Ebyte 4440-GPRS User manual

E850-DTU(4440-GPRS)
User Manual
This manual may change with the continuous improvement of the product. Please refer to the latest version of the instruction.
Chengdu Ebyte Electronic Technology Co., Ltd. reserves all rights of final interpretation and modification of this manual.

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 2
Feature
Support 4-channel analog input, default current detection
Support 4-channel switch input, default dry contact
Support 4-channel relay output
Support socket connection to remote server, support TCP Client
Support Modbus TCP/RTU protocol
Support Ebyte cloud, controlled by command
Support 2 working mode, master and slave, slave can cascade multiple devices through RS485
Support reload button to restore factory settings, tap the button and press for 5 seconds, the
Modbus device address、RS485 baud rate and parity bit restore factory settings
Hardware watchdog with high reliability
Multiple indicators to show working status
The power supply has good functions such as overcurrent, overvoltage and anti-reverse
connection
Note: Products can be customized, such as conditional control (how to output based on input state)
1. Quick start
This chapter is a quick introduction to the E850-DTU (4440-GPRS) series. It is recommended that
users read this chapter carefully and follow the instructions. It will have a systematic understanding of
the product, and users can also select the chapters of interest as needed. . For specific details and
instructions, please refer to the following sections.

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 4
1.1.4 Analog input connection
1.2 Quick instruction
Cable connection: The computer connects to the E850-DTU (4440-GPRS) via USB to RS485.
Network connection: Insert SIM card in power-off state.
Power supply: E850-DTU (4440-GPRS) working voltage is DC 8-28V.
1.2.1 RS485 control
Select the port, click “Search”, and search the device.
After the device is searched, click "Stop".

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 5
At this time, you can see the current device address, for the "auto refresh" process, you can perform
the switch output control, the switch input read, the analog input read.
1.2.2 Network control
At the website: http://yun.cdebyte.com/www/data_direct ,The acquisition can be controlled by
commands, and the command supports the Modbus TCP/RTU protocol.

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 6
2. Introduction
E850-DTU (4440-GPRS) is a network IO product that supports 4 switch inputs (default dry
contact), 4 analog inputs, and 4 relay outputs. Support Modbus TCP/RTU protocol. The product is
highly easy to use and can be easily and quickly integrated into your system for GPRS-based remote
control.
2.1 Parameters
Item
Description
Wireless parameter
Standard frequency band
850/900/1800/1900MHz
Hardware parameter
Size (H*W*D)
172*107*29mm
Weight
-
Working temperature
-20℃~+70℃
Storage temperature
-40℃~+85℃
Working humidity
5%~95%
Storage humidity
1%~95%
Working voltage
8V~28V
Current collection range
0mA~20mA

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 7
Accuracy
0.2%
Data interface
RS485:1200~115200bps
Software parameter
Network type
GPRS
Configuration command
Modbus TCP/RTU
Network protocol
Modbus TCP/RTU
Working mode
Master mode, slave mode
Data transmission mode
TCP Client
2.2 Size and interface

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 8
No.
Definition
Function
Description
1
RS485 G
Signal ground
Signal ground, can be no onnected
2
RS485 A
RS485 A
RS485 A connects with device A
3
RS485 B
RS485 B
RS485 B connects with device B
4
DC-IN -
Power input negative
Power ground
5
DC-IN +
Power input positive
Power input, DC 8V~28V, recommended 12V/24V
6
DC-IN
DC 5.5*2.1mm
Power input, DC 8V~28V, recommended 12V/24V
7
Ground screw
Ground
Ground
8
Reload
Reset button
Long press 5s to work
9
SIM Card slot
SIM Card slot
Insert SIM card to connect network
10
ANT
Antenna interface
GPRS antenna
Signal interface
1
AI 1
Analog input 1
Analog input pin, forming an input with AIG
2
AIG
Analog input ground
Can be paired with AI 1
3
AI 2
Analog input 2
Analog input pin, forming an input with AIG
4
AIG
Analog input ground
Can be paired with AI 2
5
AI 3
Analog input 3
Analog input pin, forming an input with AIG
6
AIG
Analog input ground
Can be paired with AI 3
7
AI 4
Analog input 4
Analog input pin, forming an input with AIG
8
AIG
Analog input ground
Can be paired with AI 4
9
DI 1
switch input 1
Forming dry contact with DIG
10
DIG
switch input ground
Can be paired with DI 1
11
DI 2
switch input 2
Forming dry contact with DIG

