EEC EGS Series User manual

Innovation in soft start technology
EGS Series Soft Starter
QUICK START GUIDE
EGS-QSG Series. Version 01

1
EGS Series Quick Start User Manual
Version 01 - 2020
EGS Series Quick Start Guide
Electrical & Electronics Controls (EEC) Ltd.
17 & 21 Stewart Court
Orangeville, ON
L9W3Z9
Canada
www.eecontrols.ca
[Full User Manual (EGS-V01)]
© 2019 by Electrical & Electronic Controls (EEC) Ltd. All rights reserved
Copyright subsists in all EEC deliverables including magnetic, optical and/or any other soft copy of these
deliverables. This document may not be reproduced, in full or in part, without written permission. Enquiries
about copyright of EEC deliverables should be made to Electrical & Electronic Controls (EEC) Ltd. If, by
permission of the copyright owner, any part of this document is quoted, then a statement specifying the
original document shall be added to the quotation. Any such quotation shall be according to the original (text,
figure or table) and may not be shortened or modified.

2
EGS Series Quick Start User Manual
Version 01 - 2020
Important information
Installers should read and understand the instructions in this guide prior to installing, operating and maintaining
the soft start. The following symbols may appear in this guide or on the soft start to warn of potential hazards
or to draw attention to certain information.
Dangerous Voltage
Indicates the presence of a hazardous voltage which could result in personal injury or death.
Warning/Caution
Indicates a potential hazard. Any instructions that follow this symbol should be obeyed to avoid possible
damage to the equipment, and personal injury or death.
Protective Earth (Ground)
Indicates a terminal which is intended for connection to an external conductor for protection against
electric shock in case of a fault.
Caution Statements
The examples and diagrams in this manual are included solely for illustrative purposes. The information
contained in this manual is subject to change at any time and without prior notice. In no event will responsibility
or liability be accepted for direct, indirect or consequential damages resulting from the use or application of this
equipment.
EGS Series soft starts contain dangerous voltages when
connected to the mains supply. Only qualified personnel
that have been completely trained and authorised, should
carry out installation, operation and maintenance of this
equipment.
Installation of the soft start must be made in accordance
with existing local and national electrical codes and
regulations and have a minimum protection rating.
It is the responsibility of the installer to provide suitable
grounding and branch circuit protection in accordance
with local electrical safety codes.
This soft start contains no serviceable or re-usable parts.
The STOP function of the soft start does not isolate
dangerous voltages from the output of the soft start. An
approved electrical isolation device must be used to
disconnect the soft start from the incoming supply before
accessing electrical connections.
Safety

3
EGS Series Quick Start User Manual
Version 01 - 2020
Mounting
Fix the unit to a flat, vertical surface using the mounting holes (or slots) on its base-plate. The mechanical outline
diagrams, shown on Page 4, give the dimensions and mounting hole positions for each model. Ensure that:
The orientation of the unit has the ‘TOP’ uppermost.
The location allows adequate front access.
You can view the touchscreen.
Do not install other equipment that generates significant heat close to the soft starter.
Requirements for an Enclosure
For a typical industrial environment, an enclosure would provide the following:
A single location for the unit and its protection/isolation switch-gear
The safe termination of cabling and/or busbars
Means to effect proper air flow through the enclosure
Enclosure Ventilation
When fitting EEC’S EGS Series into a cabinet, ensure proper heat dissipation. The formula below can help provide
approximations of the space required. Note: These would not be required for any NEMA 1 / IP21-41 application.
Starting
Watts (EGS Soft Start) = start current(A) x start time(s) x number of starts per hour/1800
Running
Watts (EGS Soft Start) = 0.4 x running amps
Use the following formula to determine the fan requirement. An allowance has been incorporated into the
formula so that the figure for Q is the air delivery in the fan suppliers’ data.
Q = (4 x Wt / (Tmax-Tamb))
Q = Volume of air (cubic metres per hour-m3/h)
Wt = Heat produced by the unit and all other heat sources within the enclosure (Watts) Tmax = Maximum
permissible temperature within the enclosure (40°C for a fully rated EGS Soft Start
Tamb = Temperature of the air entering the enclosure (°C) [to work in CFM, substitute °F for °C. Q is now in CFM]
Altitude De-rate
Altitude above sea level 1000m (3281ft). Above 1000m de-rate by 1% of EGS Soft Start i.e. per 100m (328ft) to
a maximum altitude of 2000m (6562ft).
Ambient Temperature De-rate
-20°C (-4°F) to 40°C (104°F). Above 40°C de-rate linearly by 2% of EGS Soft Start i.e. per °C to a maximum of 60°C
(140°F).
Installation

