echoflex E-DOC-C-SR User manual

Echoflex Installation Guide
Elaho Dual Tech Ceiling-mount Occupancy
Corporate Headquarters nMiddleton, WI, USA|+1 608 831 4116
©2023 Echoflex Solutions, Inc. |Trademark and patent info: echoflexsolutions.com/ip
Third-party license agreement info:etcconnect.com/licenses |Product information and specifications subject to
change.Echoflexintends this document to be provided in its entirety.
8186M2183RevCReleased2023-06
Overview
The Elaho Dual Tech Ceiling-mount Occupancy Sensor uses passive
infrared (PIR) technology and acoustic detection to provide reliable
occupancy and vacancy sensing for lighting control.
The ceiling-mount sensor offers 360 degree coverage with optimized lens
options to accommodate small spaces, large spaces, and spaces with high
ceilings.
Model Coverage m2Coverage ft2
E-DOC-C-SR
SmallRoom
41.8m2at2.4m 450ft2at8ft
74.3m2at 6.7m 800ft2at 12ft
E-DOC-C-LR
LargeRoom
167m2at 2.4m 1,800ft2at 8ft
279m2at 6.7m 3,000ft2at 12ft
E-DOC-C-HC
HighCeiling
28m2at 2.4m 300ft2at 10ft
650m2at 12.2m 7,000ft2at 40ft
Field-installed lens masks are provided to allow customized detection
fields for each sensor lens type.
Custom Configuration
This document guides you through the installation and local DIP switch
setup of the sensor. For more detailed information about custom
configuration options available using ElahoAccess, see the ElahoAccess
App integrated help system.
Note:
To use the configuration settings applied using
ElahoAccess, DIP switch 2 must be enabled. See DIP Switches on
page7.

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Prepare for Installation
Ceiling-mount sensors are intended for installation to a finished ceiling
surface, soft ceiling tile mounted, or attached to a round or octagonal
fixture junction box.
Compliance
• cULus Listed
• CE compliant
For use with Echoflex Elaho Control Systems, powered by an Elaho station
power supply.
Environment
Ambient
For indoor, commercial controls use only. Operating temperature
0°C–40°C (32°F–104°F), humidity maximum 90%(non-condensing).
Location
Echoflex recommends paying special attention to the installation
environment:
• When operating in PIR only modes, the sensor must have an
unobstructed view of the room. Do not mount behind or near tall
cabinets, shelves, hanging light fixtures, etc.
• Do not install the sensor within eight feet from an HVAC airflow
duct/vent.
• Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms. If the installation location cannot avoid these
conditions, portions of the lens can be masked to block the sensor
view of these undesired areas. See
Lens Masking on page10
.
Note:
In areas of increased noise activity, enabling PIR only mode
may allow for better detection results. See DIP Switches on page
7.
Dual Tech Occupancy Sensor Page 2 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Wire Specification
The Dual Tech Occupancy Sensor connects to the EchoConnect
communication bus. EchoConnect is a bi-directional protocol that uses
one pair of wires (data+ and data–) for both data and power. Echoflex
recommends using Belden 8471 Class 2 wire (or approved equal – see the
Echoflex cable cross database echoflexsolutions.com/files/Elaho_Data_
Cable_Wire_Specs for equal alternatives). The total combined length of
an EchoConnect wire run using Belden 8471 may not exceed 500m
(1,640ft), with a maximum distance of 400m(1,312ft) between any two
devices.
Note:
All control wiring should be installed and terminated by a
qualified installer and should follow standard wiring installation
practices. Leave approximately 25.4cm (10in) of wiring in the
back box for connection and to allow slack for future service
needs.
Note:
Echoflex requires that all stations and devices be grounded
for ESDprotection. Pull an additional 2.5 mm2(14AWG) wire for
grounding when control wires are not installed in grounded metal
conduit.
Note:
When using Category 5 (or equivalent) cable on the
EchoConnect communication bus, please note the following:
• Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kits and must be installed using a bus topology.