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 9
12
DIG
switch input ground
Can be paired with DI 2
13
DI 3
switch input 3
Forming dry contact with DIG
14
DIG
switch input ground
Can be paired with DI 3
15
DI 4
switch input 4
Forming dry contact with DIG
16
DIG
switch input ground
Can be paired with DI 4
17
NC 1
Relay 1 normally
closed pin
Can be paired with common end of relay 1
18
COM 1
Common end of relay
1
Can be paired with other pins of relay 1
19
NO 1
Relay 1 normally
open pin
Can be paired with common end of relay 1
20
NC 2
Relay 2 normally
closed pin
Can be paired with common end of relay 2
21
COM 2
Common end of relay
2
Can be paired with other pins of relay 2
22
NO 2
Relay 2 normally
open pin
Can be paired with common end of relay 2
23
NC 3
Relay 3 normally
closed pin
Can be paired with common end of relay 3
24
COM 3
Common end of relay
3
Can be paired with other pins of relay 3
25
NO 3
Relay 3 normally
open pin
Can be paired with common end of relay 3
26
NC 4
Relay 4 normally
closed pin
Can be paired with common end of relay 4
27
COM 4
Common end of relay
4
Can be paired with other pins of relay 4
28
NO 4
Relay 4 normally
open pin
Can be paired with common end of relay 4
LED
1
AI 1
Analog input channel
1 indication
Green LED, large enough input (≥0.5mA) lights up
2
AI 2
Analog input channel
2 indication
Green LED, large enough input (≥0.5mA) lights up
3
AI 3
Analog input channel
3 indication
Green LED, large enough input (≥0.5mA) lights up
4
AI 4
Analog input channel
4 indication
Green LED, large enough input (≥0.5mA) lights up
5
DI 1
switch input channel
1 indication
Green LED, lights up when DI 1 and DIG are shorted
6
DI 2
switch input channel
2 indication
Green LED, lights up when DI 2 and DIG are shorted
7
DI 3
switch input channel
Green LED, lights up when DI 3 and DIG are shorted

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 10
3 indication
8
DI 4
switch input channel
4 indication
Green LED, lights up when DI 4 and DIG are shorted
9
DO 1
Relay 1 output
indication
Green LED, lights up when NO 1 and COM 1 close
10
DO 2
Relay 2 output
indication
Green LED, lights up when NO 1 and COM 1 close
11
DO 3
Relay 3 output
indication
Green LED, lights up when NO 1 and COM 1 close
12
DO 4
Relay 4 output
indication
Green LED, lights up when NO 1 and COM 1 close
13
NET
Network indication
Yellow LED, Constantly bright after entering network
14
DATA
Serial data indication
Yellow LED, Lights up when the RS485 interface has
data transmission (blinking)
15
WORK
Work/Reset
indication
Yellow LED,Regular blinking / quick blinking after
successful reset
16
PWR
Power indication
Red LED, Constantly bright
Note: Grounding: It is recommended to connect the case to the ground
2.3 Reload button description
Long press 5S is valid, after the reset is successful, the WORK led blinks quickly, and the Modbus
device address, RS485 serial port baud rate and parity bit are restored to the factory settings.
3. Modbus
3.1 Register Address Table
Register Address Table(Function code: 0x01H、0x05H、0x0FH、0x03H、0x06H、0x10H)
Register
address
Number of
registers
Register properties
Register
type
Register value
range
Function code
supported
00017
(0x0010)
1
DO1 switch output
Read/Write
0x0000 or
0xFF00(0x05
function code)
0-1(0x01、
0x0F function
code)
0x01
0x05
0x0F
00018
(0x0011)
1
DO2 switch output
Read/Write
00019
(0x0012)
1
DO3 switch output
Read/Write
00020
(0x0013)
1
DO4 switch output
Read/Write
Reserve
10017
(0x0010)
1
DI1 switch intput
Read only
0-1
0x02
10018
(0x0011)
1
DI2 switch intput
Read only

