Ekinex KNX EK-CA1-TP User manual

1
8-fold analog/binary input
Product code: EK-CA1-TP
on the bus. The telegram is received and executed by
one or more KNX actuators. The device is powered by the
KNX bus line with SELV voltage 30 Vdc and requires no
auxiliary power supply. The scanning voltage for the input
connections is produced inside the device.
Main functional characteristics
Each input of the device can be programmed as [DI] to
carry out the function of:
• on/off switching of single loads or group of loads;
• detecting the state of signaling contacts (from safety
devices, alarms, etc.);
• recalling and saving of scenes;
• sending on the bus of values (temperature, brightness,
etc.);
• switching to forced operating mode (lock);
• counting of impulses and switching cycles.
Each pair of inputs can be furthermore programmed for:
• dimming of lighting devices;
• controlling drives for shading devices (such as shutters,
blinds, curtains, etc.).
As an alternative to programming it as [DI], each input 1B,
2B, 3B, 4B can be programmed as [AI] for:
• measuring of the air mass temperature with a NTC pas-
sive temperature sensor (NTC 10 kΩ at 25 °C) to be
connected to the input with possibility of sending the
value on the bus;
• 2 points (ON / OFF) or proportional (PWM or con-
tinuous) room temperature regulation. The device
is provided with 2 conduction modes (heating and
cooling) with switching via bus and 4 operating modes
(comfort, standby, economy and building protection)
with separate setpoints for heating and cooling.
Automatic switching function of the operating mode
depending on presence or opening windows. The re-
gulation may work with a weighted average of the two
temperature values.
Finally, it is possible to congure up to 4 logic functions
(AND, OR or XOR) with 4 logic objects in input each.
Other characteristics
• Housing in plastic material
• Mounting on 35 mm rail (according to EN 60715)
• Protection degree IP20 (according to EN 60529)
• Overvoltage class III (according to EN 60664-1)
• Classication climatic 3K5 and mechanical 3M2 (accor-
ding to EN 50491-2)
• Pollution degree 2 (according to IEC 60664-1)
• 4 modular units (1 unit = 18 mm)
• Weight 145 g
• Dimensions 72 x 90 x 70 mm (WxHxD)
Technical data
• 30 Vdc from KNX bus line
• Current consumption from bus < 13 mA
• Power consumption 320 mW
Inputs
• Number: 8
• Scanning voltage: > 11 V
• Scanning current: > 5 mA
• Maximal lenght of the connection cable: 10 m (with ca-
ble section 0,8 mm²)
KNX device for connecting of up to 8 conventional (not
KNX) switches, pushbuttons or 4 analog sensors. It has
to be used in KNX installations for control of homes and
buildings.
Description
The ekinex®8-fold analog/binary input EK-CA1-TP is a
S-mode KNX modular device for rail mounting for con-
nection to the bus of switches and sensors of conven-
tional type (not communicating natively on the KNX bus)
equipped with potential-free contacts, or NTC passive
temperature sensors. By means of the binary input is pos-
sible to switch and control KNX bus functions with nor-
mal switches, pushbuttons and sensors or binary signals
made available by other devices. In addition, it is possi-
ble to acquire room temperature values, so it can also be
used as a room thermostat for up to 4 independent zones.
The binary input can be used as follows:
- 8 independent inputs for potential-free contacts, for
example for the connection of traditional (not bus)
switches or pushbuttons dedicated to the switching on/
off of loads;
- 4 individually congurable inputs for NTC temperature
sensors;
- 4 independent channels, for example for the connec-
tion of traditional (not bus) pushbuttons for the control
of dimmer or motorized drives.
The device is equipped with an integrated bus communi-
cation module and is designed for rail mounting in distri-
bution boards. To operate the device receives an input
signal and converts it into a corresponding telegram sent
REAEKCA1TP
Datasheet STEKCA1TP_EN
TP1
S
2
Mounting
The device has degree of protection IP20, and is there-
fore suitable for use in dry interior rooms. The housing is
made for rail mounting according to EN 60715 in boards
or cabinets for electrical distribution. The installation is in
horizontal position, the correct position is when the KNX
bus terminal is located at the bottom and the terminals for
the inputs are located at the top. For the installation of the
device on the rail proceed as follows:
• with the aid of a tool bring the locking device in the fully
