Ecolab MU421-P Mounting instructions

Software Manual
Control Panel for Hybrid Units
Models:
MU421-P
MU422-P
BW4-P
BW7-P
BF4-P
BF8-P
Software Manual
EN


3
110007941
Software Manual
1. Description 3
2. DISPLAY LAYOUT 4
3. MODES 5
3.1 Power On 5
3.2 Standby 5
3.3 Run Mode 6
3.3.1 Single Booster with high and low pressure 6
3.4 Power O 7
3.5 Error Mode 7
4. CONTENT OF MAIN- AND SUBMENUS 8
5. OVERVIEW OF MAIN- AND SUB-MENUS 9
5.1 Content of the Info menu 10
5.2 Content of the Errors menu – CAUSE & REMEDY 11
5.2.1 Error List 11
5.3 Content of the Setup sub menu Settings 13
5.4 Content of Setup menu 14
5.4.1 Submenu Language & Units 16
5.4.2 Submenu Supply tank 16
5.4.3 Submenu Communication 17
5.4.4 Submenu Settings 17
5.4.5 Submenu Installation 17
5.4.6 Submenu Reset 17
5.5 Content of Readings 18
6. UPGRADE FIRMWARE 19
6.1 Upgrade display using USB Cable 19
6.2 Upgrade display using IrDA Cable 21
6.3 Upgrade Inverter 23

4
110007941
Software Manual
1. Description
This software manual describes the operation of the control panel of the advanced Single Booster
unit (SB and SBHL).
The advanced SB unit is operated via the control panel (see below illustration).
1. OFF
Button (1) switches OFF the unit.
2. ON/STANDBY
Button (2) switches ON the unit.
3. ERROR
Error light indicator (3).
4. NAVIGATION BUTTONS
The four ”arrow” navigation buttons (4)
are used for navigation in the display
menu. Pressing the ”OK” button
activatesthemenuandconrmsany
activity displayed.
5. DISPLAY
1
2
3
45

5
110007941
Software Manual
2. Display layout
Example:
pressure: 25 bar
Standard
ER
pressure: 25 bar
Standard
ERA +
-
OK
(1)
When switched on the display will show an arrow symbol in the top right corner equivalent to the
active navigation buttons on the control board.
The arrows illustrate that it is possible to scroll up and down between the menus. Scrolling to the
right makes it possible to enter a value. Set the value scrolling up (+) or down (-) to set the value
higherorloweraccordingly.Conrmbypressingok.
(2)
A letter combination for easy reference in connection with service work will appear in the top right
corner of the display.
(2)
(1)

6
110007941
Software Manual
3. Modes
3.1 Power On
Theveryrsttimetheunitisswitchedon,werecommendsettingdateandtimeintheSetup
menu,settings,displayEP.Ifdateandtimeisnotset,dateandtimewillcountfromthepre-set
default date and time.
2006-01-01 12:00
Date & time
EP
Set date and time using navigation buttons.
Set date & time
2006-01-01 12:00
ConrmbypressingOKbutton.
3.2 Standby
The start up display will look as the one below.
Display for SB model with High- and Low pressure - Select either HP or LP using arrows up & down.
ECOLAB
Pegasus 12:00:00

7
110007941
Software Manual
3.3 Run Mode
3.3.1 Single Booster with high and low pressure
The following screen displays will appear when the unit is in Run Mode.
Screen display for High pressure unit in Run Mode.
Scroll down to return to STANDARD pressure.
Screen display STANDARD pressure.
Scroll up to choose HP and scroll down to choose LP.
Screen display for Low Pressure unit in Run Mode.
Scroll up to return to STANDARD pressure.
Please note that you will remain in HIGH or LOW pressure Run Mode until otherwise is
selected.
STANDARD (25 bar)
P=0 BAR
T=0 °C
HPSP
HIGH (25 bar)
P=0 BAR
T=0 °C
SP
LOW (12 bar)
P=0 BAR
T=0 °C
SP