4
EGS Series Quick Start User Manual
Version 01 - 2020
Handling
The EGS Series soft starter range comprises 3 frame sizes, with various weights and dimensions. See pages 5-7
for further information.
Prior to installing the EGS unit, the installer should carry-out a risk assessment. If considered appropriate, a
suitable handling device should be used.
Do not lift the EGS Soft Start unit by attachment to the 3-phase terminal connections or busbars.
WARNING
HANDLING AND LIFTING HAZARD
Ensure the area below any equipment is clear of all personnel and property.
Failure to follow this practice may result in death, serious injury, or damage to equipment.
Accessories
The following accessories have been developed and tested for use with the EGS Soft Start range of soft starts:
EGS-RKP Remote keypad for EGS-017A to EGS-361A. Provides remote functionality for up to 32 soft starter units.
EGS-ACU 100Vac – 240Vac power supply. Provides mains voltage control power and digital control functionality.
For use with EGS-017A to EGS-361A.
EGS-FS1 Cooling fan accessory for EGS-017A to EGS-065A only. Increases the number of starts per hour (see
page 19).
EGS-FS2 Cooling fan accessory for EGS-080A to EGS-195A only. Increases the number of starts per hour (see
page 19).
Installation (continued)

5
EGS Series Quick Start User Manual
Version 01 - 2020
Dimensions EGS-017A to EGS-065A
Weight 1.97kg [3.75lb]
ht1.97kg b)
Fitting
Installation (continued)
25mm [0.98]
25mm [0.98]
75mm [2.95]
75mm [2.95]
25mm [0.98]
[4.25]
108 [5.83]
148
[6.50]
165
[7.13]
181
[3.54]
90
Air Flow
[ ] = inch

6
EGS Series Quick Start User Manual
Version 01 - 2020
Dimensions EGS-080A to EGS-195A
Weight 6kg [13.22lb]
[ ] = inch
[5.8]
147
[9.3]
237
25mm [0.98]
100mm [3.93]
100mm [3.93]
40mm [1.57]
40mm [1.57]
100mm [3.93]
Air Flow

7
EGS Series Quick Start User Manual
Version 01 - 2020
Dimensions EGS-242A to EGS-361A
Weight 15kg [33.10lb]
[ ] = inch
125mm [4.92]
Air Flow
60mm [2.36]
60mm [2.36]
125mm [4.92]
25mm [0.98]
[6.3]
160
[2.4]
60
[6.4]
162.9
[8.07]
205
[13.1]
331
[
17.1
]
435
[
19.3
]
490

8
EGS Series Quick Start User Manual
Version 01 - 2020
Warnings
Isolation
Caution: EGS Series uses semiconductor devices in the main circuit and is not designed to provide
isolation. For this reason, isolation means must be installed in the supply circuit in accordance with the
appropriate wiring and safety regulations.
Electrical Control Supply Requirements
All electrical connections are made to power input and output terminals, control terminals and an earth
stud.
Fuse Protection
The Mains Supply and the Control Supply each require protection. Although all units have electronic
overload protection for the Soft Starter, the installer should always fit fuses, for motor protection,
between the unit and the Mains Supply, not between the unit and the motor. Semiconductor fuses can
be supplied as an option for short-circuit protection of the semiconductors. These fuses must be fitted
externally to the EGS Series chassis to comply with certain standards. It is the responsibility of the
installer and system designer/specifier to ensure that the required standards or regulations are not
affected by so doing.
Safety
EGS soft starters contain hazardous voltages when connected to the electrical power supply. Only
qualified personnel who are trained and authorized should carry out installation, operation and
maintenance of this equipment. Refer to and carefully follow all of the ‘Warnings’ section at the
beginning of this user manual, as well as other warnings and notes throughout the manual.
Electrical Supplies
The unit requires a 3-phase balanced Mains Supply to provide the power for the controlled motor, and a 24Vdc
for the internal control circuitry. The unit will not operate unless the control supply voltage is within the specified
limits.
Electrical Installation