lowered position (1);
• place the upper edge of the rear inner prole on the
upper edge of the rail (2);
• rotate the device towards the rail (3);
• push the locking device upward until it stops (4).
Before removing the device, be sure the inputs have been
disconnected and the bus terminal has been extracted
from its slot. Use a screwdriver to slide down the locking
device and remove the device from the rail.
Environmental conditions
• Operating temperature: - 5 ... + 45°C
• Storage temperature: - 25 ... + 55°C
• Transport temperature: - 25 ... + 70°C
• Relative humidity: 95% not condensing
Switching, display and connection elements
The device is equipped with a programming pushbutton
and a programming LED, membrane pushbuttons, LED
for status indication and terminals for connecting the KNX
bus line and the inputs.
Switching elements
• Pushbutton (3) for switching between the normal and
programming operating mode
• Pushbutton (6) for switching between the operating mo-
des: forced (pushbuttons on the front panel: active) or
automatic (pushbuttons on the front panel: not active)
• Pushbuttons (2) for forced operation of the input con-
nections
Switching to the forced operation mode allows to simulate
the state of the inputs with the pushbuttons on the front
panel of the device; in this way it is possible to test the
correct operation of the coordinated loads before connec-
ting any device to the input terminal blocks.
Display elements
• Red LED (4) for displaying the active operating mode of
the device (on = programming, off = normal operation)
• Green LEDs (8) for displaying the switching status of
the input channels (on = closed contact, off = opened
contact)
• Red LED (7) for displaying the operating mode (on =
forced operation, off = automatic operation)
Connection of the KNX bus line
The connection of the KNX bus line is made with the ter-
minal block (black/red) included in delivery and inserted
into the slot of the housing.
Characteristics of the KNX terminal block
• spring clamping of conductors
• 4 seats for conductors for each polarity
• terminal suitable for KNX bus cable with single-wire
conductors and diameter between 0.6 and 0.8 mm
• recommended wire stripping approx. 5 mm
• color codication: red = + (positive) bus conductor,
black = - (negative) bus conductor
1 2
43
EKINSTGUIDAEKAB1TP
Warning! In order to supply the KNX bus lines use
only a KNX bus power supply (e.g. ekinex EK-AB1-
TP or EK-AG1-TP). The use of other power supplies
can compromise the communication and damage
the devices connected to the bus.
!
Note. In case of failure of bus voltage, the control of
the loads is not possible with the devices connected
to the binary input. It is still possible if the coordina-
ted KNX actuators are equipped with pushbuttons
or other control manual devices and is present the
mains voltage 230 Vac.
i
Note. It is recommended that the installation of the
device always ensure the full accessibility of the
front side to allow the operation of the membrane
pushbuttons.
i
1 2
1A 34
2A 5 6
3A 78
4A
910
1B 11 12
2B 13 14
3B 15 16
4B
1B 2B 3B 4B
1A 2A 3A 4A
EK-CA1-TP
8xD.I. Dry Contacts
bus KNX
1) Terminal blocks for inputs
2) Pushbuttons for forced operation of the inputs
3) Programming pushbutton
4) Programming LED
5) Terminal block for KNX bus line
6) Pushbutton for toggling between manual and automatic operation
7) LED for indication forced / automatic operation mode
8) LED for status indication of the inputs
DCEKCA1TP
1
2
4
5
7
6
3
8
3
Connection of the inputs
The connection of the inputs (g. b, c, d) is made with the
screw terminals located at the top.
Conguration and commissioning
Conguration and commissioning of the device require
the use of the ETS®(Engineering Tool Software) program
V4 or later releases. These activities must be carried out
according to the design of the building automation system
done by a qualied planner.
Commissioning
For commissioning the device the following activities are
required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming mode
by pressing the programming pushbutton located on
the front side of the housing. In this mode of operation,
the programming LED is turned on;
• download into the device the physical address and the
conguration with the ETS®program.
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED is turned off. Now the bus device is
programmed and ready for use.
Product
code
Application
program (## =
release)
Communica-
tion objects
(max nr.)
Group
adressses
(max nr.)
EK-CA1-TP