8
110007941
Software Manual
3.4 Power O
Whentheunitisothedisplaywillonlyshowasmalldotinthetoprightcorner.
InOmodeitispossibletoaccessallmenuswithoutthepumprunningbypressingthe
OK button on the panel.
DotisequivalenttotheOKconrmbuttononthepanel.
3.5 Error/Warning
ERROR
WARNING
Incaseofanerror,“ERROR”willappearonthedisplayscreen.
Press the OFF button to switch of unit.
IftheerrorremainswhentheunitisswitchedONagain,pleasePressrightarrowtosee
current error.
Incaseofawarning,“WARNING”willappearonthedisplayscreen.Whenawarningis
detected the machine will either stop or run with limited performance until the cause of
the warning has been improved (eg. inlet pressure).
To see further error/warning list and possible cause and remedy go to section 5.2.

9
110007941
Software Manual
4. Content of Main- and Submenus
The control panel contains the below main menu screen displays.
Scroll between the menus using the navigation buttons.
Each main menu contains submenus which will be described subsequently.
Info
i
A
Errors
B
Readings
R
Setup
C

10
5. Overview of Main- and Sub-menus
110007941
Software Manual
1. Info (A)
1 ΣCounterstotal(AA)
2 ΣCounterstrip(AB)
3 Service center(AD)
4 Machine info (AE)
2. Errors (B)
3. Setup (C) (default password 6802)
1 Password (CA)
2 Settings (E)
Post run time (ED)
Dry run level (EE)
Standard pressure (ER)
High pressure (EA)
Low pressure (EB)
Startup method (EY)
Pressure start level(EX)
Startup delay (EW)
Quick Start level (EC)
Autoodelay(EZ)
Accelleration time (EU)
Date & Time (EP)
Service text (EJ)
Inverter power (EO)
Backlight intensity (EI)
Display contrast (EV)
User password (EL)
Standard settings (EK)
3 Languages & units (F)
Language (FA)
Units (FB)
4 Supply Tank (H)
Tank control OFF (HA)
LLA Detect Delay (HB)
5 Communication (I)
Firmware Upgrade by cable (IC)
Firmware Upgrade by infrared (ID)
6. I/O Settings (J)
Output 1 (JA)
Output 2 (JB)
Input (JC)
7. Installation (K)
Install password (KA)
8 Resets (D)
Reset trip counters(DA)
4. Readings (R)
Pump state (RA)
Outlet pres. (RB)
Water temp (RC)
Supply pressure (RD)
Flow Status (RF)

11
110007941
Software Manual
5.1 Content of the Info menu
Please note that the Info menu is only for display – all data must be typed in via the setup menu!
Info
i
A
total
ΣCounters
AA
ΣTOTAL
ΣPower 0kWh
ΣHours 0h
AAA
Displays accumulated consumption of power and
operation hours.
trip
ΣCounters
AB
ΣTRIP
ΣPower 0kWh
ABA
ΣHours 0h
Displays accumulated consumption of power and
operation hours.To reset the trip counter go to the setup
menu.
Service center
AD
SERVICE ADA
Enter TEXT HERE
Displays name and tel. no. of service technician.
Machine info
AE
DisplaysSoftwareversionandPumpsize,machine
congurationandinvertersoftwareversion.
This display view is only
mentasanexample,SWID
and CT ID shows the cur-
rent SW version.
INFO
HW ID:HYBRID
CT ID:1.01
AEA
SW ID:5.02 5-14