Refer to the instructions provided with the Cat5 Termination
Kit (8186A1207) for information to terminate Cat5 wiring.
• Not all topologies are supported using Cat5; careful
planning is required to ensure the proper termination kits
are available and the wire is pulled appropriately.
Supplies
The following supplies are provided with the sensor:
• Soft ceiling tile adapters
• 2 each mounting screws, 6-32x3/4in and 6-32x1 3/4in
• Lens masks
• WAGO connectors, 3-position
Dual Tech Occupancy Sensor Page 3 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Installation
Note:
Installation must follow all national and local codes for
electrical equipment. NEC Class 2 product to be wired in
accordance to NEC Article 725 and local jurisdiction requirements.
The ceiling-mount sensor is provided with a mounting plate that can be
mounted to a junction box, finished ceiling, or soft ceiling tile. Determine
the installation method and follow the detailed instructions:
•
Junction Box or Surface Installation below
•
Soft Ceiling Tile Installation on the facing page
Junction Box or Surface Installation
1. Pull the Belden 8471 (or
equivalent) and one 2.5mm2
(14AWG) ground wire to the
mounting location (junction
box or finished surface). Strip
each wire 11mm (7/16in).
2. Temporarily remove the sensor
cover to gain access to the
configuration switches and
mounting access holes. Hold
the sensor in one hand while
gently twisting the cover
clockwise.
3. Connect the EchoConnect
wires from the sensor to the
installed wires.
a. Connect the data–EchoConnect wire(black) from sensor to the
incoming data– EchoConnect wire (typically black) using a
WAGO wire termination connector.
b. Repeat the above step for the data+EchoConnect wire(white)
and again for the ESD ground wire (green/yellow), using a new
WAGO connector for each termination type.
4. Orient the flat side of the sensor to the junction box or surface and
secure it in place using the screws provided (both short and long
screws are provided for installation convenience).
Dual Tech Occupancy Sensor Page 4 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Soft Ceiling Tile Installation
Ceiling tile
adapter Ceiling tile
Ceiling tile adapter
1. Pull the Belden 8471 (or equivalent) and 2.5mm2(14AWG) ground
wire to the mounting location. Strip each wire 11mm(7/16in).
2. Temporarily remove the sensor cover to gain access to the
configuration switches and mounting access holes. Hold the sensor
in one hand while gently twisting the cover clockwise.
3. Prepare the ceiling tile.
a. Align the flat side of the sensor to the finished side of the
ceiling tile and mark the center access hole for wire pass-
through.
b. Remove the ceiling tile material from marked access hole.
c. Pull all incoming wires through the access holes of the ceiling
tile.
4. Secure the sensor in place.
a. Insert the soft ceiling tile adapters through the provided
pinholes on the sensor, one set located on each side of the
sensor near the mounting keyholes.
b. Push the adapters through the ceiling tile, and then bend each
tine over in opposite directions for a secure fit.
5. Connect the EchoConnect wires from the sensor to the installed
wires.
a. Connect the data– EchoConnect wire (black) from sensor to the
incoming data– EchoConnect (typically black) wire using a
WAGO wire termination connector (provided).
b. Repeat the above step for the data+ EchoConnect wires (white),
and again for the ESD ground wires (green/yellow). Use a new
WAGO connector for each termination type.
Dual Tech Occupancy Sensor Page 5 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Settings
DIP switches
Space and Address
switches
The Elaho Dual Tech
Ceiling-mount
Occupancy Sensor
participates in an
Elaho control system
using the configured
Space and Address,
which are selectable
using the rotary
switches on the
sensor electronics located behind the removable cover.
DIP switches and the [MODE] button, also located on the sensor
electronics, set the sensor functionality and the occupancy detection
action when set to Basic configuration mode. See
Configuration on
page8
.
Note:
When the sensor is placed into Custom configuration
mode, DIP switch 2 set to On, all other DIP switch and Mode
button settings are ignored.
Set Space and Address
Two rotary switches on the sensor electronics provide for Space and
Address assignment for the sensor. By default, these switches are set to
Space1, Address1. Commands are shared by all devices within a given
space.