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 11
10019
(0x0012)
1
DI3 switch intput
Read only
10020
(0x0013)
1
DI4 switch intput
Read only
30017
(0x0010)
1
AI1 input value,unit
(uA)
Read only
0-20000
0x03
0x04
30018
(0x0011)
1
AI2 input value,unit
(uA)
Read only
30019
(0x0012)
1
AI3 input value,unit
(uA)
Read only
30020
(0x0013)
1
AI4 input value,unit
(uA)
Read only
Reserve
40049
(0x0030)
1
DI1 Pulse counting
value
Read only
0-65535
0x03
40050
(0x0031)
1
DI2 Pulse counting
value
Read only
0-65535
40051
(0x0032)
1
DI3 Pulse counting
value
Read only
0-65535
40052
(0x0033)
1
DI4 Pulse counting
value
Read only
0-65535
Reserve
40065
(0x0040)
1
DI1-DI4 Pulse
counting to zero
Write only
0x00 - 0x0F
0x06
Reserve
40078
(0x004D)
1
Device address
Read/Write
1 - 247
0x03
0x06
0x10
40079
(0x004E)
1
Baud rate
Read/Write
0 - 7
40080
(0x004F)
1
Parity bit
Read/Write
0 - 2
40081(0x005
0)
1
Master or slave
mode
Read/Write
0 - 1
40082
(0x0051)
1
Automatic reporting
of switch quantity
Read/Write
0 - 2
40083
(0x0052)
1
switch output time
setting (ms)
Read/Write
300-65535
40084(0x005
3)
1
Analog quantity
range setting
Read/Write
0 - 1
40085
(0x0054)
1
switch quantity
restart output state
setting
Read/Write
0x00 - 0x10
Reserve
40100
(0x0063)
22
Server IP or
domain name
(domain name is
ASCII)
Read/Write
--
0x03
0x06
0x10
40122
(0x0079)
1
Server port
Read/Write
1 - 65535
40123
(0x007A)
1
Protocol type
(UDP、TCP)
Read/Write
0 - 1
40124(0x007
B)
22
User defineddd
package
Read/Write
--
40146(0x009
1)
1
Registration
package
mechanism
Read/Write
0 - 4
40147(0x009
2)
22
Heartbeat package
Read/Write
--
40169
(0x00A8)
1
Heartbeat package
time
Read/Write
0 - 65535
40170
1
Cloud transparent
Read/Write
0 - 1

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 12
(0x00A9)
transmission
40171
(0x00AA)
11
IMEI value
Read only
--
0x03
40182
(0x00B5)
11
SN value
Read only
--
40193
(0x00C0)
20
LBS
Read only
--
Reserve
40300(0x012
B)
1
Version number
Read only
--
0x03
3.2 Modbus address table
Modbus address table
1 (default)
1
2
2
3
3
…
…
245
245
246
246
247
247
3.3 RS485 Serial port baud rate value table
Serial port baud rate value table
0
1200
1
2400
2
4800
3 (default)
9600
4
19200
5
38400
6
57600
7
115200
3.4 RS485 Serial port parity bit value table
Serial port parity bit value table
0 (default)
No parity
1
Even parity
2
Odd parity
3.5 Configure parameters through the host computer
Select “Parameter Setting” to read parameters and write parameters. For specific functions, see the
product function description below.

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 13
4. Function
4.1 Working mode
The working mode is master mode and slave mode, configured by Modbus register 40081
(0x0050). When the register value is 0, it is in master mode; when the register value is 1, it is slave
mode, the default slave mode.
4.1.1 Slave mode
In slave mode (register value 0x01), the data sent to the device by the network or 485 bus (sender)
conforms to Modbus RTU, Modbus TCP protocol, and the address in the data is the device address,
and the device will reply with the same protocol. If the data sent by the network or 485 bus to the
device does not comply with the Modbus RTU, Modbus TCP protocol, or even if the Modbus RTU and
Modbus TCP protocols are met, but the data address is not the device address, the data will be
discarded.
In the slave mode, the device can directly connect to the device in the master mode through the
485 bus. When the slave is not connected to the network, the network can also access the data of the
slave through the master.

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 14
4.1.2 Master mode
In Master mode (register value is 0x00), the data sent by the network or 485 bus (sender) to the
device conforms to the Modbus RTU, Modbus TCP protocol, and the address in the data is the device
address, and the device responds to the sender with the same protocol. If the data sent by the
network or 485 bus to the device does not comply with the Modbus RTU, Modbus TCP protocol, or
even if the Modbus RTU and Modbus TCP protocols are met, but the data address is not the device
address, the data transmitted from the 485 bus will be transmitted to the network, the data transmitted
from the network will be transmitted to the network 485 bus.
This function of the host mode enables device cascading and data transfer between the 485 bus
and the network.