12
110007941
Software Manual
5.2 Content of the Errors menu – CAUSE & REMEDY
Example of Error log screen display:
All error occurrences will be stamped with date and time.
E indicates Error number. P indicates Pump number.
E0\P1
2006-01-01 12:00
C1 Inverter
Error
BA
E0\P1
2006-01-01 12:00
C1 Inverter
Error
BA
Theerrorlogstoresupto1000occurrences.Whenmax.memoryisreached,theerrorswillbe
deleted according to ”First in” First out” principle.
5.2.1 Error List
Error Cause Remedy
C1 Inverter
Error
1. Frequency inverter in error state 1.Switchothepowerontheservice
switch. Wait 180 sec. Switch on the unit
again.Iferrorstilloccurs,pleasecontact
your local service technician.
C2 Low Supply
Pressure
1.Insucientwatersupply 1.Securesucientwatersupplypres-
sure.
2.Checkinletlterforimpurities/rinse
lter
3. Contact your local service technician.
C3 High Water
Temp.
1. Water pump top temperature is above 80°
2. Water consumption is too low (pump column has
been overheated)
1. Lower the inlet water temp. (max
70°C)
2.Securesucientwaterconsumption
3. Contact your local service technician.
C4 High Motor
Temp.
1.Insucientcoolingofmotor
2. The ambient temperature is above 40°
1. Secure that all air channels are open
and not blocked by impurities
2. Lower ambient temperature
C5 High Supply
Temp.
1. Water inlet temperature is above 70° 1. Lower the water temp. (max 70°C)
2. Contact your local service technician.
C6 Low Sensor
Supply Voltage
1. Voltage supply for sensors too low 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C7 No Response
Error
1. No communication between display and control
board
1. Contact your local service technician.
C8 Low Tank
Level
1.Insucientwatersupply
2. Water supply valve not open
1. Check correct water supply
2.Securesucientairsupplytovalve
3. Contact your local service technician.
C9 High Tank
Level
1. Water supply valve not closed 1.Securesucientairsupplytothe
valve.
2. Contact your local service technician.
C11 Warning
Cri. Inlet press.
1.Insucientwatersupply
2. Booster will return to standby mode after 20 sec.
If this error occurs 3 times within 20 min. Error C2
occurs.
1.Securesucientwatersupplyorre-
duce consumption
2.Checkinletlterforimpurities/rinse
lter
3. Contact your local service technician.
C13 Warning
Low inlet press.
1.Insucientwatersupply.
Themachinewillkeeponworkingasalways,butthe
maximum speed of the pump will be reduced until
sucientinletpressureispresent.
1.Securesucientwatersupplyor
reduce consuption
2.Checkineltlterforimpurities/Rinse
lter

13
110007941
Software Manual
C14 Warning
leakage start
1.Boosterstartconditionchangedtoow,dueto
leakage in pipe
1. Check for leakage in pipe system.
2.Press“o”button
3.Iferrorreoccurs,contactyourlocal
service technician.
C20 Low Sensor
Signal P-Pump-
top
1.Pressuresignalfrompumptopsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C21 Low Sensor
Signal T-Pump-
top
1.Temparaturesignalfrompumptop,sensor,outof
range
1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C22 Low Sensor
Signal P-Inlet
1.Pressuresignalforminletsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C23 Low Sensor
Signal T-Inlet
1.Temperaturesignalfrominletsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C24 Low Sensor
Signal block
1.Signalfromblocksensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C25 Low Sensor
Signalow
1.Signalfromowsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C30 High Sensor
Signal P-Puump-
top
1.Pressuresignalfrompumptopsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C31 High Sensor
Signal T-Pump-
top
1.Temperaturesignalfrompumptopsensor,outof
range
1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C32 High Sensor
Signal P-Inlet
1.Pressuresignalfrominletsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C33 High Sensor
Signal T-Inlet
1.Temperaturesignalfrominletsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C34 High Sensor
Signal block
1.Signalfromblocksensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C35 High Sensor
Signalow
1.Signalfromowsensor,outofrange 1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C40 Sensor Load
Pumptop Sensor
1. Supply voltage for pumptop sensor too low.
2. Pumptop sensor using too much current
1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C41 Sensor Load
Inlet sensor
1. Supply voltage for inlet sensor too low
2. Inlet sensor using too much current
1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C42 Sensor Load
Block sensor
1. Supply voltage for block sensor too low
2. Block sensor using too much current
1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C43 Sensor Load
Flow sensor
1.Supplyvoltageforowsensortoolow
2. Flow sensor using too much current
1.Press“o”button
2.Iferrorreoccurs,contactyourlocal
service technician.
C45 Inverter
Module temp.
1. Water consumption too high
2. Ambient temperature too high"
1. Lower the load for inverter
2. Lower the ambient temperature"
C46 Inverter
Board temp."
1. Water consumption too high
2. Ambient temperature too high
3. Load at Board high"
1. Lower the load for inverter
2. Lower the ambient temperature
3. lower the load at board"