1. Set the Space rotary switch to the desired number (1 through 16)
for the space you want the sensor to control.
2. Set the Address rotary switch to desired address (1 through 16) for
the sensor identification in the selected space.
Note:
Do not duplicate a device Address within the same Space.
Dual Tech Occupancy Sensor Page 6 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
DIP Switches
DIP switches on the sensor electronics provide for additional
configuration options including Use Custom Config, Vacancy Timeout,
Enable/Disable detection LEDs, PIR Only Mode, and the ability to restore
the sensor to its factory defaults.
Switch # Use
1Unused (leave Off)
2Enable/Disable Custom Config Mode
• When “Custom Config” is set to On (the default
setting), all other local DIP switch settings are
ignored. Instead, the settings made by the
ElahoAccess App are used.
• When “Custom Config” is set to Off, also known as
Basic configuration mode, the local DIP switch
settings for Vacancy Timeout, Enable PIR LED, and
dual technology features are used. Sensor actions
can be adjusted using the program [MODE] button.
See
Configuration on page 8
.
3 and 4 Vacancy Timeout
• 5 min = Switches 3 and 4 are Off
• 15 min = Switch 3 is Off and Switch 4 is On (default)
• 30 min = Switch 3 is On and Switch 4 is Off
• Auto = Both switches are On
5Detection LEDs
• When set to On (the default setting), the occupancy
detection LEDs illuminate when movement is
detected.
• When set to Off, the occupancy detection LEDs are
disabled unless the unit is in Walk Test mode.
6PIR Only Mode
• When set to On, acoustic detection technology is
disabled for the sensor.
• When set to Off (the default setting), both PIR and
acoustic detection technologies are used by the
sensor.
7Unused (leave Off)
8Restore to Defaults at boot
• When set to On and power is cycled to the sensor,
the unit restores to its factory default settings.
• Off is the default setting.
Dual Tech Occupancy Sensor Page 7 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Power Up
All EchoConnect terminations in the system must be made before
applying power to the system and sensor. When the sensor is powered,
the PIR and acoustic detection LEDs illuminate for one minute for
calibration and warm-up, and then return to normal operation according
to the configuration.
Both the PIR and acoustic detection features of the sensor will
automatically adjust the sensitivity threshold to eliminate nuisance
tripping. During this time, configuration is not allowed and no events are
triggered.
Configuration
Basic
MODE button
and LED
AUXILIARY
button
and LED
A sensor that is set for Basic
configuration mode
(DIPswitch 2 set to Off) can be
further configured locally
using the other available
DIPswitch settings, and the
[MODE] and Auxiliary [A]
buttons and their associated
LEDs.
Custom
A sensor that is set for Custom configuration mode (DIPswitch 2 set to
On, the default setting) can be customized using the ElahoAccess App.
For more detailed information about custom configuration options
available, see the ElahoAccess App integrated help system.
Preset
While in Basic configuration mode (DIPswitch 2 set to Off), use the
[MODE] and Auxiliary [A] buttons to program the preset that is activated
with an occupancy detected state change. By default, this is Preset1.
When vacancy is detected, the default action event is Off.
Follow these steps to configure the preset for your sensor:
1. Access the sensor electronics and press and hold the [MODE]
button for three seconds to enter “Program Mode.” The Mode LED
lights in amber to indicate the sensor is in Program Mode and the
Auxiliary LED flashes to indicate the preset number controlled by
the occupancy action. By default, this is Preset 1, therefore the LED
will flash one time, pause two seconds and flash again.
Dual Tech Occupancy Sensor Page 8 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
2. Press and release the Auxiliary [A] button the number of times that
corresponds to the preset that you want to use. For example, press
the [A] button eight times to set Preset 8. The LED flashes the
number of the preset used.
3. Press and release the [MODE] button to save the current setting.
Operation
Dual Technology
When both PIR and acoustic detection are used, the following logic is
used:
• When the space is vacant, PIR detection and manual control can
switch the state to occupied.