APEKCA1TP##.knxprod
430 254
Conguration
For the conguration of the device parameters the corre-
sponding application program or the whole ekinex®pro-
duct database must be loaded in the ETS program. For
detailed information on conguration options, refer to the
application manual of the device available on the website
www.ekinex.com
Characteristics of the terminals
• screw clamping of conductors
• maximum cross section of conductor 2.5 mm² (single-
wire) or 1.5 mm² (multi-wire)
• recommended wire stripping approx. 6 mm
• torque max 0.8 Nm
1 2
1A 34
2A 5 6
3A 78
4A
910
1B 11 12
2B 13 14
3B 15 16
4B
1B 2B 3B 4B
1A 2A 3A 4A
EK-CA1-TP
8xD.I. Dry Contacts
bus KNX
+
-
KNX
bus
a Connection of the KNX bus network
Note. The conguration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tied training centers.
i
Warning! The electrical connection of the device
can be carried out only by qualied personnel. The
incorrect installation may result in electric shock or
re. Before making the electrical connections, make
sure the power supply has been turned off.
!
b
Connection for 8 independent inputs for potential-free contacts, e.g., for tra-
ditional (not bus) switches or pushbuttons dedicated to the on/off switching
of loads
c
Connection as 4 pairs of inputs (coupled inputs for dimming of lighting devi-
ces or controlling drives for shading devices, such as shutters, blinds, cur-
tains, etc.
21 1A 43 2A 65 3A 87 4A 109 1B 1211 2B 1413 3B 1615 4B
ca1 4can
L
21 1A
109 1B
43 2A
1211 2B
65 3A
1413 3B
87 4A
1615 4B
ca1 4can
dCollegamento come 4 ingressi congurabili singolarmente per sonde di tem-
peratura passive (NTC 10 kΩ a 25 °C).
Warning! If congured as analog input, the
connection of a NTC temperature sensor with a
characteristic resistance value of 10 kΩ at 25°C,
β = 3435 is allowed only.
!
4
72 525 20 20
70
90
45
1 2
1A
3 4
2A
56
3A
7 8
4A
910
1B
11 12
2B
13 14
3B
15 16
4B
1B 2B 3B 4B
1A 2A 3A 4A
EK-CA1-TP
8xD.I. Dry Contacts
bus KNX
DQEKCA1TP
Dimensions [mm]
Marks
• KNX
• CE: the device complies with the Electromagnetic
Compatibility Directive (2014/30/UE). Tests carried out
according to EN IEC 63044-5-1:2019, EN 63044-5-
2:2019.
Maintenance
The device is maintenance-free. To clean use a dry cloth.
It must be avoided the use of solvents or other aggressive
substances.
Disposal
At the end of its useful life the product
described in this datasheet is classied
as waste from electronic equipment in
accordance with the European Direc-
tive 2002/96/EC (WEEE), and cannot
be disposed together with the munici-
pal undifferentiated solid waste.
Warning! Incorrect disposal of this product may
cause serious damage to the environment and hu-
man health. Please be informed about the correct
disposal procedures for waste collecting and pro-
cessing provided by local authorities.
!
Documentation
This datasheet refers to the release A1.0 of the ekinex®
device EK-CA1-TP, and is available for download at www.
ekinex.com as a PDF (Portable Data Format) le.
File name Device release Updating
STEKCA1TP_IT.pdf A1.0 01 / 2022
Warnings
• Installation, electrical connection, conguration and
commissioning of the device can only be carried out by
qualied personnel in compliance with the applicable
technical standards and laws of the respective countri-
es
• The use of the device in security applications is not al-
lowed. The device may however be used for auxiliary
signaling functions
• Opening the housing of the device causes the imme-
diate end of the warranty period
• In case of tampering, the compliance with the essential
requirements of the applicable directives, for which the
device has been certied, is no longer guaranteed
• ekinex®KNX defective devices must be returned to the
manufacturer at the following address: EKINEX S.p.A.
Via Novara 37, I-28010 Vaprio d’Agogna (NO) Italy
Other information
• This datasheet is aimed at installers, system integra-
tors and planners
• For further information on the product, please contact
the ekinex®technical support at the e-mail address:
[email protected] or visit the website www.ekinex.
com
• Each ekinex®device has a unique serial number on
the label. The serial number can be used by installers
or system integrators for documentation purposes and
has to be added in each communication addressed to
the EKINEX technical support in case of malfunctioning
of the device
• KNX®and ETS®are registered trademarks of KNX As-
sociation cvba, Brussels
© EKINEX S.p.A. The company reserves the right to make changes to
this documentation without notice.