14
110007941
Software Manual
5.3 Content of the Setup sub menu Settings
TheSetupMainmenucontainsthebelowsubmenus,whichwillbedescribedsubsequently.
Setup
C
0000
Password
CA
Settings
S
E
Languages &
L
F
units
Supply
H
tank
Communication
I
PC
Reset
R
D
I/O Settings
J
Installation
K

15
110007941
Software Manual
5.4 Content of Setup menu
0000
Password
CA
Settings
S
E
Time: 20 sec.
Post run
ED
Time: 20 sec.
Post run
EDA
+
-
OK
Password Note: Default user password is
6802. Enter the settings menu to change the
default password. To avoid unintended access
to the system the your local service technician.
can insert a blocking preventing access to the
password controlled menus.
Set Post run time.
level: 0.5 bar
Dry run
EE
level: 0.5 bar
Dry run
EEA
+
-
OK
Set dry run level.
pressure: 25 bar
Standard
ER
pressure: 25 bar
Standard
ERA
+
-
OK
Set standard pressure.
pressure: 25 bar
High
EA
pressure: 25 bar
High
EAA +
-
OK
Set high pressure.
pressure: 12 bar
Low
EB
pressure: 12 bar
Low
EBA
+
-
OK
Set low pressure.
Startup
Method: Pressure
EY
Method: Pressure
Set Startup
EYA +
-
OK
Pressure Start
Level: 8 bar
EX
Level: 8 bar
Set Pres. Start
EXA +
-
OK
Startup
Delay:10 sec
EW
Delay: 10 sec.
Set Startup
EWA +
-
OK
level: Off
Quick start
EC
level: Off
Quick start
ECA
+
-
OK
Set Quick start level.

16
110007941
Software Manual
Autooff
Delay:OFF
EZ
Delay: OFF
Set auto off
EZA +
-
OK
Accelleration
Ramp: 3 sec
EU
Ramp: 3 sec
Set Acc.
EUA
+
-
OK
2006-01-01 12:00
Date & time
EP
Set date & time
2006-01-01 12:00
Set date and time
SERVICE EJ
Enter TEXT HERE
SERVICE EJA
Enter TEXT HERE
+
OK
-
Enter name and tel. no of Your local service technician.
power: 11000W
Inverter
EO
power: 11000W
Inverter
EOA
+
-
OK
Set rated power of frequency inverter
intensity: 75 %
Backlight
EI
intensity: 75 %
Backlight
EIA
+
-
OK
Set the backlight intensity.
Display
Contrast:8
EV
Set display
Contrast: 8
EVA +
-
OK
Password: 6802
User
EL
6802
Password
ELA
Create new user password (default 6802).
settings
Standard
EK
Reset?
EKA
OK
Reset to standard factory settings.

17
110007941
Software Manual
5.4.1 Submenu Language & Units
Languages &
L
F
units
English
Language:
FA
English
Language:
FAA +
-
OK
Metric
Units:
FB
Imperial
Units:
FBA +
-
OK
5.4.2 Submenu Supply tank
Supply
H
tank
Control: OFF
Tank
HA
Control: OFF
Tank
HAA +
-
OK
LLA Detect
Delay: 3 sec
HB
LLA Detect
Delay: 3 sec
HBA +
-
OK
5.4.3 Submenu Communication*
Communication
I
PC
*For the use of authorized Your local service technician only.
Firmware upgrade
by cable
IC
Confirm
Firmware Upgrade ?
ICA
OK
Upgrade Ready
Power Cycle and
Start PC App.
Firmware upgrade
by infrared
ID
Confirm
Firmware Upgrade ?
IDA
OK
Upgrade Ready
Power Cycle and
Start PC App.