• When the space is occupied, PIR, acoustic detection, and manual
control can reset the vacancy timeout.
• When occupancy in the space has only been triggered by acoustic
detection for 60 minutes, acoustic detection is disabled until the
next PIR detection event.
PIR (only) Detection
When acoustic detection is disabled (DIP switch 6 set to On), the
following logic is used:
• When the space is vacant, PIR detection and manual control can
switch the state to occupied.
• When the space is occupied, PIR detection and manual control can
reset the vacancy timeout.
Vacancy Timeout
Vacancy timeout is the amount of time the sensor waits to take action
after no movement is detected. By default, vacancy timeout is set to 15
minutes (indicated by DIP switch 3 set to Off and 4 set to On; see
DIP
Switches on page 7
). When the vacancy timeout ends, the grace period
begins.
When the sensor detects vacancy, the vacancy timeout period begins. If
the sensor does not detect occupancy again during the vacancy timeout
period, the lights turn off and a 30 second grace period begins.
Grace Period
The sensor features a 30 second grace period after a vacancy timeout
occurs. During this grace period, if the sensor detects occupancy, it will
turn on or restore the previous lighting condition.
Auto Vacancy Timeout
The “Auto” vacancy timeout setting varies the vacancy timeout between
5 and 30 minutes depending on how often it identifies an occupancy
trigger after a vacancy timeout occurs (during the grace period).
Dual Tech Occupancy Sensor Page 9 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Walk Test
The sensor offers a Walk Test mode, which shortens the vacancy timer to
10seconds and allows for simple and quick verification of the sensor’s
coverage and range in the installed space.
[Walk Test]
1. Prepare the site for configuration.
a. Make certain the sensor and lighting loads are powered and
connected for control by the Elaho control system.
b. You will need direct access to the sensor in order to place it into
Walk Test mode.
2. Press the [Walk Test] button on the sensor to enable the Walk Test
feature. A green LED flashes, indicating Walk Test is enabled and
the vacancy timer is shortened to 10seconds.
3. Move throughout the space, including corners and areas that may
be obscured from line of sight to the sensor. Each time the sensor
detects movement, the lens illuminates red. If acoustic detection is
enabled, any sound detected illuminates the lens green.
4. Adjust the lens masking, if installed, blocking certain areas of the
installed space from sensor detection. See
Lens Masking below
.
5. Walk Test mode automatically exits and the sensor returns to
normal operation after five minutes. You can also manually
terminate by pressing the [Walk Test] button again.
Lens Masking
Lens masks are provided in the packaging for your convenience. Use this
to block a section of the lens from detecting occupancy. To attach, cut to
the desired size, remove the backing and stick it on the sensor lens,
covering the desired sections.
Dual Tech Occupancy Sensor Page 10 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Sensor Coverage
Small Room Lens
Side View
0
0
1.5 m
5 ft
1.5 m
5 ft
3.0 m
10 ft
3.0 m
10 ft
4.6 m
15 ft
4.6 m
15 ft
6.1 m
20 ft
6.1 m
20 ft
8 ft
2.4 m
10 ft
3.0 m
12 ft
3.7 m
Large RoomLens
Side View
0
8 ft
2.4 m
10 ft
3.0 m
12 ft
3.7 m
0
3.0 m
10 ft
3.0 m
10 ft
6.1 m
20 ft
6.1 m
20 ft
9.1 m
30 ft
9.1 m
30 ft
12.2 m
40 ft
12.2 m
40 ft
High Ceiling Lens
Side View
0
3.0 m
10 ft
3.0 m
10 ft
6.1 m
20 ft
6.1 m
20 ft
9.1 m
30 ft
9.1 m
30 ft
12.2 m
40 ft
12.2 m
40 ft
0
12.2 m
40 ft
9.1 m
30 ft
6.1 m
20 ft
Dual Tech Occupancy Sensor Page 11 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Occupancy Sensor
Dual Tech Occupancy Sensor Page 12 of 12 Echoflex