9
EGS Series Quick Start User Manual
Version 01 - 2020
Electrical Connections
Mains Circuit Wiring Diagram
Electrical Installation (continued)
3
-
Phase
Electrical
Supply
Connections
(L1, L2, L3)
RJ45
connector
(Modbus
RTU)
USB Connector
Control
Terminals
Protection Switch Gear
(Provided by customer)
AC Induction
Motor
Connections
(T1, T2, T3)

10
EGS Series Quick Start User Manual
Version 01 - 2020
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
X
X
M
1
Protection Switch Gear
(Provided by customer)
L
N
PE
Electrical Connection
For single phase operation the mode of the soft start must be set correctly in the Advanced menu:
Protection Switch Gear
(Provided by customer)

11
EGS Series Quick Start User Manual
Version 01 - 2020
24V
COM
0V
13
D1
14
D2
22
21
Control Terminal Connections
Control Terminal Functions
#1 24Vdc Specification: See General Specification (page 19) for VA rating, residual ripple < 100mV,
spikes/switching peaks < 240mV, Turn On/Off response no overshoot of Vout, Overvoltage voltage protection
output voltage must be clamped <30Vdc
#2 The voltage applied to the digital inputs D1 and D2 must not exceed 24Vdc
#3 250Vac, 2A, Cosø =0.5
Digital Input 2 (D2) Selectable Functions
Different functions may be assigned to Digital Input 2 in the I/O menu. Available assignments are:
Reset
Hold Start Ramp
Enable
Fire Mode
In Fire Mode all trips are disabled.
Digital Outputs13,14, 21,22 Selectable Functions
The outputs may be mapped to Fault or Top-of-Ramp, Auto Reset Pending or Exceeded.
Terminal Description Default Function Selectable Note
24Vdc Control Supply +Us - No #1
0V Control Supply -Us - No
COM Digital Inputs Common - No
D1 Digital Input 1 - No #2
D2 Digital Input 2 - Yes #2
13/14 Main Contactor Control (Run Relay) - Yes #3
21/22 Fault Relay - Yes #3
Electrical Installation (continued)

12
EGS Series Quick Start User Manual
Version 01 - 2020
3-Wire Control Circuit Wiring Diagram
2-Wire Control Wiring Diagram
Electrical Installation (continued)
K1
0V
Start Stop
24V
D1
D2 13
0V COM
14
21
22
FU1
24Vdc
K1
0V
K2.2
24V
D1
D2
13
0V COM
14
21
22
FU1
24Vdc
Note: 110 – 230V
control supply possible
with optional control
supply modules - EGS-
ACU.
K2.1
K2
Start
Stop
Note:
110 – 230V control supply
possible with optional
control supply modules -
EGS-ACU.

13
EGS Series Quick Start User Manual
Version 01 - 2020
The EGS Series provides full motor overload protection, configurable through the user interface. Overload trip
settings are determined by the Motor Current setting and the Trip Class setting. Trip class choices are Class 10,
Class 20, and Class 30. The EGS Series soft starters are protected using full I2T motor overload with memory.
Please note: When the overload has tripped, there is a forced cooling time to allow the overload to recover
before the next start.
The ‘warm’ trip times are 50% of the ‘cold’ trip time
Motor Overload

14
EGS Series Quick Start User Manual
Version 01 - 2020
Display and Controls
Keypad Guidance Examples
All keys active Left & Right keys active Right, Down & Centre keys active
Note: A flashing centre button indicates that a menu item may be selected or saved.
Configuration and Parameters
Status messages
Instantaneous motor current
Control scheme: Local, Control terminal,
Modbus RTU
Motor overload level; 0 to 100%
Keypad guidance wizard: Displays which keys are valid for specific menu items
Status LED (incorporated into centre button) Green/Red
READY
32A
Local
Control keypad