Other Ekinex Switch manuals

Ekinex 71 Series User manual

Ekinex

Ekinex 71 Series User manual

Ekinex EK-FA1-TP User manual

Ekinex

Ekinex EK-FA1-TP User manual

Ekinex EK-TM1-TP User manual

Ekinex

Ekinex EK-TM1-TP User manual

Popular Switch manuals by other brands

Gigafast EF800-SI manual

Gigafast

Gigafast EF800-SI manual

HP V1810-48G Quickspecs

HP

HP V1810-48G Quickspecs

Aeon Labs Aeotec Micro Smart Energy Switch G2 manual

Aeon Labs

Aeon Labs Aeotec Micro Smart Energy Switch G2 manual

NETGEAR FS728TP - ProSafe 24 Port 10/100 Smart... installation guide

NETGEAR

NETGEAR FS728TP - ProSafe 24 Port 10/100 Smart... installation guide

Doepke DASY 10-2/24V Installation and operating instructions

Doepke

Doepke DASY 10-2/24V Installation and operating instructions

StarTech.com DS254 Spec sheet

StarTech.com

StarTech.com DS254 Spec sheet

Roland V-1SDI owner's manual

Roland

Roland V-1SDI owner's manual

Bome BomeBox quick start guide

Bome

Bome BomeBox quick start guide

3Com SuperStack 3 4300 datasheet

3Com

3Com SuperStack 3 4300 datasheet

Siemens SCALANCE X-200 operating instructions

Siemens

Siemens SCALANCE X-200 operating instructions

Lantronix SISGM1040-284-LRT quick start guide

Lantronix

Lantronix SISGM1040-284-LRT quick start guide

Sygonix 1423284 operating instructions

Sygonix

Sygonix 1423284 operating instructions

BayTech DS3 owner's manual

BayTech

BayTech DS3 owner's manual

Extron electronics IN1606 user guide

Extron electronics

Extron electronics IN1606 user guide

Cisco 3524-PWR - Catalyst XL Enterprise Edition... datasheet

Cisco

Cisco 3524-PWR - Catalyst XL Enterprise Edition... datasheet

Extron electronics IN1806 Series user guide

Extron electronics

Extron electronics IN1806 Series user guide

Oton Geek N8 user manual

Oton

Oton Geek N8 user manual

TRENDnet TEG-S2600I - 10/100Mbps Switch With Mini-GBIC... Specifications

TRENDnet

TRENDnet TEG-S2600I - 10/100Mbps Switch With Mini-GBIC... Specifications

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.