18
110007941
Software Manual
5.4.4 Submenu I/O Settings
I/O Settings
J
Output 1
Cfg: None
JA
Output 1
Cfg: None
JAA
+
-
OK
Output 2
Cfg: None
JB
Set Output 2
Cfg: None
JBA
+
-
OK
Input
Cfg:None
JC
Set Input
Cfg: None
JCA
+
-
OK
Output 1 options:
• None – No function
• Error – Active if an error are detected
• Run/Stop – Active if booster is running and not active when it is stopped.
• Standby/o-activeifboosterisrunningorinstandby.
Output 2 options:
• None – No function
• Delaystart–Givesasignalatthisport,beforestartingthepump.
Thelengthofthedelayissetinthesettingsmenu,startupdelay.
This function could for instance be used to secure start up of prepressure pump before starting the unit.
Input
• None – No function
• Release – unit unable to start before this signal is present.
• Setpoint – Output pressure is controlled by external voltage source.
• Chem. Low - Low level in chemistry can

19
110007941
Software Manual
5.4.5 Submenu Installation
Installation
K
* For the use of authorised Your local service technician only.
5.4.6 Submenu Reset
Reset
R
D
Reset
trip counters?
DA
Reset?
DAA
OK
5.5 Content of Readings
Readings
R
Pump state
82Hz
RA
24bar
Outlet pres.
RB
29°C
Water temp.
RC
2.5 bar
Supply pressure
RD
No Flow
Flow status
RF

20
6. Upgrade Firmware
Upgrading from software 5.02 or higher.
6.1 Upgrade display using USB Cable
1. Connect USB cable (Item No. 110007947) to PC USB port (Remove other USB cables
connected to PC)
2. Connect Display cable to USB cable
3. Inthemenugoto,Setup->”password”->Communication->Firmwareupgradebycable-
>ConrmFirmwareupgradeandpress“OK”
4. Display should now be looking like this:
Upgrade Ready
Power Cycle and
Start PC App.
5. Disconnect display from usb cable and connect it again (Power cycle)
6. MakesuretheGreen“ON”ledandthered“OFF”ledatthedisplayisbothon,displayis
blank
7. StartupPCprogramFWU200.exe(canbedownloadedfromNilskFoodwebsite)
8. Window should be looking like this
9. Press ”Browse” button
10. Selecttheleyouwilluseforupgrade.SoftwareFilecanbedownloadedfromNilskFood
website.Thenameoftheleshouldendwith“.hex”.ExV5.14_SB_DISP.hex
11. Whentheleislocatedpress“Open”inbrowserwindow
12. Thelenamewillnowbewritteninletextline
110007941
Software Manual
This manual suits for next models
5
Table of contents
Other Ecolab Control Panel manuals
Popular Control Panel manuals by other brands

DITEC
DITEC LCA85 Translation of the original instructions

Siemens
Siemens CERBERUS PYROTRONICS PXL Installation, operation and maintenance manual

BMS
BMS DLC50 Installation & operation manual

Bosch
Bosch AMAX panel 2100 user manual

HKC
HKC SW-1070 installation manual

SJE Rhombus
SJE Rhombus H2O Drive RD150 user manual

Extron electronics
Extron electronics SCP 150L user manual

Bosch
Bosch ICP-SOL2-P installation guide

Siemens
Siemens SIMATIC HMI KTP400 Basic operating instructions

American DJ
American DJ TP-1201 User instructions

Prosense
Prosense S-DP32 user manual

Honeywell
Honeywell Galaxy Dimension series Integration guide