15
EGS Series Quick Start User Manual
Version 01 - 2020
Operation - Local Motor Start
Example Navigation Method
Auto Application Setup
Configuration and Parameters (continued)
Quick Return to Status Screen
(Centre button to adjust)

16
EGS Series Quick Start User Manual
Version 01 - 2020
Auto Application Setup Parameter Settings
Initial
Volts
Start
Time
Stop
Time
Trip
Class
Current
Limit
Current
Limit Time
Unit % s s - *FLC s
Default 20% 10 0 10 3.5 30
Heavy 40% 10 0 20 4 40
Agitator 30% 10 0 10 3.5 25
Compressor 1 40% 15 0 20 3.5 25
Compressor 2 35% 7 0 10 3.5 25
Conveyor Loaded 10% 10 7 20 5.5 30
Conveyor Unloaded 10% 10 7 10 3.5 30
Crusher 40% 10 0 30 3.5 60
Fan High Inertia 40% 10 0 30 3.5 60
Fan Low Inertia 30% 15 0 10 3.5 30
Grinder 40% 10 0 20 3.5 40
Mill 40% 10 0 20 3.5 40
Mixer 10% 10 0 20 4 25
Moulding M/C 10% 10 0 10 4.5 25
Press Flywheel 40% 10 0 20 3.5 40
Pump 1 10% 10 60 10 3.5 25
Pump 2 10% 10 60 20 3.5 25
PumpJack 40% 10 0 20 3.5 40
SawBand 10% 10 0 10 3.5 25
SawCircular 40% 10 0 20 3.5 40
Screen Vibrating 40% 10 0 20 4.5 40
Shredder 40% 10 0 30 3.5 60
Wood Chipper 40% 10 0 30 3.5 60
Compressor 1 = Centrifugal, Reciprocating, Rotary Screw
Compressor 2 = Rotary Vane, Scroll
Pump 1 = Submersible: Centrifugal, Rotodynamic
Pump 2 = Positive Displacement: Reciprocating, Rotary
Configuration and Parameters (continued)

17
EGS Series Quick Start User Manual
Version 01 - 2020
General Specification
Product Standard EN 60947-4-2: 2012
Rated operational voltages Ue 200Vac to 600Vac (See Key to part numbers)
Rated operational current Ie See Rating Table
Rating index See Rating Table
Rated frequencies 50 - 60Hz ± 5Hz
Rated duty Uninterrupted.
Form designation Form 1, Internally Bypassed
Method of operation Symmetrically controlled starter
Method of control Semi-automatic
Method of connecting Thyristors connected between motor windings
and supply
Number of poles 3 main poles, 2 main poles controlled by
semiconductor switching element
Rated insulation voltage Ui Main circuit See Key to part
numbers
Control supply circuit 230Vac r.m.s 1)
Rated impulse withstand voltage Uimp
Main circuit 6 kV
Control supply circuit 4 kV 1)
IP code
Main circuit IP00 (IP20 with finger
guards6)
Supply and Control
circuit IP20
Overvoltage Category / Pollution degree III / 3
Rated conditional short-circuit current and type of co-ordination
with associated short circuit protective device (SCPD)
Type 1 co-ordination
See Short Circuit Protection Tables for rated
conditional short-circuit current and required
current rating and characteristics of the associated
SCPD
Technical
Information/Specification