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 15
4.2 IO basic function
4.2.1 switch DO output
Read switch DO output
Function code: 01, Read coil state
Address range:00017(0x0010)~00020(0x0013)
Note: When the device relay is passively output, and the coil is not power on, the NC and COM of
the relay are normally closed, the NO and the COM are normally open, the value is 0; when the coil is
power on, the phenomenon is reversed, the relay NC and COM are disconnected, the NO and the
COM are closed, and the value is 1. The relay state can be queried by command.
For example:
When reading the 4-channel switch output state, assume that the return value is 03,
corresponding to the binary bit 0000 0011, the lower four bits represent the switch output state, which
in turn is DO4, DO3, DO2, DO1.
Modbus RTU protocol read switch output:
Send
01
01
00 10
00 04
3C 0C
Device
ModBus
address
Function
code
Start address
Read number of
switch quantity
CRC code
Receive
01
01
01
03
11 89
Device ModBus
address
Function
code
Bytes returned
Switch Output
Value
CRC code
Modbus TCP protocol read switch output:
Send
00 01
00 00
00 06
01
01
00 10
00 04
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Start address
Read number
of switch
quantity
Receive
00 01
00 00
00 04
01
01
01
03
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Bytes returned
Switch Output
Value

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 16
Control switch quantity DO output
Function: 05,Write a single coil state, 0F, Write multiple coil states
Address range: 00017(0x0010)~00020(0x0013)
Note: When the device relay is passively output, and the coil is not power on, the NC and COM of
the relay are normally closed, the NO and the COM are normally open; when the coil is power on, the
phenomenon is reversed, the relay NC and COM are disconnected, the NO and the COM are closed,.
The state of relay can be controlled by command.
For example:
Function code 0x05 writes DO2 switch output, making NC2, COM2 disconnect, NO2, COM2
close, writing value FF 00; making NC2, COM2 close, NO2, COM2 disconnect, writing value 00.
Modbus RTU protocol write switch output:
Send
01
05
00 11
FF 00
DC 3F
Device ModBus
address
Function
code
Switch quantity
address
Write value
CRC code
Receive
01
05
00 11
FF 00
DC 3F
Device ModBus
address
Function
code
Switch quantity
address
Write value
CRC code
Modbus TCP protocol write switch output:
Send
00 01
00 00
00 06
01
05
00 11
FF 00
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Start address
Read number
of switch
quantity
Receive
00 01
00 00
00 06
01
05
00 11
FF 00
Transmis
sion
identifier
Protocol
identifier
Length
Unit
identifier
Functi
on
code
Start address
Read number
of switch
quantity
Function code 0x0F writes DO2, DO3 switch output, making NC2, COM2 disconnected, NO2,
COM2 closed; making NC3, COM3 disconnected, NO3, COM3 closed. Write value should be 0x03,
corresponding to binary bit 0000 0011
Modbus RTU protocol write switch output:

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 17
Send
01
0F
00 11
00 02
01
03
62 95
Device
ModBus
address
Function
code
Switch
quantity
address
Write
number of
switch
quantity
Bytes
Write
value
CRC
code
Receive
01
0F
00 11
00 02
84 0F
Device ModBus
address
Function
code
Switch
quantity
address
Write value
CRC code
Modbus TCP protocol write switch output:
Send
00 01
00 00
00
08
01
0F
00 11
00 02
01
03
Transm
ission
identifie
r
Protoco
l
identifie
r
Len
gth
Unit
identifier
Funct
ion
code
Switch
quantity
address
Write
number of
switch
quantity
Bytes
Write
value
Recei
ve
00 01
00 00
00
06
01
0F
00 11
00 02
Transm
ission
identifi
er
Protoc
ol
identifi
er
Leng
th
Unit
identifier
Funct
ion
code
Switch quantity
address
Write number of
switch quantity
4.2.2 Read switch quantity DI input
Function: 02, Read switch quantity input state
Address range: 10017(0x0010)~10020(0x0013)
Note: The device default dry contact input. When DI and COM are shorted, the read value should
be 1; when DI and COM are not shorted, the read value should be 0.
For example:
Reading 4 channel switch input value, DI1 and COM1 are shorted, DI2 and COM2 are not shorted,
DI3 and COM3 are shorted, DI4 and COM4 are not shorted. The input switch value is 0x05,
corresponding to the binary bit 0000 0101, and the lower four bits represent the switch input value,
which are in turn DI4, DI3, DI2, DI1.
Modbus RTU protocol read switch input:

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 18
Send
01
02
00 10
00 04
78 0C
Device ModBus
address
Function
code
Start address
Write number of
switch quantity
CRC code
Receive
01
02
01
05
61 8B
Device ModBus
address
Function
code
Bytes returned
Write value
CRC code
Modbus TCP protocol read switch input:
Send
00 01
00 00
00 06
01
02
00 10
00 04
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Switch quantity
address
Write number
of switch
quantity
Receive
00 01
00 00
00 04
01
02
01
05
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Bytes returned
Write value
4.2.3 Read analog quantity AI input
Function code: 03, Read holding register; 04, Read input register
Address range: 30017(0x0010)~30020(0x0013)
Note: Input unit is uA
For example:
Function code 0x03, read AI1 input, assuming AI1 input is 9946uA, the corresponding value
should be 0x0x26DA.
Modbus RTU read analog quantity input:
Send
01
03
00 10
00 01
85 CF
Device ModBus
address
Function
code
Start address
Write number of
switch quantity
CRC code
Receive
01
03
02
26 DA
23 BF
Device ModBus
address
Function
code
Bytes returned
Write value
CRC code
Modbus TCP read analog quantity input:
Send
00 01
00 00
00 06
01
03
00 10
00 01

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 19
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Analog quantity
address
Write number
of analog
quantity
Receive
00 01
00 00
00 05
01
03
02
26 DA
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Bytes returned
Write value
Function code 0x04, read AI1 input, assuming AI1 input is 9946uA, the corresponding value
should be 0x0x26DA
Modbus RTU read analog quantity input:
Send
01
04
00 10
00 01
30 0F
Device ModBus
address
Function
code
Start address
Write number of
switch quantity
CRC code
Receive
01
04
02
26 DA
22 CB
Device ModBus
address
Function
code
Bytes returned
Write value
CRC code
Modbus TCP read analog quantity input:
Send
00 01
00 00
00 06
01
04
00 10
00 01
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Analog quantity
address
Write number
of analog
quantity
Receive
00 01
00 00
00 05
01
04
02
26 DA
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Bytes returned
Write value
4.2.4 Analog quantity input AI range setting
When register 0x40084(0x0053)is 0, analog quantity input range is 0 -- 20mA;
When register 0x40084(0x0053)is 1, analog quantity input range is 4 -- 20mA;

Wireless Data Transceiver E850-DTU(4440-GPRS) datasheet
Copyright ©2012–2018,成都亿佰特电子科技有限公司 20
4.3 IO special function
4.3.1 Pulse count and count clear to zero
The pulse count will not be saved after power off, and the pulse level maintenance time must be
more than 10ms to be effective. The switch input changes from the disconnected state to the closed
state and maintains the closing time of 10ms or more, and then becomes to disconnected state,
completing a pulse count.
Read pulse count value
Function code: 03,Read hoding register
Address: 40049 (0x0030)~40052 (0x0033)
Note: The maximum value of the pulse count is 65535
For example:
DI1 has detected 16 pulses at present, DI2 has detected 3 pulses at present, and reads DI1 and
DI2 switch input count values.
Modbus RTU protocol read pulse count value:
Send
01
03
00 30
00 02
C4 04
Device ModBus
address
Function
code
Start address
Read number
CRC code
Receiv
e
01
03
04
00 10
00 03
BB F7
Device ModBus
address
Function
code
Bytes
returned
DI1 count
value
DI2 count
value
CRC code
Modbus TCP protocol read pulse count valu:
Send
00 01
00 00
00 06
01
03
00 30
00 02
Transmi
ssion
identifie
r
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Start address
Read number
Receiv
e
00 01
00 00
00 07
01
03
04
00 10
00 03
Transmis
sion
identifier
Protocol
identifier
Length
Unit
identifie
r
Functi
on
code
Bytes
returned
DI1 count
value
DI2 count
value
Clear to zero pulse count value
Function code: 06,Writing hoding register
This manual suits for next models