 to 999 5
c3 OFF time of fault cycle Minutes 0 to 999 5
c4 Minimum ON time of the compressor Minutes 0 to 240 0
c5 Minimum time between two Minutes 0 to 240 1
connections of the compressor
c6 Delay time for second compressor Seconds 0 to 999 30
dEF Description Units Range Factory
d0 Cold / Heat mode (KLT13) Range re /in re
d0 Type of defrosting (KLT23, 33 & 43) Range re /in re
d1 Temperature at which defrosting Degrees -99.9 to 302 80.0
will stop
d2 Maximum defrosting time Minutes 0 to 240 30
d3 First Hour of Day for Defrosting h-m 00,0 to 18,0 00.0
d4 Delay of first defrosting Minutes 0 to 999 0
d5 Display on defrosting Range off/on/-d- -d-
d6 Display return limit. Minutes 0 to 240 15
d7 Compressor drip time. Minutes 0 to 240 0
d8 Interval between defrosting. h - m 00,0 to 99,0 8.0
d9 Fan works on defrosting. Range no/yes no
d10 Fan drip time Minutes 0 to 240 0
d11 Minimum Defrosting time Minutes 0 to 240 0
d12 Fan/defrosting control probe Range sd1/sd2/sd3 sd2
d14 Units to count the defrosting cycle Option rt / ct rt
Pro Description Units Range Factory
P0 Temperature scale Option ºC/ºF ºC
P1 Ambient probe 1 calibration Degrees -20,0 to 20,0 0.0
P2 Defrosting probe 2 calibration Degrees -20,0 to 20,0 0.0
P3 Product probe 3 calibration Degrees -20,0 to 20,0 0.0
P4 Decimal point Option no/yes no
P5 Probe to display Range sd1/sd2/sd3 sd1
P6 Probe 2 present Option no/yes yes
P7 Probe 3 present Option no/yes no
ALA Description Units Range Factory
A0 Fan and alarm differential Degrees 0.1 to 20.0 4.0
A1 Maximum alarm temperature Degrees 0.1 to 99.9 8.0
A2 Minimum alarm temperature Degrees 0.1 to 99.9 8.0
A3 Time validation open door or Minutes 0 to 999 11
external alarm
A4 Time without alarm after defrosting h - m 0.0 to 18.0 1.1
A5 Time without alarm after h - m 0.0 to 18.0 1.1
opening the door
A6 Time without alarm h - m 0.0 to 18.0 1.1
after connection
A7 Alarm verification time h - m 0.0 to 18.0 1.1
A8 Probe for alarm Range sd1/sd2/sd3 sd1
Ini Description Units Range Factory
Hor Hour Hours 0 to 23 0
Min Minutes Minutes 0 to59 0
E0 Configure digital input Range off/Al/In/def/ndf def
H0 Factory Settings Range 0 to 3
H1 Master/Slave Range Mst/Slv Mst
H2 Keypad protection Option no/yes no
H3 Delay time on connecting Seconds 0 to 240 0
H4 Address for serial communication Numeric 0 to 999 0
H5 Keyboard code Numeric 0 to 999 0
H6 Type of probe Option ptc / ntc ptc
H7 Relay 2 Setup Option Lit/FAn/ALA/dEF/FAI dEF
H8 Relay 3 Setup Option Lit/FAn/ALA/dEF/FAI FAn
H9 Relay 4 Setup Option Lit/FAn/ALA/dEF/Con Con
H10 HACCP Activated Option no/yes no
HdE Next defrost Time Hours (only read)
MdE Next defrost Time Minutes (only read)
SLINK
In this input we can connect a programming key to read or to write the
parameters. We can also connect a clock module so that the hour of
the thermostat goes with a realtime clock. If we manage the system
with a PC we can connect it to the thermostat through this input with a
communication module.