18
EGS Series Quick Start User Manual
Version 01 - 2020
General Specification (continued)
As
Standard
Control
Supply
(2)
Supply input 0, 24V
Protect
with
UL248
listed
fuse
rated
Max 4A
Kind of current, rated
frequency dc
Rated voltage Us 24Vdc
Maximum power
consumption
12VA (EGS-017A to EGS-065A)
48VA (EGS-080A to EGS-361A)
Control
circuit (2)
Programmable opto-isolated
inputs D1, D2
Common input, marking COM
Kind of current, rated
frequency dc
Rated voltage Uc 24Vdc
With
EGS-ACU
module
Control
Supply
Supply input L, N
Kind of current, rated
frequency ac, 50 - 60Hz ± 5Hz
Rated voltage Us 110V to 230Vac
Rated input current 210mA max (cont.) 1A Peak
Control
circuit
Programmable opto-isolated
inputs D1, D2
Common input COM
Kind of current, rated
frequency ac, 50 - 60Hz ± 5Hz
Rated voltage Uc 110V to 230Vac
Auxiliary
Circuit 3)
Form A – Single gap make -contact
(normally open) 13, 14
Form B – Single gap break-contact
(normally closed) 21, 22
Utilisation category, voltage rating,
current rating
Resistive load, 250Vac, 2A.
Cosø =0.5, 250Vac, 2A 4)
Continued over
Technical Information/Specification

19
EGS Series Quick Start User Manual
Version 01 - 2020
EGS-242A – EGS-361A have permanently fitted fans
General Specification (continued)
Electronic
overload relay
with manual reset and
thermal memory
Trip Class 10 (factory default), 20 or 30 (selectable)
Current setting See Electronic Overload Relay Current Settings
Rated frequency 50 to 60Hz ± 5Hz
Time-current characteristics See Fig.1 for trip curves (Trip time Tp ± 20%)
1) With optional EGS-ACU power supply module.
2) Must be supplied by class 2, limited voltage current or protected by a 4A UL 248 listed fuse
3) Compliant with Annex S of IEC 60947-1:2007 at 24Vdc
4) Not applicable for UL
5) The safety functions were not evaluated by UL. Listing is accomplished according to requirements of Standard UL 508 and CSA14-13, general use
applications
6) For models EGS-017A to EGS-195A the main circuit IP20 rating only applies when the finger guards as supplied are fitted
7) Transient surge suppression shall be installed on the line side of this equipment and shall be rated 600_V (phase to phase), suitable for overvoltage
category III, and shall provide protection for a rated impulse withstand voltage peak of 6 kV.
Electromagnetic Compatibility
EMC Emission levels EN 55011 Class A 1
EMC Immunity levels IEC 61000-4-2 8kV/air discharge or 4kV/contact discharge
IEC 61000-4-3 10 V/m
IEC 61000-4-4 2kV/5kHz (main and power ports)
1kV/5kHz (signal ports)
IEC 61000-4-5 2kV line-to-ground
1kV line-to-line
IEC 61000-4-6 10V
1 NOTICE: This product has been designed for environment A. Use of this product in environment B may cause
unwanted electromagnetic disturbances, in which case the user may be required to take adequate mitigation
measures
Fan Option
EGS Series model Maximum duty cycle F-S with optional fan fitted
EGS-017A - EGS-100A 90-40 (40 cycles per hour)
EGS-125A 90-30 (30 cycles per hour)
EGS-160A 90-20 (20 cycles per hour)
EGS-195A 90-10 (10 cycles per hour)
Technical Information/Specification
This manual suits for next models
15
Table of contents
Popular Software manuals by other brands

Snom
Snom Configuring snom phones for Mass Deployment Frequently asked questions

Red Hat
Red Hat LINUX 7.2 - OFFICIAL LINUX CUSTOMIZATION... manual

Ericsson GE
Ericsson GE EDACS LBI-39077 user guide

Canon
Canon PowerShot G10 - Digital Camera - Compact Software user's guide

Sanyo
Sanyo PLC-XU300 owner's manual

HP
HP ProLiant ML310 Generation 5p user guide

Canon
Canon 2MC - Elura 2MC MiniDV Digital Camcorder instruction manual

NEC
NEC Storage Manager Configuration Setting Tool user's manual

KIP
KIP TASKalfa 2420w Operation guide

Buffalo
Buffalo Turbo USB Utility HD-HSU2 product manual

Texas Instruments
Texas Instruments DSP/BIOS Real-Time Analysis (RTA) user manual

Lenovo
Lenovo ThinkPad L410 Deployment guide